Description

Schneider GV3P50 | Motor circuit breaker, TeSys GV3, 3P, 37-50 A, thermal magnetic, EverLink terminals

Technical Specifications

  • Model: Schneider GV3P50

  • Series: TeSys GV3

  • Type: Motor Circuit Breaker

  • Number of Poles: 3P (Three-phase)

  • Current Rating: Adjustable 37-50A

  • Protection Type: Thermal-magnetic

  • Connection Type: EverLink terminals

  • Breaking Capacity: High-performance short-circuit protection

  • Mounting: DIN rail or panel mounting

Key Features

  1. Reliable Motor Protection (37-50A Range)

    • Adjustable thermal protection against overloads.

    • Magnetic protection ensures quick disconnection during short circuits.

  2. EverLink Terminals for Secure Connections

    • Reduces the risk of connection failures due to vibrations.

    • Provides stable and durable wiring in harsh environments.

  3. High Breaking Capacity

    • Protects motors from high short-circuit currents, ensuring system safety.

    • Ensures fast and efficient fault clearance.

  4. Compact and Modular Design

    • Space-saving design allows for easy integration into electrical panels.

    • Supports DIN rail and panel mounting for flexible installation.

  5. Built for Industrial Applications

    • Withstands high electrical and mechanical stress.

    • Ensures long-lasting performance in demanding conditions.

Applications

  • Industrial Motor Protection: Safeguards pumps, compressors, conveyors, and fans.

  • Manufacturing & Automation: Ensures reliable motor operation in production lines.

  • HVAC Systems: Protects motors in heating, ventilation, and air conditioning units.

  • Agriculture & Irrigation: Secures water pumps and farming equipment motors.

Additional information

brands

Schneider Electric

Specifications

Main
Range TeSys Deca
Product name TeSys GV3 TeSys Deca
Product or component type Motor circuit breaker
Device short name GV3P
Device application Motor protection
Trip unit technology Thermal-magnetic
Complementary
poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Fixing mode 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws)
Motor power kW 22 kW at 400/415 V AC 50/60 Hz 30 kW at 500 V AC 50/60 Hz 45 kW at 690 V AC 50/60 Hz
Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type Rotary handle
[In] rated current 50 A
Thermal protection adjustment range 37…50 A conforming to IEC 60947-4-1
Magnetic tripping current 700 A
[Ith] conventional free air thermal current 50 A conforming to IEC 60947-4-1
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Suitability for isolation Yes conforming to IEC 60947-1
Power dissipation per pole 8 W
Mechanical durability 50000 cycles
Electrical durability 50000 cycles for AC-3 at 415 V In
Rated duty Continuous conforming to IEC 60947-4-1
Tightening torque 5 N.m - on screw clamp terminal
Width 55 mm
Height 132 mm
Depth 136 mm
Net weight 0.96 kg
Colour Dark grey
Environment
Standards EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1
Product certifications CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV ABS DNV-GL UKCA
IK degree of protection IK09 enclosure
IP degree of protection IP20 conforming to IEC 60529
Climatic withstand Conforming to IACS E10
ambient air temperature for storage -40…80 °C
Fire resistance 960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation -20…60 °C
Mechanical robustness Shocks: 15 Gn for 11 ms contactor open Shocks: 30 Gn for 11 ms contactor closed Vibrations: 4 Gn, 5...300 Hz
Operating altitude 3000 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 16.000 cm
Package 1 Width 6.500 cm
Package 1 Length 14.500 cm
Package 1 Weight 1.008 kg
Unit Type of Package 2 P06
Number of Units in Package 2 120
Package 2 Height 75.000 cm
Package 2 Width 60.000 cm
Package 2 Length 80.000 cm
Package 2 Weight 136.960 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider GV3P50 | Motor circuit breaker, TeSys GV3, 3P, 37-50 A, thermal magnetic, EverLink terminals”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare