Description

Schneider A9K01420 | Acti9 K60N 4P – 20A – B curve 6000 A

The Schneider A9K01420  circuit breaker is a highly reliable solution for protecting electrical circuits from overloads and short circuits. It features a four-pole (4P) design, making it suitable for three-phase electrical systems with a neutral wire. The B curve characteristic allows it to respond quickly to minor current surges, making it ideal for applications with low inrush currents, such as lighting systems and electronic control devices.

2. Technical Specifications of Schneider A9K01420

  • Rated Current: 20 Amps.
  • Number of Poles: 4 poles (4P).
  • Curve Type: B curve (responds quickly to slight current increases, ideal for sensitive loads).
  • Maximum Short-Circuit Breaking Capacity: 6000 Amps.
  • Electrical Rating: Provides protection against overloads and short circuits.
  • Operating Voltage: Compatible with low-voltage electrical systems in industrial and commercial setups.
  • Protection Class: IP20 (offers adequate protection against environmental factors).

3. Key Features:

  • Reliable Protection: Prevents damage caused by overloads and short circuits, ensuring electrical system safety.
  • Fast Response: The B curve characteristic allows the breaker to trip quickly at slight overcurrents, making it ideal for sensitive loads.
  • Four-Pole Design (4P): Provides comprehensive protection for three-phase circuits with a neutral wire.
  • Easy Installation and Maintenance: The compact design enables quick and hassle-free installation.
  • Long Operational Life: Designed to withstand varying operating conditions, ensuring durability.
  • High Breaking Capacity: Can handle short-circuit currents of up to 6000 A, ensuring effective circuit protection.

4. Applications:

  • Protection of Low-Inrush Current Circuits: Suitable for circuits containing electronic devices and low-inrush current loads, such as lighting systems.
  • Residential and Commercial Buildings: Used in electrical distribution networks to ensure circuit safety in homes, offices, and commercial establishments.
  • Control and Electronics Systems: Ideal for protecting sensitive electronic equipment requiring a rapid response to overcurrent conditions.
  • Low-Voltage Power Distribution Systems: Used in electrical panels for effective protection of small to medium loads.

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
product name Acti9 K60
Product or component type Miniature circuit-breaker
Device short name K60N
Poles description 4P
Number of protected poles 4
[In] rated current 20 A
network type AC
Trip unit technology Thermal-magnetic
Curve code B
Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilisation category Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN/IEC 60898-1
Standards EN/IEC 60898-1
Product certifications VDE
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 3...5 x In
[Ics] rated service breaking capacity 6000 A 100 % conforming to EN/IEC 60898-1 - 400 V AC 50/60 Hz
Limitation class 3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage 440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage 4 kV conforming to EN/IEC 60898-1
Contact position indicator No
control type Toggle
Local signalling Without
Mounting mode Fixed
Mounting support DIN rail
Comb busbar and distribution block compatibility Downside: biconnect
9 mm pitches 8
Height 81 mm
Width 72 mm
Depth 70 mm
Product weight 0.48 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 20000 cycles
Connections - terminals Tunnel type terminals (downstream) 0.5…35 mm² rigid
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom
Earth-leakage protection Without
Environment
IP degree of protection IP20 conforming to IEC 60529
Pollution degree 2 conforming to IEC 60898-1
overvoltage category II
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0...2000 m
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -25…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.2 cm
Package 1 Width 7.08 cm
Package 1 Length 8.1 cm
Package 1 Weight 0.41 kg

Reviews (0)

Be the first to review “Schneider A9K01420 | Acti9 K60N 4P – 20A – B curve 6000 A”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare