Schneider C063H420FM | Circuit breaker, ComPacT NS630bH, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 630A
Schneider C063H420FM | Circuit breaker, ComPacT NS630bH, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 630A
Description
Schneider C063H420FM | Circuit breaker, ComPacT NS630bH, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 630A
Technical Specifications:
-
Brand: Schneider Electric
-
Product Code: C063H420FM
-
Series: ComPacT NS630bH
-
Type: Molded Case Circuit Breaker (MCCB)
-
Rated Current (In): 630 Amps
-
Number of Poles: 4 Poles
-
Breaking Capacity (Icu): 70 kA at 415 V AC
-
Rated Operating Voltage (Ue): Up to 690 V AC
-
Rated Insulation Voltage (Ui): 800 V AC
-
Trip Unit: MicroLogic 2.0 (electronic, adjustable protection)
-
Mounting Type: Fixed
-
Operation Mode: Manually operated
-
Conformity Standards: IEC 60947-2
-
Protection Class: Typically IP40 (with enclosure

Key Features:
-
High interrupting capacity (70kA) to ensure safety under extreme fault conditions.
-
MicroLogic 2.0 trip unit provides advanced electronic protection with precision settings for overload and short circuit.
-
4-pole design offers neutral protection, ideal for unbalanced loads or sensitive installations.
-
Compact dimensions with robust mechanical construction for long-term performance.
-
Fixed mounting for cost-effective and secure installation.
Typical Applications:
-
Power distribution panels in industrial and commercial buildings.
-
Renewable energy systems where high fault levels require solid protection.
-
Hospitals, airports, and data centers with sensitive load profiles and neutral protection requirements.
-
Backup systems and generators for critical infrastructure.
-
Heavy-duty machinery protection in manufacturing environments.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 630 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category B |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H 70 kA 415 V AC |
| Trip unit name | MicroLogic 2.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LI |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2 |
| Power losses | 10 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time) I : for instantaneous short-circuit protection |
| Trip unit rating | 630 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
| Earth-leakage protection | Without |
| Neutral protection setting | No protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D) |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication 1 LED (yellow) for overload |
| Width (W) | 280 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 18 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 37.0 cm |
| Package 1 Width | 38.0 cm |
| Package 1 Length | 30.0 cm |
| Package 1 Weight | 15.892 kg |
Download Cataloge
Download Cataloge
Download Cataloge
Download Cataloge
Reviews (0)
Recommended for you
-
0
Schneider A9N18569 | Vigi C120 – earth leakage add-on block – 4P – 30 mA – class AC
-
0
Schneider A9N18469 | Miniature circuit-breaker, Acti9 C120H, 3P, 100 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18447 | Miniature circuit-breaker, Acti9 C120H, 1P, 100 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18446 | Miniature circuit-breaker, Acti9 C120H, 1P, 80 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18369 | Miniature circuit-breaker, Acti9 C120N, 3P, 125 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.