Schneider LC1D150E7 Contactor | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 150 A – 48 V AC 50/60 Hz coil
Schneider LC1D150E7 Contactor
Description
Schneider LC1D150E7 Contactor: Streamlining Electrical Operations
Introduction to Schneider LC1D150E7 Contactor
In the realm of electrical engineering and automation, the Schneider LC1D150E7 Contactor stands out as a reliable and efficient solution for controlling electric circuits. Whether in industrial plants, commercial buildings, or residential setups, this contactor plays a crucial role in ensuring smooth electrical operations.
What is a Contactor?
A contactor is an electromechanical device used to make or break electrical connections. It is typically employed in applications where large currents need to be controlled, such as switching motors, heaters, lighting, and other heavy-duty electrical loads.
Overview of Schneider LC1D150E7 Contactor
The Schneider LC1D150E7 Contactor is designed to meet the demanding requirements of modern electrical systems. With its robust construction and advanced features, it provides reliable performance in a wide range of applications.
Features
- High-quality construction for durability and reliability.
- Rated operational current of 150A, suitable for heavy-duty applications.
- Coil voltage options available for compatibility with various control systems.
- Compact design for easy integration into electrical panels.
Specifications
- Rated Operational Voltage: Up to 690V AC.
- Number of Poles: 3.
- Coil Voltage: 24V AC.
- Maximum Operating Frequency: 600 cycles per hour.
Applications
The Schneider LC1D150E7 Contactor finds its utility across diverse sectors:
Industrial Use: In industrial settings, it is used for controlling motors, pumps, conveyors, and other equipment.
Commercial Use: In commercial buildings, it helps manage HVAC systems, lighting, and other electrical loads.
Residential Use: In homes, it can be employed for controlling appliances like air conditioners, water heaters, and electric gates.
Advantages
Efficiency: The contactor ensures efficient operation of electrical systems, reducing energy wastage and optimizing performance.
Durability: Built to withstand harsh environments and heavy usage, it offers long-term reliability and durability.
Safety: With built-in safety features such as overload protection and arc suppression, it helps prevent accidents and equipment damage.
Installation Guide
Installing the Schneider LC1D150E7 Contactor is a straightforward process:
- Ensure power supply is turned off.
- Mount the contactor securely on a DIN rail or panel.
- Connect the control circuit wires to the appropriate terminals.
- Connect the power circuit wires to the main terminals.
- Secure all connections and ensure proper insulation.
- Power on the system and test the contactor for functionality.
Safety Precautions:
- Always follow local electrical codes and regulations.
- Use appropriate personal protective equipment (PPE) when working with electrical components.
- Double-check all connections before energizing the system.
Maintenance Tips
To ensure optimal performance and longevity of the Schneider LC1D150E7 Contactor, follow these maintenance tips:
- Conduct regular visual inspections for signs of wear or damage.
- Clean the contactor contacts and terminals periodically to remove dust and debris.
- Check for loose connections and tighten them if necessary.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | TeSys |
|---|---|
| Range of product | TeSys Deca |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load Motor control |
| Utilisation category | AC-1 AC-4 AC-3 AC-3e |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: <= 1000 V AC 25...400 Hz Power circuit: <= 300 V DC |
| [Ie] rated operational current | 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 150 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| [Uc] control circuit voltage | 48 V AC 50/60 Hz |
| Motor power kW | 40 kW at 220...230 V AC 50/60 Hz (AC-3) 75 kW at 380...400 V AC 50/60 Hz (AC-3) 80 kW at 415...440 V AC 50/60 Hz (AC-3) 90 kW at 500 V AC 50/60 Hz (AC-3) 100 kW at 660...690 V AC 50/60 Hz (AC-3) 75 kW at 1000 V AC 50/60 Hz (AC-3) 22 kW at 400 V AC 50/60 Hz (AC-4) 40 kW at 220...230 V AC 50/60 Hz (AC-3e) 75 kW at 380...400 V AC 50/60 Hz (AC-3e) 80 kW at 415...440 V AC 50/60 Hz (AC-3e) 90 kW at 500 V AC 50/60 Hz (AC-3e) 100 kW at 660...690 V AC 50/60 Hz (AC-3e) 75 kW at 1000 V AC 50/60 Hz (AC-3e) |
|---|---|
| Motor power hp | 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1660 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1400 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 250 A 40 °C - 10 min for power circuit 580 A 40 °C - 1 min for power circuit 1200 A 40 °C - 10 s for power circuit 1400 A 40 °C - 1 s for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 315 A gG at <= 690 V coordination type 1 for power circuit 250 A gG at <= 690 V coordination type 2 for power circuit |
| Average impedance | 0.6 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 24 W AC-1 13.5 W AC-3 13.5 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.85 Mcycles 150 A AC-3 at Ue <= 440 V 1 Mcycles 200 A AC-1 at Ue <= 440 V 0.85 Mcycles 150 A AC-3e at Ue <= 440 V |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.3...0.5 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.15 Uc (-40…55 °C):operational AC 50/60 Hz 1...1.15 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.9 (at 20 °C) 280…350 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.9 (at 20 °C) 2…18 VA 50 Hz cos phi 0.9 (at 20 °C) |
| Heat dissipation | 3…4.5 W at 50/60 Hz |
| Operating time | 20...35 ms closing 40...75 ms opening |
| Maximum operating rate | 1200 cyc/h 60 °C |
| Maximum operating rate | 1200 cyc/h at 60 °C |
| Connections - terminals | Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 10…120 mm² - cable stiffness: solid without cable end Power circuit: connector 2 10…50 mm² - cable stiffness: solid without cable end |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate Rail |
| Standards | CSA C22.2 No 14 EN 60947-4-1 IEC 60947-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 |
|---|---|
| Product certifications | UL CCC CSA CE UKCA Marine EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor closed (15 Gn for 11 ms) Shocks contactor open (6 Gn for 11 ms) |
| Height | 158 mm |
| Width | 120 mm |
| Depth | 136 mm |
| Net weight | 2.5 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.500 cm |
| Package 1 Width | 19.000 cm |
| Package 1 Length | 20.500 cm |
| Package 1 Weight | 2.492 kg |
| Unit Type of Package 2 | S06 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 49.870 kg |
| Warranty | 18 months |
|---|
Main documents
Main documents
Reviews (0)
Recommended for you
-
0
Schneider LC1D65AQ7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 65 A – 380 V AC 50/60 Hz coil
-
0
Schneider LC1D80M7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 80 A – 220 V AC 50/60 Hz coil
-
0
Schneider LC1D80Q7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 80 A – 380 V AC 50/60 Hz coil
-
0
Schneider LC1D95E7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 95 A – 48 V AC 50/60 Hz coil
-
0
Schneider LC1D95F7 | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 95 A – 110 V AC 50/60 Hz coil
-
0