Schneider ATS480M10Y | Soft starter, Altistart 480, 1000A, 208 to 690V AC, control supply 110 to 230V AC
Description
Schneider ATS480M10Y| Soft starter, Altistart 480, 1000A, 208 to 690V AC, control supply 110 to 230V AC
Schneider ATS480M10Y | Soft Starter Overview
The Schneider ATS480M10Y is a high-performance soft starter from the Altistart 480 series, designed for motor control applications requiring smooth acceleration and deceleration. This device ensures reduced mechanical stress on motors and electrical networks, making it ideal for industrial applications.
1. General Specifications
-
Product Name: Schneider ATS480M10Y
-
Series: Altistart 480
-
Function: Soft Starter
-
Rated Current: 1000A
-
Operating Voltage: 208V to 690V AC
-
Control Supply Voltage: 110V to 230V AC
2. Features & Benefits
Smooth Motor Start & Stop: Reduces mechanical shocks, extending motor lifespan.
Wide Voltage Range: Compatible with multiple power systems (208V – 690V AC).
Energy Efficiency: Minimizes inrush current, reducing power consumption.
Integrated Protections: Provides motor and system protection, preventing overheating and overloading.
User-Friendly Interface: Simple configuration and monitoring via built-in digital display.
Network Compatibility: Supports industrial communication protocols for easy integration.
3. Applications
🔹 Industrial Machinery – Pumps, compressors, conveyors
🔹 HVAC Systems – Fans, blowers
🔹 Water & Wastewater – Large water pumps, treatment facilities
🔹 Mining & Heavy Industry – Crushers, mills
🔹 Oil & Gas Sector – Pipeline systems, drilling equipment
4. Protection & Safety
-
Overload Protection – Prevents excessive current draw
-
Short Circuit Protection – Enhances system safety
-
Overtemperature Protection – Prevents damage from excessive heat
-
Phase Loss & Imbalance Detection – Ensures stable motor operation
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Altivar Soft Starter ATS480 |
|---|---|
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Process and infrastructures |
| Device short name | ATS480 |
| Network number of phases | 3 phases |
| Utilisation category | AC-3A AC-53A |
| Ue power supply voltage | 208...690 V - 15...10 % |
| power supply frequency | 50...60 Hz - 20...20 % |
| [Ie] rated operational current | Normal duty: 1000.0 A (at <40 °C) |
| rated current in heavy duty | 790.0 A at 40 °C for heavy duty |
| Torque control | True |
| IP degree of protection | IP00 |
| Motor power kW | 250.0 kW at 230 V in the motor supply line normal duty 220.0 kW at 230 V in the motor supply line heavy duty 500.0 kW at 400 V in the motor supply line normal duty 400.0 kW at 400 V in the motor supply line heavy duty 630.0 kW at 440 V in the motor supply line normal duty 500.0 kW at 440 V in the motor supply line heavy duty 630.0 kW at 500 V in the motor supply line normal duty 500.0 kW at 500 V in the motor supply line heavy duty 630.0 kW at 525 V in the motor supply line normal duty 500.0 kW at 525 V in the motor supply line heavy duty 900.0 kW at 660 V in the motor supply line normal duty 710.0 kW at 660 V in the motor supply line heavy duty 900.0 kW at 690 V in the motor supply line normal duty 710.0 kW at 690 V in the motor supply line heavy duty 355.0 kW at 230 V to the motor delta terminals heavy duty 710.0 kW at 400 V to the motor delta terminals normal duty 630.0 kW at 400 V to the motor delta terminals heavy duty |
| Motor power hp | 350.0 hp at 208 V normal duty 250.0 hp at 208 V heavy duty 350.0 hp at 230 V normal duty 300.0 hp at 230 V heavy duty 800.0 hp at 460 V normal duty 600.0 hp at 460 V heavy duty 1000.0 hp at 575 V normal duty 800.0 hp at 575 V heavy duty |
| Option card | Communication module for Profibus DP V1 Communication module for Modbus TCP/EtherNet/IP Communication module for CANopen daisy chain Communication module for CANopen Sub-D Communication module for CANopen open style |
| Device connection | In the motor supply line To the motor delta terminals |
|---|---|
| [Us] control circuit voltage | 110...230 V AC 50/60 Hz - 15...10 % |
| Apparent power | 0.2 kVA |
| Integrated motor overload protection | True |
| motor thermal protection class | Class 10E |
| Protection type | Phase failure: line Integrated thermal protection: motor Thermal protection: starter Current overload: motor Underload: motor Excessive starting time, locked rotor: motor Motor phase loss: motor Line supply phase loss: line Line supply phase loss: motor Thermal protection: motor |
| current limiting %In (5 x Ie maximum) | 150…700 % |
| Rated current pwr loss specification | 1000.0 A |
| Power loss static current independent | 25.0 W |
| Power loss per device current dependent | 2845.0 W |
| Standards | IEC 60947-4-2 UL 60947-4-2 IEC 60664-1 |
| Product certifications | CE cULus CCC UKCA RCM EAC DNV ABS BV CCS |
| Marking | CE CCC UKCA EAC RCM CULus |
| [Uc] control circuit voltage | 24 V DC |
| Discrete input number | 4 |
| Discrete input type | (STOP) logic inputs, 3500 Ohm (RUN) logic inputs, 3500 Ohm (DI3) programmable as logic input, 3500 Ohm (DI4) programmable as logic input, 3500 Ohm |
| Input compatibility | STOP: discrete input level 1 PLC conforming to IEC 61131-2 RUN: discrete input level 1 PLC conforming to IEC 61131-2 DI3: discrete input level 1 PLC conforming to IEC 61131-2 DI4: discrete input level 1 PLC conforming to IEC 61131-2 |
| Discrete input logic | Programmable digital input at State 0: < 5 V |
| Relay output number | 3 |
| Relay output type | Relay outputs R1A 1 NO Relay outputs R1B 1 NO Relay outputs RIC NO/NC programmable |
| Minimum switching current | 100 mA at 12 V DC for relay outputs |
| Maximum switching current | Relay outputs 2 A at 250 V AC Relay outputs 2 A at 30 V DC Relay outputs |
| Discrete output number | 2 |
| Discrete output type | (DQ1) programmable digital output <= 30 V (DQ2) programmable digital output <= 30 V |
| Output compatibility | Open collector level 1 PLC conforming to IEC 65A-68 |
| Analogue input number | 1 |
| Analogue input type | AI1/PTC PTC/Pt 100 temperature probe PTC2 PTC/Pt 100 temperature probe PTC3 PTC/Pt 100 temperature probe |
| Analogue output number | 1 |
| Analogue output type | Current output AQ1: 0...20 mA or 0...10 V, impedance <500 Ohm |
| Communication port protocol | Modbus serial |
| Connector type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | 2-wire RS 485 |
| Transmission rate | 1200...256000 bit/s |
| Transmission frame | RTU |
| Data format | 8 bits, configurable odd, even or no parity |
| Type of polarization | No impedance for Modbus serial |
| Number of addresses | 0…227 for Modbus serial |
| Method of access | Slave Modbus serial |
| Function available | External bypass control Pre-heating Smoke extraction Multi-motor cascade Second motor set User management Ports and services hardening Security event logging Cybersecure firmware update Single direction |
| Display screen available | True |
| Operating position | Vertical +/- 10 degree |
| Height | 890.0 mm |
| Width | 770.0 mm |
| Depth | 329.0 mm |
| Net weight | 115.0 kg |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2 Conducted and radiated emissions with bypass level B conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-11 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
|---|---|
| pollution degree | Level 3 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| [Ui] rated insulation voltage | 690 V |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3 |
| Relative humidity | 0…95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | 40…60 °C (with current derating of 2 % per °C) -15…40 °C (without derating) |
| Ambient air temperature for storage | -25…70 °C |
| Operating altitude | <= 1000 m without derating > 1000...4000 m with current derating 1 % per 100 m |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum acceleration under vibratory load (during storage) | 15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz |
| Maximum acceleration under vibratory load (during transport) | 15 m/s² at 200...500 Hz 10 m/s² at 9...200 Hz |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under shock load (during storage) | 100 m/s² at 11 ms |
| Maximum acceleration under shock load (during transport) | 100 m/s² at 11 ms |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 59.0 cm |
| Package 1 Width | 95.0 cm |
| Package 1 Length | 103.0 cm |
| Package 1 Weight | 136.0 kg |
Reviews
There are no reviews yet.