Schneider ATS22C32Q | Soft starter for asynchronous motor, Altistart 22, control 230V, 230 to 440V, 90 to 160kW
Description
Schneider ATS22C32Q | Soft starter for asynchronous motor, Altistart 22, control 230V, 230 to 440V, 90 to 160kW
Schneider ATS22C32Q | Soft Starter Overview
The Schneider ATS22C32Q is a soft starter from the Altistart 22 series, designed to optimize the startup and shutdown of asynchronous motors. It minimizes mechanical stress, extends motor lifespan, and enhances energy efficiency, making it ideal for industrial applications.
1. General Specifications
-
Product Name: Schneider ATS22C32Q
-
Series: Altistart 22
-
Type: Soft Starter for Asynchronous Motors
-
Power Range: 90 to 160 kW
-
Operating Voltage: 230V to 440V AC
-
Control Supply Voltage: 230V AC
-
Motor Compatibility: Three-phase asynchronous motors
2. Key Features & Benefits
-
Soft Start & Stop Functionality – Reduces mechanical wear and extends motor lifespan.
-
Built-in Motor Protection – Prevents overheating, overloads, and electrical faults.
-
Integrated Bypass Contactors – Improves energy efficiency by reducing heat dissipation.
-
Compact & Space-Saving Design – Ideal for control panel installations.
-
User-Friendly Interface – Simplifies configuration and monitoring.
-
Enhanced Energy Efficiency – Lowers electricity consumption and reduces peak currents.
3. Applications
-
Pumps & Compressors – Reduces pressure surges and water hammer effects.
-
Fans & Blowers – Provides controlled acceleration and deceleration.
-
Conveyors & Material Handling – Ensures smooth operation and prevents sudden jerks.
-
Industrial Machinery – Enhances safety and reliability in heavy-duty applications.
-
Mining & Heavy-Duty Equipment – Handles high-power motors efficiently.
4. Protection & Safety Features
-
Overload & Overtemperature Protection – Prevents motor damage due to excessive heat.
-
Phase Loss & Imbalance Detection – Ensures stable motor operation.
-
Short Circuit & Voltage Monitoring – Protects against electrical faults.
-
Fault Diagnostics & Alerts – Provides real-time error detection and troubleshooting.
-
Smooth Stop Functionality – Prevents abrupt shutdowns, reducing system strain.
5. Installation & Maintenance
-
Easy to Install & Configure – Quick integration into industrial systems.
-
LCD Display & Real-Time Monitoring – Simplifies diagnostics and parameter adjustments.
-
Durable & Reliable Construction – Built for long-term performance with minimal maintenance.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Altistart 22 |
|---|---|
| Product or component type | Soft starter |
| Product destination | Asynchronous motors |
| Product specific application | Pumps and fans |
| Component name | ATS22 |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 230...440 V - 15...10 % |
| Motor power kW | 160 kW 400 V 160 kW 440 V 90 kW 230 V |
| Factory setting current | 285 A |
| Power dissipation in W | 150 W for standard applications |
| Utilisation category | AC-53A |
| Type of start | Start with torque control (current limited to 3.5 In) |
| IcL starter rating | 320 A for connection in the motor supply line for standard applications |
| IP degree of protection | IP00 |
| Assembly style | With heat sink |
|---|---|
| Function available | Internal bypass |
| Supply voltage limits | 195…484 V |
| Supply frequency | 50...60 Hz - 10...10 % |
| Network frequency | 45...66 Hz |
| Device connection | To the motor delta terminals In the motor supply line |
| [Uc] control circuit voltage | 230 V - 15...10 % 50/60 Hz |
| Control circuit consumption | 20 W |
| Discrete output number | 2 |
| Discrete output type | Relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O Relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O |
| Minimum switching current | 100 mA at 12 V DC (relay outputs) |
| Maximum switching current | 5 A 250 V AC resistive 1 relay outputs 5 A 30 V DC resistive 1 relay outputs 2 A 250 V AC inductive 0.4 20 ms relay outputs 2 A 30 V DC inductive 7 ms relay outputs |
| Discrete input number | 3 |
| Discrete input type | (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm |
| Discrete input voltage | 24 V <= 30 V |
| Discrete input logic | Positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA |
| Output current | 0.4...1 Icl adjustable |
| PTC probe input | 750 Ohm |
| Communication port protocol | Modbus |
| Connector type | 1 RJ45 |
| Communication data link | Serial |
| Physical interface | RS485 multidrop |
| Transmission rate | 4800, 9600 or 19200 bps |
| Installed device | 31 |
| Protection type | Phase failure: line Thermal protection: motor Thermal protection: starter |
| Marking | CE |
| type of cooling | Forced convection |
| Operating position | Vertical +/- 10 degree |
| Height | 425 mm |
| Width | 206 mm |
| Depth | 299 mm |
| Net weight | 33 kg |
| Motor power range AC-3 | 55…100 kW at 200…240 V 3 phases 110…220 kW at 380…440 V 3 phases |
| Motor starter type | Soft starter |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-12 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5 |
|---|---|
| Standards | IEC 60947-4-2 |
| Product certifications | UL CCC C-Tick CSA GOST |
| Vibration resistance | 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 1.5 mm (f= 2…13 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Noise level | 56 dB |
| Pollution degree | Level 2 conforming to IEC 60664-1 |
| Relative humidity | 0…95 % without condensation or dripping water conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -10…40 °C (without derating) 40…60 °C (with current derating 2.2 % per °C) |
| Ambient air temperature for storage | -25…70 °C |
| Operating altitude | <= 1000 m without derating > 1000...< 2000 m with current derating of 2.2 % per additional 100 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 49.0 cm |
| Package 1 Width | 36.5 cm |
| Package 1 Length | 54.5 cm |
| Package 1 Weight | 24.5 kg |
| Warranty | 18 months |
|---|
Reviews
There are no reviews yet.