Schneider G12T3F63 | Circuit breaker, GoPact MCCB 125, 3 poles, 10kA at 415VAC, 63A rating, TMD trip unit, fixed thermal protection
Description
Schneider G12T3F63| Circuit breaker, GoPact MCCB 125, 3 poles, 10kA at 415VAC, 63A rating, TMD trip unit, fixed thermal protection
Schneider G12T3F63 | Circuit Breaker, GoPact MCCB 125, 3P, 10kA at 415V AC, 63A, TMD Trip Unit
1. Overview
The Schneider G12T3F63 is a Molded Case Circuit Breaker (MCCB) from the GoPact MCCB 125 series, designed for circuit protection in industrial and commercial applications. It features a 63A rating, TMD (Thermal Magnetic) trip unit, and a 10kA breaking capacity at 415V AC, making it ideal for power distribution and overload protection.
2. Key Features
-
Rated Current: 63A – Suitable for medium-power applications
-
Poles: 3P (Three-Pole) – Designed for three-phase power systems
-
Breaking Capacity: 10kA at 415V AC – Ensures protection against moderate fault currents
-
Trip Unit Type: TMD (Thermal Magnetic Device)
-
Thermal Protection: Fixed setting for overload protection
-
Magnetic Protection: Instantaneous trip for short-circuit protection
-
-
Durable & Compact Design – Built for industrial environments
-
Standards Compliance: IEC 60947-2
3. Technical Specifications
| Parameter | Details |
|---|---|
| Product Type | MCCB (Molded Case Circuit Breaker) |
| Series | GoPact MCCB 125 |
| Rated Current (In) | 63A |
| Number of Poles | 3P (Three-Pole) |
| Breaking Capacity | 10kA at 415V AC |
| Trip Unit Type | TMD (Thermal Magnetic Device) |
| Thermal Protection | Fixed |
| Magnetic Protection | Fixed |
| Voltage Rating | ≤ 415V AC |
| Frequency | 50/60Hz |
| Operating Temperature | -25°C to +55°C |
| Mounting Type | Panel Mount |
| Compliance | IEC 60947-2 |
4. Applications
The Schneider G12T3F63 MCCB is commonly used in:
Power Distribution Systems – Protects electrical panels and switchgear
Motor Protection – Prevents damage from overloads and short circuits
Industrial & Commercial Buildings – Ideal for factories, offices, and warehouses
Renewable Energy Systems – Used in solar and wind power installations
Backup Power Systems – Essential in UPS and generator circuits
5. Benefits
Reliable Circuit Protection – Prevents damage due to overloads and short circuits
Efficient Power Isolation – Ensures safe maintenance and operation
High Breaking Capacity – Handles fault currents up to 10kA at 415V AC
Industry-Compliant – Meets IEC 60947-2 standards
Space-Saving Design – Compact for power panels with limited space
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | GoPact MCCB |
|---|---|
| Product or component type | Circuit breaker |
| Product name | GoPact MCCB 125 |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 63 A at 40 °C |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 10 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Performance level | T 10 kA 380/415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 440 V AC conforming to EN/IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 10 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Mechanical durability | 30000 cycles |
| Electrical durability | 8000 cycles at 415 V In |
| Power dissipation per pole | 18.7 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection terminals | screw terminals |
| Connection pitch | 25 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 63 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Fixed |
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 10 x In |
| Width (W) | 75 mm |
| Height (H) | 130 mm |
| Depth (D) | 60 mm |
| Net weight | 0.7 kg |
| Colour | Grey (RAL 7035) |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H |
|---|---|
| Overvoltage category | III |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…55 °C |
| Ambient air temperature for storage | -35…85 °C |
| Operating altitude | 0...2000 m without derating 2000...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 12.4 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 13.9 cm |
| Package 1 Weight | 908 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 7.579 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 128 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 129.764 kg |
Reviews