Schneider TM3TM3 | analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC
Schneider TM3TM3 | analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC
Description
Schneider TM3TM3 | analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC
The Schneider Electric TM3TM3 is an analog I/O expansion module from the Modicon TM3 series. Designed for use with Modicon controllers, it offers reliable analog signal processing with flexible input/output configurations for a variety of industrial control and automation applications.
Key Features
-
Product Type: Analog I/O expansion module
-
Series: Modicon TM3
-
Input Channels:
-
2 configurable analog or temperature inputs
-
-
Output Channels:
-
1 analog output
-
-
Signal Type: Voltage or current for analog; PT100, PT1000, or thermocouples for temperature
-
Connection Type: Screw terminals
Electrical Specifications
-
Power Supply: 24V DC
-
Input Resolution: 12-bit (typical, depending on configuration)
-
Output Resolution: 12-bit analog signal
-
Input Range Options:
-
Voltage: 0–10 V
-
Current: 0–20 mA or 4–20 mA
-
Temperature: PT100, PT1000, J, K, T thermocouples
-
-
Output Range:
-
Voltage or current (0–10 V, 4–20 mA, etc.)
-
Mechanical & Environmental Characteristics
-
Mounting: DIN rail, direct attachment to TM3-compatible PLCs
-
Enclosure: Compact plastic housing
-
Operating Temperature: 0°C to +55°C
-
Storage Temperature: -40°C to +70°C
-
Protection Rating: IP20 (module body)
Compatibility
-
Compatible Controllers: Modicon M221, M241, M251, and other TM3-ready devices
-
Expansion Method: Plug-in to the right side of the main controller or existing I/O modules
Applications
-
Process control and monitoring
-
Temperature regulation systems
-
Industrial automation for machines and equipment
-
HVAC systems and energy management
-
Analog sensor integration in PLC-based systems
Advantages
-
Flexible analog input configuration (voltage, current, or temperature)
-
Precise analog output for control systems
-
Easy integration with TM3 and Modicon PLC platforms
-
Compact design for space-saving installations
-
Ideal for mixed analog and digital control environments
Additional information
| brands | Schneider Electric |
|---|
Specifications
| range of product | Modicon TM3 |
|---|---|
| Product or component type | Input/output analog module |
| Range compatibility | Modicon M221 Modicon M241 Modicon M251 Modicon M262 |
| analogue input number | 2 |
| Analogue input type | Current 4...20 mA current 0...20 mA voltage 0...10 V voltage - 10...10 V thermocouple - 200...1000 °C with thermocouple J thermocouple - 200...1300 °C with thermocouple K thermocouple 0...1760 °C with thermocouple R thermocouple 0...1760 °C with thermocouple S thermocouple 0...1820 °C with thermocouple B thermocouple - 200...400 °C with thermocouple T thermocouple - 200...1300 °C with thermocouple N thermocouple - 200...800 °C with thermocouple E thermocouple 0...2315 °C with thermocouple C Ni 100/Ni 1000 temperature probe - 60...180 °C Pt 100 temperature probe - 200...850 °C Pt 1000 temperature probe - 200...600 °C |
| analogue output number | 1 |
| Analogue output type | Current: 4...20 mA Current: 0...20 mA Voltage: 0...10 V Voltage: - 10...10 V |
| Analogue input resolution | 16 bits 15 bits + sign |
|---|---|
| Permissible continuous overload | 13 V, analogue input type: voltage 40 mA, analogue input type: current |
| Input impedance | <= 50 Ohm current >= 1 MOhm voltage >= 1 MOhm thermocouple >= 1 MOhm temperature probe |
| Analogue output resolution | 12 bits |
| LSB value | 0.15 mV 0...10 Vvoltage 0.30 mV - 10...10 Vvoltage 0.30 µA 0...20 mAcurrent 0.244 µA 4...20 mAcurrent 0.1 °Ctemperature probe 0.1 °Cthermocouple 2.44 mV 0...10 V voltage 4.88 mV - 10...10 V voltage 4.88 µA 0...20 mA current 3.91 µA 4...20 mA current |
| Load type | Resistive |
| Load impedance ohmic | 1 kOhm voltage 300 Ohm current |
| Stabilisation time | 1 ms |
| Conversion time | 100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current |
| Sampling duration | 10 ms, analogue input type: voltage/current 100 ms, analogue input type: voltage/current 100 ms, analogue input type: thermocouple 100 ms, analogue input type: temperature probe |
| Absolute accuracy error | +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C +/- 0.1 % of full scale at 25 °C for analogue input voltage/current +/- 0.1 % of full scale at 25 °C for thermocouple C 0...2315 °C +/- 0.1 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe +/- 0.1 % of full scale at 25 °C for thermocouple R, S 200...1760 °C +/- 0.1 % of full scale at 25 °C for thermocouple B 300...1820 °C +/- 0.1 % of full scale at 25 °C for thermocouple K 0...1300 °C +/- 0.1 % of full scale at 25 °C for thermocouple J 0...1000 °C +/- 0.1 % of full scale at 25 °C for thermocouple E 0...800 °C +/- 0.1 % of full scale at 25 °C for thermocouple T 0...400 °C +/- 0.1 % of full scale at 25 °C for thermocouple N 0...1300 °C +/- 0.1 % of full scale at 25 °C for analogue output voltage/current |
| Temperature drift | +/- 0.006 %FS/°C |
| Repeat accuracy | +/-0.5 %FS for input +/- 0.4 %FS for output |
| Non-linearity | +/- 0.01 %FS, analogue output type: analog output +/- 0.1 %FS, analogue input type: analog input |
| Output ripple | 20 mV |
| Cross talk | <= 1 LSB |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 20.4…28.8 V |
| Type of cable | Twisted shielded pairs cable <30 m for input/output circuit |
| Current consumption | 55 mA at 24 V DC via external supply no load 55 mA at 5 V DC via bus connector no load 60 mA at 5 V DC via bus connector full load 80 mA at 24 V DC via external supply full load |
| Local signalling | 1 LED (green) for PWR |
| Electrical connection | 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply |
| Insulation | Between input and supply at 1500 V AC Between input and internal logic at 500 V AC Between output and supply at 1500 V AC Between output and internal logic at 500 V AC |
| Marking | CE |
| Surge withstand | 1 kV power supply common mode conforming to IEC 61000-4-5 0.5 kV power supply differential mode conforming to IEC 61000-4-5 1 kV I/O common mode conforming to IEC 61000-4-5 0.5 kV I/O differential mode conforming to IEC 61000-4-5 |
| Mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit |
| height | 90 mm |
| Depth | 70 mm |
| Width | 23.6 mm |
| Net weight | 0.115 kg |
| Standards | IEC 61131-2 |
|---|---|
| product certifications | CE UKCA RCM EAC cULus cULus HazLoc |
| Resistance to electrostatic discharge | 8 kV in air conforming to IEC 61000-4-2 4 kV on contact conforming to IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3 |
| Resistance to magnetic fields | 30 A/m conforming to IEC 61000-4-8 |
| Resistance to fast transients | 1 kV (I/O) conforming to IEC 61000-4-4 |
| Resistance to conducted disturbances | 10 V 0.15...80 MHz conforming to IEC 61000-4-6 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
| Electromagnetic emission | Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011 |
| Immunity to microbreaks | 10 ms |
| Ambient air temperature for operation | -10…55 °C horizontal installation -10…35 °C vertical installation |
| Ambient air temperature for storage | -25…70 °C |
| Relative humidity | 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage) |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Operating altitude | 0...2000 m |
| Storage altitude | 0…3000 m |
| Vibration resistance | 3.5 mm at 5…8.4 Hz on DIN rail 3 gn at 8.4…150 Hz on DIN rail |
| Shock resistance | 15 gn for 11 ms |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.611 cm |
| Package 1 Width | 10.688 cm |
| Package 1 Length | 12.753 cm |
| Package 1 Weight | 220.0 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 42 |
| Package 2 Height | 30 cm |
| Package 2 Width | 40 cm |
| Package 2 Length | 60 cm |
| Package 2 Weight | 10.421 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 504 |
| Package 3 Height | 105 cm |
| Package 3 Width | 120 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 130 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
-
0
Schneider TM3DI16 | Modicon TM3 – 16 inputs (screw) 24Vdc
Schneider TMCR2DM4U | cartridge M200 – 2 Digital inputs and 2 Transistor sink outputs
TM200C40R | controller M200 40 IO relay
Schneider TM200C24R | controller M200 24 IO relay
Schneider TM200C16R | controller M200 16 IO relay
-
0
Reviews
There are no reviews yet.