Description

Schneider A9F87432 | Miniature circuit-breaker, Acti9 iC60H, 4P, 32 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)

Schneider A9F87432 | Miniature circuit-breaker, Acti9 iC60H, 4P, 32 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)

  • Product Type: Miniature Circuit Breaker (MCB)

  • Product Series: Acti9 iC60H

  • Reference Code: A9F87432

  • Number of Poles: 4P (Four-pole)

  • Rated Current (In): 32 A

  • Tripping Curve: C Curve (trips between 5–10 times the rated current)

  • Breaking Capacity:

    • 10,000 A according to IEC 60898-1

    • 15,000 A according to IEC 60947-2

  • Rated Operational Voltage: 400/415 V AC

  • Frequency: 50/60 Hz

  • Degree of Protection: IP20 (improves with enclosure)

  • Mechanical Endurance: Up to 20,000 operations

  • Electrical Endurance: Up to 10,000 operations under load

  • Mounting Type: DIN rail (35 mm standard)

  • Insulation Class: Class II (double insulation)

. Key Features

  • High Breaking Capacity: Ensures safe disconnection under high fault conditions, protecting both equipment and personnel.

  • C Curve Sensitivity: Ideal for general-purpose circuits that include loads with moderate starting currents like motors, compressors, and lighting.

  • Compact Modular Design: Saves panel space and integrates seamlessly with other Acti9 devices.

  • Easy Installation: Snap-on DIN rail mounting for quick setup and simplified maintenance.

  • Trip Status Indicator: Clear and visible indicators for ON, OFF, and trip positions.

  • Accessory Compatibility: Supports a wide range of modular accessories such as auxiliary contacts, shunt trips, and under-voltage releases.

  • Eco-Conscious Manufacturing: Fully compliant with RoHS and REACH directives.

. Applications

The Schneider A9F87432 is suited to various electrical protection applications, including:

a. Residential

  • Provides protection for high-load appliances and circuits, including electric water heaters, ovens, and AC systems.

b. Commercial

  • Used in lighting systems, distribution panels, and equipment circuits in office buildings, hospitals, and retail outlets.

c. Industrial

  • Protects circuits powering industrial equipment, pumps, and control systems in manufacturing environments.

d. Sub-panels and Distribution Boards

  • Frequently installed in sub-distribution boards where selective and localized protection is required.

e. Renewable and Backup Power Systems

  • Effective in safeguarding AC distribution circuits within solar and backup power infrastructures.

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
Product or component type Miniature circuit-breaker
Device short name iC60H
Poles description 4P
Number of protected poles 4
[In] rated current 32 A
Network type DC AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2
Standards EN 60947-2 IEC 60947-2 EN 60898-1 IEC 60898-1
Quality labels NF
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 8 x In +/- 20 %
[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 - 180...250 V DC 15 kA 100 % conforming to EN 60947-2 - 180...250 V DC
Limitation class 3 conforming to EN 60898-1 3 conforming to IEC 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator Yes
control type Toggle
local signalling Trip indicator
Mounting mode Fixed
mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 8
height 85 mm
Width 72 mm
Depth 78.5 mm
Net weight 0.5 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals Single terminal (top or bottom) 1…35 mm² rigid Single terminal (top or bottom) 1…25 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom
earth-leakage protection Separate block
Environment
IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0...2000 m
ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.5 cm
Package 1 Width 7.1 cm
Package 1 Length 9.4 cm
Package 1 Weight 476 g
Unit Type of Package 2 BB1
Number of Units in Package 2 3
Package 2 Height 3 cm
Package 2 Width 30 cm
Package 2 Length 20 cm
Package 2 Weight 1.489 kg
Unit Type of Package 3 S03
Number of Units in Package 3 33
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 16.98 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider A9F87432 | Miniature circuit-breaker, Acti9 iC60H, 4P, 32 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare