Description

Schneider A9K24240 | Miniature circuit-breaker, Acti9 iK60N, 2P, 40 A, C curve, 6000 A (IEC60898-1)

1. Technical Specifications

  • Rated Operational Voltage (Ue): Up to 240/415 V AC

  • Number of Poles: 2 (Double-pole protection for two-phase or single-phase circuits)

  • Rated Current (In): 40 Amperes

  • Tripping Characteristic: Type C — suited for circuits with moderate inrush currents (typically for lighting systems, small motors, and general-purpose circuits)

  • Breaking Capacity: 6000 A (according to IEC 60898-1)

  • Mounting Method: Standard 35 mm DIN rail

  • Degree of Protection: IP20 (IP40 when housed in an appropriate enclosure)

  • Insulation Class: Class II (double/reinforced insulation for safety)

  • Electrical Endurance: Capable of up to 20,000 load operations

  • Mechanical Endurance: Up to 20,000 manual operations

  • Operating Temperature Range: -25°C to +70°C

  • Compliance Standards: IEC 60898-1

2. Key Features

  1. Double-Pole Protection: Provides protection for two-phase systems, or one phase and neutral, ensuring proper isolation and safety in two-wire or single-phase circuits

  2. C Curve Tripping: Suitable for circuits that handle moderate inrush currents, such as small motors, lighting systems, and heating equipment

  3. Compact Design: Slim, space-efficient design that fits easily into residential or commercial distribution boards

  4. High Breaking Capacity: Capable of interrupting fault currents up to 6000 A, ensuring reliable protection in case of short circuits or overloads

  5. Simple Installation: Easy-to-install with finger-safe terminals and a standard DIN rail mounting system

  6. Durable Performance: Long operational life with both high electrical and mechanical endurance for consistent protection

  7. Visual ON/OFF Indicator: Clear visibility of the breaker’s operational status for easier monitoring and maintenance

  8. Eco-Friendly Construction: Made with recyclable materials and fully compliant with RoHS environmental standards

3. Typical Applications

The Schneider A9K24240 MCB is designed for various applications where double-pole protection is required, typically in residential, commercial, and light industrial environments:

  • Residential Electrical Systems: Protection for lighting, socket circuits, and small appliances

  • Small Commercial Applications: For protecting general-purpose circuits in retail, offices, or workshops

  • Motor Circuits: Protects small motors, HVAC systems, and pumps that have moderate inrush currents

  • Control Panels: Ideal for protecting auxiliary control circuits and low-voltage equipment

  • Data Centers: Suitable for protecting sensitive circuits, low-power servers, and IT equipment

  • Educational Institutions: Used in schools, laboratories, and office spaces to protect various electrical circuits

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
Product name Acti9 iK60
Product or component type Miniature circuit-breaker
Device short name iK60N
Poles description 2P
Number of protected poles 2
[In] rated current 40 A at 30 °C
Network type AC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Suitability for isolation Yes conforming to EN/IEC 60898-1
Standards EN/IEC 60898-1
product certifications SNI
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 5...10 x In
[Ics] rated service breaking capacity 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz
Limitation class 3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage 440 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Uimp] rated impulse withstand voltage 4 kV conforming to EN/IEC 60898-1
Contact position indicator No
control type Toggle
local signalling ON/OFF indication
Mounting mode Clip-on
mounting support DIN rail
9 mm pitches 4
height 85 mm
Width 36 mm
Depth 78.5 mm
Net weight 200 g
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Locking options description Padlocking device
Connections - terminals Tunnel type terminal (top or bottom) 1…35 mm² rigid Tunnel type terminal (top or bottom) 1…25 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom
earth-leakage protection Without
Environment
IP degree of protection IP20 conforming to IEC 60529
Pollution degree 2 conforming to EN/IEC 60898-1
Overvoltage category II
ambient air temperature for operation -25…60 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 3.6 cm
Package 1 Width 7.5 cm
Package 1 Length 9.4 cm
Package 1 Weight 237 g
Unit Type of Package 2 BB1
Number of Units in Package 2 6
Package 2 Height 8.6 cm
Package 2 Width 9.6 cm
Package 2 Length 21.8 cm
Package 2 Weight 1.49 kg
Unit Type of Package 3 S03
Number of Units in Package 3 66
Package 3 Height 30 cm
Package 3 Width 30 cm
Package 3 Length 40 cm
Package 3 Weight 17.816 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : A9K24240 

Main Document

Data Sheet : A9K24240 