Schneider A9R44263 | Acti 9 iID – RCCB – 2P – 63A – 300mA – type AC
Schneider A9R44263 | Acti 9 iID – RCCB – 2P – 63A – 300mA – type AC
Description
Schneider A9R44263 | Acti 9 iID – RCCB – 2P – 63A – 300mA – type AC
Technical Specifications A9R44263
-
Product Code: A9R44263
-
Product Range: Acti 9 iID
-
Device Type: Residual Current Circuit Breaker (RCCB)
-
Number of Poles: 2 (Single-phase or Two-phase)
-
Rated Current (In): 63 A
-
Rated Residual Operating Current (IΔn): 300 mA
-
Type: Type AC (detects sinusoidal alternating residual currents only)
-
Rated Voltage: 230V AC (single-phase)
-
Rated Frequency: 50/60 Hz
-
Tripping Characteristic: Instantaneous
-
Mounting Type: DIN rail
-
Degree of Protection: IP20 (protection against accidental contact)
-
Standards Compliance: IEC 61008-1
-
Test Button: Yes (for manual testing)
-
Mechanical Durability: > 5000 operations
-
Electrical Durability: > 2000 operations at rated load
Key Features
-
63A Rated Current: Suitable for low- to medium-power circuits requiring protection against earth leakage currents.
-
300mA Sensitivity: Designed for fire prevention, this RCCB detects residual currents that could cause overheating or other risks associated with prolonged leakage currents, especially in systems where human safety is less of a concern than fire protection.
-
Type AC Detection: Specifically designed to detect sinusoidal AC leakage currents that are typically found in general residential and commercial systems.
-
Instantaneous Tripping: Instantly trips when the leakage current exceeds the rated threshold, ensuring rapid disconnection to avoid potential fire hazards.
-
Test Button: Allows for regular manual testing of the RCCB to ensure its functionality.
-
Compact and Modular Design: Space-saving and easy to install on DIN rails, making it an ideal choice for distribution panels.
-
Compliance with IEC Standards: Meets the IEC 61008-1 standard for electrical safety and reliability.
Applications
The A9R44263 RCCB is ideal for use in applications where the primary concern is fire protection due to residual current leakage. Its 300mA sensitivity makes it suitable for:
Residential Installations
-
Protection for household appliances and lighting systems, where fire prevention is the key concern due to extended leakage currents over time.
Commercial Installations
-
Suitable for retail spaces, offices, and small commercial buildings, providing safety for electrical systems in areas where personnel are less likely to come into direct contact with live conductors.
Industrial Environments
-
Ideal for protecting circuits in workshops, warehouses, and other industrial facilities that use three-phase or two-phase systems.
Electrical Distribution Panels
-
Provides residual current protection in main electrical panels where extended leakage currents may be a concern, especially for older systems or systems with deteriorating insulation.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | Acti9 |
|---|---|
| Product name | Acti9 iID |
| Product or component type | Residual current circuit breaker (RCCB) |
| Device short name | iID |
| Poles description | 2P |
| Neutral position | Left |
| [In] rated current | 63 A |
| Network type | AC |
| Earth-leakage sensitivity | 300 mA |
| earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type AC |
| device location in system | Outgoer |
|---|---|
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 220...240 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| Rated breaking and making capacity | Idm 1500 A Im 1500 A |
| Rated conditional short-circuit current | 10 kA |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Surge current | 250 A |
| Contact position indicator | Yes |
| control type | Toggle |
| Mounting mode | Clip-on |
| mounting support | DIN rail |
| 9 mm pitches | 4 |
| height | 91 mm |
| Width | 36 mm |
| Depth | 73.5 mm |
| Net weight | 0.21 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | AC-1: 15000 cycles |
| Locking options description | Padlocking device |
| Connections - terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 3.5 N.m top or bottom |
| Standards | EN/IEC 61008-1 EN/IEC 61008-2-1 |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.000 cm |
| Package 1 Width | 8.000 cm |
| Package 1 Length | 10.000 cm |
| Package 1 Weight | 211.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 9.000 cm |
| Package 2 Width | 10.500 cm |
| Package 2 Length | 25.000 cm |
| Package 2 Weight | 1.332 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 54 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 12.375 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61521 | miniature circuit breaker – C60H – 2 poles – 1 A – C curve
Schneider A9N61502 | miniature circuit breaker – C60H – 1 pole – 2 A – C curve
-
0
Schneider A9N26929 | Acti9 – Auxiliary contact OC plus 1 SD and OF ac dc
-
0
Schneider A9N18470 | Miniature circuit-breaker, Acti9 C120H, 3P, 125 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18369 | Miniature circuit-breaker, Acti9 C120N, 3P, 125 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.