Schneider GV3P40 | Motor circuit breaker, TeSys GV3, 3P, 30-40 A, thermal magnetic, EverLink terminals
Schneider GV3P40 | Motor circuit breaker, TeSys GV3, 3P, 30-40 A, thermal magnetic, EverLink terminals
Description
Schneider GV3P40 | Motor circuit breaker, TeSys GV3, 3P, 30-40 A, thermal magnetic, EverLink terminals
Technical Specifications GV3P40
-
Product Type: Motor Circuit Breaker
-
Range: TeSys GV3
-
Model: GV3P40
-
Poles: 3P (Three-pole)
-
Current Setting Range: Adjustable from 30 A to 40 A
-
Protection Type:
-
Thermal protection: for overload conditions
-
Magnetic protection: for short-circuit conditions
-
-
Trip Class: Class 10 (quick tripping suitable for standard motor protection)
-
Breaking Capacity:
-
Up to 100 kA at 400/415 V AC (with fuses)
-
-
Rated Operational Voltage: Up to 690 V AC
-
Frequency: 50/60 Hz
-
Conformity Standards:
-
IEC 60947-2
-
IEC 60947-4-1
-
-
Terminal Technology: EverLink (ensures consistent tightening force and resists loosening over time)
-
Mounting: DIN rail or screw mounting
-
Degree of Protection: IP20 (without enclosure)
-
Ambient Temperature for Operation: -20°C to +60°C
-
Dimensions (approx.):
-
Height: ~130 mm
-
Width: ~55 mm
-
Depth: ~120 mm
-
-
Weight: Approximately 0.9 kg
Key Features
-
Integrated Motor Protection: Offers reliable protection against overloads, short circuits, and phase failures, eliminating the need for separate protective relays.
-
Adjustable Thermal Setting: Allows fine-tuning of current range to match motor specifications, improving protection accuracy.
-
Magnetic Trip Mechanism: Provides instantaneous trip during high fault currents, reducing damage to motors and cables.
-
EverLink Terminals: Patented connection technology ensures permanent contact pressure and prevents loosening due to temperature changes or vibrations.
-
Manual Operation with Clear Indicators: ON/OFF/trip status is clearly shown on the front of the device.
-
Compact Design: Saves space in control panels while maintaining high performance.
-
High Short-Circuit Breaking Capacity: Suitable for use in demanding industrial environments.
-
Coordination Compatibility: Fully compatible with Schneider TeSys contactors and starters for Type 1 and Type 2 coordination.
-
Environmentally Friendly: Complies with RoHS standards and designed with recyclable materials.
Applications
The GV3P40 motor circuit breaker is ideal for various industrial and commercial settings where reliable motor protection is essential:
-
Motor Control Centers (MCCs): Core protection for motors in industrial control panels.
-
Pumps and Compressors: Ensures safe startup and protection from overload or jamming conditions.
-
HVAC Systems: Protects motors in heating, ventilation, and air conditioning systems.
-
Conveyor Systems: Prevents damage from mechanical overloading or phase loss.
-
Manufacturing Equipment: Suitable for protecting motors driving presses, mixers, or production lines.
-
Agricultural Installations: Ideal for irrigation motors and grain handling systems.
-
Building Automation: Used in motorized systems such as lifts, escalators, and fans.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | TeSys Deca |
|---|---|
| Product name | TeSys GV3 TeSys Deca |
| product or component type | Motor circuit breaker |
| Device short name | GV3P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| poles description | 3P |
|---|---|
| Network type | AC |
| Utilisation category | AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
| Motor power kW | 18.5 kW at 400/415 V AC 50/60 Hz 22 kW at 500 V AC 50/60 Hz 37 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 40 A |
| Thermal protection adjustment range | 30…40 A conforming to IEC 60947-4-1 |
| Magnetic tripping current | 560 A |
| [Ith] conventional free air thermal current | 40 A conforming to IEC 60947-4-1 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Power dissipation per pole | 8 W |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles for AC-3 at 415 V In |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Tightening torque | 5 N.m - on screw clamp terminal |
| Width | 55 mm |
| Height | 132 mm |
| Depth | 136 mm |
| net weight | 0.96 kg |
| Colour | Dark grey |
| Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 |
|---|---|
| Product certifications | CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV ABS DNV-GL UKCA |
| IK degree of protection | IK09 enclosure |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | Conforming to IACS E10 |
| ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 15 Gn for 11 ms contactor open Shocks: 30 Gn for 11 ms contactor closed Vibrations: 4 Gn, 5...300 Hz |
| Operating altitude | 3000 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 16.000 cm |
| Package 1 Width | 6.500 cm |
| Package 1 Length | 14.600 cm |
| Package 1 Weight | 983.000 g |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 120 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 133.960 kg |
| Warranty | 18 months |
|---|