Schneider C11N6TM025L | circuit breaker ComPacT NSXm N (50 kA at 415 VAC), 4P 3d, 25 A rating TMD trip unit, EverLink connectors
Schneider C11N6TM025L | ComPacT NSXm100N 50kA AC 4P3R 25A TMD ELINK automatic switch
Description
Schneider C11N6TM025L | circuit breaker ComPacT NSXm N (50 kA at 415 VAC), 4P 3d, 25 A rating TMD trip unit, EverLink connectors
Technical Specifications C11N6TM025L
-
Product Reference: C11N6TM025L
-
Series: ComPacT NSXm N
-
Device Type: Molded Case Circuit Breaker (MCCB)
-
Rated Current (In): 25 Amperes
-
Rated Operational Voltage: Up to 415 VAC
-
Breaking Capacity: 50 kA at 415 VAC
-
Number of Poles: 4P (3 poles protected + neutral pole – 3d configuration)
-
Trip Unit Type: TMD (Thermal Magnetic)
-
Connection Technology: EverLink lug connectors
-
Mounting Type: Fixed
-
Frequency: 50/60 Hz
-
Standards: Complies with IEC 60947-2
-
Control Mechanism: Manual
Key Features
-
High Breaking Capacity: Offers superior fault protection with 50 kA interrupting capacity at 415 VAC, suitable for demanding industrial applications.
-
Thermal-Magnetic Trip Unit: Provides both overload (thermal) and short-circuit (magnetic) protection for enhanced safety.
-
EverLink Technology: Equipped with patented EverLink lugs that maintain a secure, stable connection over time, even in environments with thermal cycling or vibrations.
-
Compact and Lightweight Design: The NSXm frame is optimized for space-constrained panels and modern installations.
-
4-Pole Protection: The 3d configuration ensures the neutral is not protected but is switched, providing full-phase disconnection.
-
Modular Design: Easily integrated with auxiliaries such as shunt trips, under-voltage releases, and auxiliary contacts.
-
Clear Visual Indication: Offers visible status indication for ON/OFF/TRIPPED positions for safe operation and diagnostics.
Applications
-
Industrial Control Panels: Protects equipment and circuits in production lines, automated machinery, and process industries.
-
Commercial Distribution Boards: Suitable for main and sub-feeder applications in commercial buildings like shopping centers and office complexes.
-
Renewable Energy Systems: Used in solar and wind energy systems where high fault-level protection is required.
-
Backup Power Systems: Ensures safe connection and protection for generators and UPS systems.
-
Infrastructure Projects: Ideal for use in airports, hospitals, metro stations, and public service buildings with high reliability demands.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Spectrum | ComPacT new generation |
|---|---|
| Product name | ComPact NSX DC |
| Product range | Compact NS KIT |
| Short name of the device | NSXm 63N |
| Type of product or component | Automatic switch |
| Function | For current > 0.1 A |
| Number of poles | 4P |
| description of protected poles | 3R |
| neutral position | Left |
| [In] Rated current | 25 A at 40 °C |
| [Ue] Nominal operating voltage | 690V AC 50/60Hz |
| Network type | A.C. |
| Network frequency | 50/60Hz |
| sectioning power | Yes according to En> 50 A |
| employment category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 90 kA Icu at 220...240 V AC 50/60 Hz according to En> 50 A 50 kA Icu at 380...415 V AC 50/60 Hz according to En> 50 A 50 kA Icu at 440 V AC 50 /60 Hz according to En> 50 A 25 kA Icu in 500 V AC 50/60 Hz according to En> 50 A 15 kA Icu in 525 V AC 50/60 Hz according to En> 50 A 10 kA Icu in 660.. .690 V AC 50/60 Hz according to En> 50 A |
| Performance level | Unprotected 50 kA 415 V AC |
| control unit | TM-D |
| trip unit technology | Thermal-magnetic |
| control unit protection functions | LIG |
| Control type | Handle |
| Circuit breaker mounting mode | Permanent |
| [Ui] Rated insulation voltage | 800V AC 50/60Hz |
|---|---|
| [Uimp] Resistance to voltage spikes | 8kV |
| [ICS] rated service short-circuit breaking capacity | 90 kA at 220...240 V AC 50/60 Hz according to En> 50 A 50 kA at 380...415 V AC 50/60 Hz according to En> 50 A 50 kA at 440 V AC 50/60 Hz according to En> 50 A 25 kA at 500 V AC 50/60 Hz according to En> 50 A 15 kA at 525 V AC 50/60 Hz according to En> 50 A 2.5 kA at 660...690 V AC 50/60 Hz according to En> 50 A |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| power dissipated per pole | 2.83W |
| Mounting bracket | Back plate |
| Mounting position | Horizontal and vertical Flat on the back |
| top connection | Frontal |
| downward connection | Front of |
| Connection terminals | 1 IK07 2.5…95 mm², rigid or braided aluminum / copper 1 IK07 2.5…70 mm², flexible copper |
| Connection step | 35 mm with spreaders 27 mm without spreaders |
| 9mm steps | 12 module |
| trigger unit caliber | 25 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Go] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Permanent |
| Neutral protection settings | Overload protection (long time) - cable type: 3R) |
| Instantaneous protection pick-up adjustment type Ii | Permanent |
| [II] instantaneous protection pick-up adjustment range | 600A |
| earth leakage protection | Without |
| Number of slots for electrical auxiliaries | 1 slot(s) for OF auxiliary switch 1 slot(s) for South Dakota alarm switch 1 slot(s) for MN or MX trip coil |
| local signage | Presence of auxiliary contacts, state 1 flag - cable type: green) |
| Width (W) | 108mm |
| Height (H) | 137mm |
| Depth (D) | 80mm |
| Product weight | 1.42kg |
| Color | Gray - cable type: RAL 7016) |
| Rules | HB2 |
|---|---|
| Pollution degree | 3 according to IK07 |
| IP protection class | IP40 conforming to IEC 60529 |
| IK protection grade | IK07 conforming to IEC 62262 |
| Ambient operating temperature | -25…70 °C |
| Storage ambient temperature | -50…85 °C |
| RH | 0…95% |
| maximum operating altitude | 2000 m without decrease 5000 m with restrictions |
| Package Unit Type 1 | PCE |
|---|---|
| Number of units in package 1 | 1 |
| Package 1 Height | 12,000cm |
| Package 1 Wide | 13,000cm |
| Package 1 Length | 22,000cm |
| Package 1 Weight | 1,600kg |
| Package Unit Type 2 | S03 |
| Number of units in package 2 | 6 |
| Package 2 Height | 30,000cm |
| Pack 2 Wide | 30,000cm |
| Package 2 Length | 40,000cm |
| Package 2 Weight | 9,600kg |
| Package Unit Type 3 | P12 |
| Number of units in package 3 | 144 |
| Package 3 Height | 150,000cm |
| Pack 3 Wide | 80,000cm |
| Package 3 Length | 120,000cm |
| Package 3 Weight | 254,490kg |
Reviews