Schneider C25B6TM200: Product Overview and Applications
Introduction
The Schneider C25B6TM200 is a powerful molded case circuit breaker (MCCB) designed for systems with high power needs, offering a current rating of 200A. Known for its reliability, this MCCB is crafted to protect against overloads, short circuits, and electrical faults in heavy-duty and high-capacity applications. With Schneider’s thermal-magnetic trip technology, the C25B6TM200 offers effective circuit protection for industrial, commercial, and critical infrastructure installations.
Key Features of Schneider C25B6TM200
- Rated Current of 200A: Suited for applications with substantial power requirements, ensuring safe operation under heavy loads.
- Thermal-Magnetic Trip Unit: Provides dual protection with thermal sensing for gradual overloads and magnetic sensing for instant response to short circuits.
- High Breaking Capacity: Can withstand significant fault currents, making it a dependable solution in environments with high load requirements.
- Rugged and Compact Design: Engineered for durability, yet compact enough for easy integration in standard electrical panels.
- Adjustable Trip Settings: Customizable settings allow the breaker to be tailored to specific applications, enhancing both safety and flexibility.
Applications of Schneider C25B6TM200
- Industrial Equipment and Heavy Machinery: Ideal for protecting circuits in industrial facilities, including machines, motors, and conveyor systems.
- Commercial Power Systems: Ensures consistent power distribution in high-demand commercial environments, such as hotels, hospitals, and office buildings.
- Data Centers and IT Infrastructure: Provides critical protection in data centers, server rooms, and network hubs where stable and uninterrupted power is vital.
- Utility and Substation Networks: Suitable for circuit protection in substations and other utility infrastructure, ensuring reliability in complex power grids.
- Renewable Energy Installations: Offers dependable circuit protection in renewable energy systems, like solar or wind farms, which can experience variable loads.
Benefits of Using Schneider C25B6TM200
- Enhanced Protection for High-Capacity Applications: Reliable performance ensures safety and reduces downtime, even in demanding settings.
- Versatile and Adaptable: Can be customized for different applications, making it a flexible choice for both industrial and commercial environments.
- Compact, Space-Saving Design: Allows for efficient panel integration without compromising performance.
- Low Maintenance Requirements: Built for long-term reliability, this MCCB requires minimal upkeep, making it cost-effective over time.
Conclusion
The Schneider C25B6TM200 MCCB is a robust, 200A circuit breaker designed to handle high-demand applications in industrial and commercial settings. With its high breaking capacity, thermal-magnetic trip unit, and adjustable settings, it offers powerful protection while maintaining flexibility and ease of installation. Ideal for settings ranging from industrial facilities to renewable energy systems, the C25B6TM200 provides the reliability and safety essential for modern, high-capacity electrical infrastructures.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSX new generation |
| Device short name | NSX250B |
| product or component type | Circuit breaker |
| Device application | Distribution |
| poles description | 4P |
| Protected poles description | 3D |
| Neutral position | Left |
| [In] rated current | 200 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | B 25 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 15.4 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 200 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
| Neutral protection settings | No protection (3D) |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 5...10 x In |
| Earth-leakage protection | Without |
| Number of slots for electrical auxiliaries | 5 slot(s) |
| Width (W) | 140 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| net weight | 2.8 kg |
| Standards | EN/IEC 60947 |
|---|---|
| Product certifications | CCC EAC Marine |
| Overvoltage category | Class II |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.5 cm |
| Package 1 Width | 14.5 cm |
| Package 1 Length | 19 cm |
| Package 1 Weight | 2.6375 kg |
| Unit Type of Package 2 | CAR |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 23 cm |
| Package 2 Width | 39 cm |
| Package 2 Length | 49 cm |
| Package 2 Weight | 16.7105 kg |
| Unit Type of Package 3 | PAL |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 107 cm |
| Package 3 Width | 40 cm |
| Package 3 Length | 60 cm |
| Package 3 Weight | 138.684 kg |