Schneider C11N3TM080B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 3 Poles 3d, 80A rating TMD trip unit, compression lugs and busbar connectors
Schneider C11N3TM080B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 3 Poles 3d, 80A rating TMD trip unit, compression lugs and busbar connectors
Description
Schneider C11N3TM080B: A Comprehensive Overview of Its Features and Applications
Introduction
Circuit breakers are critical components in electrical systems, providing essential protection against overloads and short circuits. it is a standout product in this category, known for its reliability and advanced features. This article delves into the key aspects of this circuit breaker and its significance in contemporary electrical installations.
What is Schneider C11N3TM080B?
Product Description
it is a high-quality circuit breaker designed to protect electrical circuits from overcurrents and short circuits. As part of Schneider Electric’s extensive range of circuit protection devices, it boasts a robust construction and cutting-edge features.
Key Specifications
- Rated Current: 80A
- Voltage Rating: 690V AC
- Breaking Capacity: 25kA at 415V AC
- Mounting Type: Fixed
- Standards Compliance: IEC 60947-2
Features of Schneider C11N3TM080B
Performance Capabilities
it delivers outstanding performance, efficiently managing high electrical loads.
Safety Features
It includes advanced safety mechanisms such as thermal-magnetic trip units, ensuring reliable protection against overcurrents and short circuits.
Durability
Built with high-quality materials, this circuit breaker is designed to endure demanding operating conditions, providing long-term reliability.
Benefits of Using Schneider C11N3TM080B
Enhanced Protection
It offers comprehensive protection for electrical circuits, significantly reducing the risk of damage due to electrical faults.
Energy Efficiency
Its design promotes energy efficiency, helping to reduce energy consumption and contribute to overall energy savings.
Cost Savings
With its durable construction and minimal maintenance requirements, it provides cost-effective operation over its lifespan.
Applications of Schneider C11N3TM080B
Industrial Applications
Ideal for industrial settings where robust circuit protection is essential for continuous operations.
Commercial Installations
Suitable for various commercial applications, ensuring reliable electrical protection in office buildings, manufacturing facilities, and retail outlets.
Residential Use
While primarily used in larger installations, it can also provide enhanced protection for residential electrical systems with high power requirements.
Installation Guide
Step-by-Step Installation Process
- Power Off: Ensure the power supply is turned off before starting the installation process.
- Mounting: Securely mount the circuit breaker in the electrical panel according to the manufacturer’s guidelines.
- Wiring: Follow the provided wiring diagram to ensure correct connections.
- Testing: After installation, perform thorough testing to verify proper functionality.
Tools Required
- Screwdriver
- Wire strippers
- Multimeter
- Safety gloves and goggles
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSXm new generation |
| Range of product | ComPacT NSXm new generation |
| Device short name | NSXm 160N |
| product or component type | Circuit breaker |
| Device application | Distribution |
| poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 80 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | N 50 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 6.96 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | Compression lug/busbar |
| Connection pitch | 35 mm with spreaders 27 mm without spreaders |
| 9 mm pitches | 9 module |
| Trip unit rating | 80 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 1000 A |
| Earth-leakage protection | Without |
| Number of slots for electrical auxiliaries | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| Local signalling | Flag (green) for presence of auxiliary contacts |
| Width (W) | 81 mm |
| Height (H) | 137 mm |
| Depth (D) | 80 mm |
| net weight | 1.06 kg |
| Colour | Grey (RAL 7016) |
| Standards | EN/IEC 60947 |
|---|---|
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 2000 m without derating 5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 12.0 cm |
| Package 1 Width | 9.0 cm |
| Package 1 Length | 21.0 cm |
| Package 1 Weight | 1.1 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 9 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 10.276 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider C11N3TM080L | Circuit breaker, ComPacT NSXm 160N, 50kA/415VAC, 3 poles, TMD trip unit 80A, EverLink lugs
Schneider C12N6TM125L | Circuit breaker, ComPacT NSXm 160N, 50kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 125A, EverLink lugs
Schneider C12F6TM125B | Circuit breaker, ComPacT NSXm 160F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 125A, lugs/busbars
Schneider C12B6TM160L | Circuit breaker ComPacT NSXm B (25kA at 415VAC), 4 Poles 3d, 160A rating TMD trip unit, EverLink connectors
Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors
-
0
Reviews
There are no reviews yet.