Description

Schneider C16F6TM160 | Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 160A, 4 poles 3d

Schneider C16F6TM160: Product Overview and Applications

Introduction

The Schneider C16F6TM160 is a molded case circuit breaker (MCCB) built to deliver reliable circuit protection for medium- to high-power electrical systems. With a rated current of 160A, this MCCB is suited for industrial, commercial, and high-capacity applications where safeguarding against overloads, short circuits, and electrical faults is essential. The C16F6TM160 integrates thermal and magnetic trip units for precise fault response, providing high-performance protection with Schneider’s trusted engineering.

Key Features of Schneider C16F6TM160

  • High Current Rating (160A): Suitable for systems with moderate to high power demands, ensuring dependable protection for essential circuits.
  • Thermal-Magnetic Trip Mechanism: Features a dual-mode trip unit that offers thermal sensing for overload protection and magnetic sensing for immediate response to short circuits.
  • High Breaking Capacity: Designed to handle significant fault currents, ensuring stability and safety in high-load environments.
  • Robust and Compact Design: Built for longevity and resilience, this MCCB fits into standard panels while delivering reliable circuit protection.
  • Adjustable Trip Settings: Allows customized protection, adapting to varying application requirements for optimized safety and operational flexibility.

Applications of Schneider C16F6TM160

  1. Industrial Equipment and Machinery: Protects high-power machinery, such as motors, pumps, and conveyor systems, in manufacturing and processing facilities.
  2. Commercial Power Distribution: Provides reliable circuit protection for commercial properties with high energy demands, including lighting, HVAC, and elevator systems.
  3. Data Centers and IT Infrastructure: Ensures stable power for essential systems, protecting against faults in data centers, server rooms, and communication hubs.
  4. Renewable Energy Installations: Ideal for use in medium- to high-capacity renewable energy systems, such as solar farms, where dependable fault protection is crucial.
  5. Utility and Substation Applications: Suitable for use in utility networks and substations, ensuring continuity of service and fault tolerance across complex power grids.

Benefits of Using Schneider C16F6TM160

  • Enhanced Protection for High-Demand Applications: Provides robust circuit protection for high-power equipment and systems, reducing the risk of electrical damage.
  • Versatility Across Multiple Settings: Suitable for both industrial and commercial uses, with adjustable settings that make it adaptable to different environments.
  • Space-Efficient Design: Compact and easy to install in various panel configurations, maximizing space and efficiency.
  • Low Maintenance and High Reliability: Designed to operate with minimal maintenance requirements, ensuring continuous protection with high dependability.

Conclusion

The Schneider C16F6TM160 MCCB is an excellent choice for those requiring robust protection in medium- to high-capacity electrical systems. With its 160A rating, dual-mode trip mechanism, and compact design, it offers high performance for a range of demanding applications, from industrial machinery to utility networks. Whether used in renewable energy systems or commercial infrastructure, this MCCB ensures the safety and reliability essential for any high-performance electrical setup.

Additional information

brands

Schneider Electric

Specifications

Main
Range ComPacT new generation
Product name ComPacT NSX new generation
Device short name NSX160F
Product or component type Circuit breaker
Device application Distribution
poles description 4P
Protected poles description 3D
Neutral position Left
[In] rated current 160 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508
Performance level F 36 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 40000 cycles
Electrical durability 40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Power dissipation per pole 13.95 W
Mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating 160 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
[tr] long-time protection delay adjustment range 120…400 s at 1.5 x In 15 s at 6 x Ir
Neutral protection settings No protection (3D)
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 1250 A
Earth-leakage protection Without
Number of slots for electrical auxiliaries 5 slot(s)
Width (W) 140 mm
Height (H) 161 mm
Depth (D) 86 mm
Net weight 2.6 kg
Environment
Standards EN/IEC 60947-2
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 14.0 cm
Package 1 Width 14.5 cm
Package 1 Length 19.0 cm
Package 1 Weight 2.378 kg
Unit Type of Package 2 S03
Number of Units in Package 2 6
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 14.642 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider C16F6TM160 | Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 160A, 4 poles 3d”