Schneider LV510477 | Easypact CVS – CVS100N circuit breaker – 3P/3d

Technical Specifications:

  1. Product Type: The LV510477 is a 3-pole (3P) circuit breaker from the Easypact CVS100N range, providing protection for three-phase systems. It is designed to protect electrical systems from overloads, short circuits, and other fault conditions.

  2. Rated Current: This model is rated for a 100A continuous current, providing effective protection for electrical circuits with loads up to 100A.

  3. Voltage Rating: The circuit breaker can handle electrical systems operating at up to 690V AC, making it suitable for use in a wide range of applications, from industrial machinery to commercial power systems.

  4. Short-Circuit Breaking Capacity: The Easypact CVS100N circuit breaker features a high short-circuit breaking capacity, allowing it to interrupt and safely disconnect high fault currents, protecting the system from electrical hazards.

  5. Trip Unit: The circuit breaker is equipped with an electronic trip unit that provides precise overload protection and short-circuit protection. This ensures that the breaker responds quickly to both sustained overcurrents and short-circuit conditions, enhancing the safety and reliability of the system.

  6. Number of Poles: The LV510477 is a 3-pole circuit breaker, designed specifically for three-phase electrical systems, offering balanced protection for all three phases.

  7. Frame Size: The CVS100N circuit breaker is part of the 100A frame size category, ensuring it is capable of protecting circuits that carry up to 100A of continuous current.

  8. Mounting Type: The circuit breaker is designed for DIN rail mounting, making it easy to install in standard DIN rail electrical panels and switchboards, which is a common mounting method in industrial and commercial installations.

  9. Compliance and Standards: The LV510477 complies with international standards such as IEC, guaranteeing that it meets safety, performance, and quality requirements for circuit protection.

Features:

  1. Overload and Short-Circuit Protection: The Easypact CVS100N circuit breaker provides thermal-magnetic protection, which ensures that the electrical system is protected from both overload conditions and short-circuit faults.

  2. High Breaking Capacity: The LV510477 is designed to handle high fault currents, making it suitable for installations that require robust protection against short-circuit conditions.

  3. 3-Pole Configuration: The 3-pole design ensures balanced protection for three-phase systems, providing comprehensive coverage for electrical circuits operating on three-phase power.

  4. DIN Rail Mounting: The circuit breaker can be mounted on DIN rails, ensuring easy installation in a variety of electrical panels and distribution boards.

  5. Adjustable Settings: The electronic trip unit in the circuit breaker allows for adjustable settings, enabling the user to tailor the protection parameters for different loads and operational conditions.

  6. Compact Design: Despite offering powerful protection, the Easypact CVS100N circuit breaker is designed to be compact, which allows for easy integration into installations where space is limited.

  7. Durability and Reliability: The circuit breaker is built from high-quality materials, ensuring long-lasting performance and reliability even in harsh operating environments.

  8. Ease of Use: The Easypact CVS100N circuit breaker is designed for ease of use, with clear and intuitive controls, making it simple to install, adjust, and maintain.

Applications:

The Schneider LV510477 Easypact CVS100N circuit breaker is ideal for use in various applications, including:

  1. Industrial Electrical Systems: The LV510477 provides reliable protection for industrial machinery, motors, and control panels in three-phase systems, helping to prevent damage from overloads and short circuits.

  2. Commercial Installations: In commercial buildings and facilities, this circuit breaker ensures the safety of electrical distribution systems, protecting against overload conditions and fault currents.

  3. Motor Protection: The Easypact CVS100N is commonly used to protect motors in industrial and commercial applications. It provides reliable protection against overload and short-circuit faults.

  4. Power Distribution: The LV510477 is used in power distribution panels, ensuring safe and efficient operation of the electrical system. Its high short-circuit breaking capacity helps safeguard the system from electrical faults.

  5. Renewable Energy Systems: Ideal for use in solar power and wind energy systems, where protection is essential for handling electrical faults and ensuring the safe operation of renewable energy systems.

  6. Residential Three-Phase Systems: The circuit breaker can be used in three-phase residential systems, providing protection for circuits that require higher protection, such as those used for large appliances or specialized equipment

Additional information

brands

Schneider Electric

Specifications

Main
Range EasyPact
Range of product EasyPact CVS100...250
Product name EasyPact CVS
Device short name CVS100N
Product or component type Circuit breaker
Device application Distribution
poles description 3P
Protected poles description 3D
Earth leakage protection (Vigi add on) Without
[In] rated current 100 A at 40 °C
Network type AC
Utilisation category Category A
[Icu] Breaking capacity 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit rating 100 A at 40 °C
Protection type Short-circuit protection (magnetic) Overload protection (thermal)
Complementary
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
Network frequency 50/60 Hz
Breaking capacity code N
[Ics] rated service breaking capacity 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 30000 cycles
Electrical durability 12000 cycles 415 V In conforming to IEC 60947-2
Control type Toggle
Thermal protection adjustment range 0…100 A
Long time pick-up adjustment type Ir Adjustable
Long time pick-up adjustment range 0.7...1 x In
Long time delay adjustment type Fixed
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Ii Fixed
instantaneous pick-up adjustment range 800 A
Contact position indicator Yes
Mounting support Backplate
Mounting mode Fixed
Upside connection Front
downside connection Front
Connections - terminals Screw connection
Connection pitch 35 mm
Compatibility code CVS100
Width 105 mm
Depth 86 mm
Height 161 mm
Net weight 1.5 kg
Environment
Standards EN 60947-2 IEC 60947-2
Product certifications GOST IEC
Electrical shock protection class Class II
IP degree of protection IP40
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.7 cm
Package 1 Width 13.3 cm
Package 1 Length 19.1 cm
Package 1 Weight 1.78 kg
Unit Type of Package 2 S03
Number of Units in Package 2 7
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 2 Weight 12.46 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider LV510477 | Easypact CVS – CVS100N circuit breaker – 3P/3d”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare