Schneider LV516333 | circuit breaker EasyPact CVS160F, 36 kA at 415 VAC, 160 A rating thermal magnetic TM-D trip unit, 3P 3d
Schneider LV516333 | circuit breaker EasyPact CVS160F, 36 kA at 415 VAC, 160 A rating thermal magnetic TM-D trip unit, 3P 3d
Description
Schneider LV516333 | circuit breaker EasyPact CVS160F, 36 kA at 415 VAC, 160 A rating thermal magnetic TM-D trip unit, 3P 3d
EasyPact CVS160F is a 3 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality.
It is an optimal choice for small and medium-sized buildings protection applications.
The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 440VAC 50/60Hz.
This product embeds a 160A rating thermal-magnetic trip unit (TMD).
TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection.
This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.
Schneider Electric is a global leader in energy management and automation solutions. With its commitment to innovation and sustainability, the company has delivered high-quality products that meet the evolving needs of various industries. Among its standout offerings is the Schneider LV516333, a robust component designed to enhance electrical systems with unmatched reliability and performance.
Understanding the Schneider LV516333
The LV516333 is a premium product from Schneider Electric’s range of electrical components. Known for its superior quality, it is engineered to handle demanding environments and deliver optimal performance.
Key Features of the LV516333
- High Durability: Built to withstand harsh conditions.
- Energy Efficiency: Minimizes power losses, contributing to reduced energy consumption.
- Easy Integration: Compatible with a variety of electrical systems.
Technical Specifications
- Voltage Rating: Designed for high-voltage applications.
- Current Rating: Supports a wide range of current loads.
- Dimensions: Compact and space-saving design.
- Weight: Lightweight for easy handling.
Benefits of the Schneider LV516333
- Reliability: Ensures consistent performance under all conditions.
- Durability: Constructed with premium materials for a longer lifespan.
- Energy Efficiency: Optimized to reduce energy waste and promote sustainability.
- Ease of Installation: Simplified design for quick and hassle-free setup.
Applications of the Schneider LV516333
- Industrial: Suitable for manufacturing plants and heavy machinery.
- Commercial: Ideal for office buildings and large commercial complexes.
- Residential: Provides reliable power solutions for homes.
EasyPact CVS160F is compliant with international standards (IEC 60947, CCC, EAC). It can be installed in class II insulation switchboards as it is a class II front face device (IEC 60664-1).
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | EasyPact |
|---|---|
| Range of product | EasyPact CVS100...250 |
| Product name | EasyPact CVS |
| Device short name | CVS160F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| Earth leakage protection (Vigi add on) | Without |
| [In] rated current | 160 A at 40 °C |
| Network type | AC |
| Utilisation category | Category A |
| [Icu] Breaking capacity | 36 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit rating | 160 A at 40 °C |
| Protection type | Short-circuit protection (magnetic) Overload protection (thermal) |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
|---|---|
| Network frequency | 50/60 Hz |
| Breaking capacity code | F |
| [Ics] rated service breaking capacity | 18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 25000 cycles |
| Electrical durability | 12000 cycles 415 V In conforming to IEC 60947-2 |
| Control type | Toggle |
| Thermal protection adjustment range | 112…160 A |
| Long time pick-up adjustment type Ir | Adjustable |
| Long time pick-up adjustment range | 0.7...1 x In |
| Long time delay adjustment type | Fixed |
| Instantaneous pick-up adjustment type Ii | Fixed |
| Instantaneous pick-up adjustment range | 1250 A |
| Contact position indicator | Yes |
| Mounting support | Backplate |
| Mounting mode | Fixed |
| Upside connection | Front |
| Downside connection | Front |
| Connections - terminals | Screw connection |
| Connection pitch | 35 mm |
| Compatibility code | CVS160 |
| Width | 105 mm |
| Depth | 86 mm |
| Height | 161 mm |
| Net weight | 1.5 kg |
| Standards | IEC 60947-2 EN 60947-2 |
|---|---|
| Product certifications | IEC GOST |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14 cm |
| Package 1 Width | 11.5 cm |
| Package 1 Length | 19 cm |
| Package 1 Weight | 2.04 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 16.32 kg |
Reviews (0)
Recommended for you
-
0
Schneider A9N26924 | Acti9 – Auxiliary contact OC plus 1 SD and OF ac dc
-
0
Schneider A9N18469 | Miniature circuit-breaker, Acti9 C120H, 3P, 100 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18447 | Miniature circuit-breaker, Acti9 C120H, 1P, 100 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18357 | Miniature circuit-breaker, Acti9 C120N, 1P, 80 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Schneider A9K24232 | Miniature circuit-breaker, Acti9 iK60N, 2P, 32 A, C curve, 6000 A (IEC 60898-1)
-
0
Reviews
There are no reviews yet.