Schneider C160H420FM | Circuit breaker, ComPacT NS1600H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1600A
Schneider C160H420FM | Circuit breaker, ComPacT NS1600H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1600A
-
Delivers up to 1600A capacity, perfect for high-demand power systems.
-
70kA fault interruption capability ensures maximum system safety and uptime.
-
Advanced electronic trip unit (MicroLogic 2.0) gives reliable and adjustable protection.
-
4-pole design ensures comprehensive circuit isolation, including neutral.
-
Built for harsh industrial environments, ensuring long-lasting performance.
Description
Schneider C160H420FM | Circuit breaker, ComPacT NS1600H, 70kA at 415VAC, 4P, fixed, manually operated, MicroLogic 2.0 control unit, 1600A
Technical Specifications:
-
Manufacturer: Schneider Electric
-
Model: C160H420FM
-
Series: ComPacT NS1600H
-
Rated Current (In): 1600 Amperes
-
Poles: 4 poles (3 phases + neutral)
-
Breaking Capacity (Icu): 70 kA at 415 VAC
-
Rated Operational Voltage (Ue): Up to 690 V AC
-
Rated Insulation Voltage (Ui): 800 V AC
-
Trip Unit: MicroLogic 2.0 – electronic protection
-
Mounting Type: Fixed
-
Operation: Manual (toggle handle)
-
Protection Types: Overload, short circuit (with adjustable thresholds)
-
Standard Compliance: IEC 60947-2
-
Installation Position: Vertical or horizontal
-
Mechanical Durability: High, designed for extended operation in industrial environments
Key Features:
-
High breaking capacity of 70kA provides strong protection in high-fault environments.
-
MicroLogic 2.0 trip unit allows precise adjustment and better control of protection settings.
-
4-pole configuration ensures safe disconnection of all power lines including the neutral.
-
Compact and robust design ideal for industrial panels and space-restricted switchboards.
-
Manual fixed operation provides reliability and ease of use in maintenance and emergency shutdown.
Applications:
-
Main protection device in industrial and commercial low-voltage power distribution systems.
-
Critical infrastructure such as hospitals, airports, and data centers requiring high reliability.
-
Backup generators and transfer panels where fault interruption speed is essential.
-
Large mechanical systems including HVAC, pumps, and compressors.
-
Power plants and substations needing stable and durable protection.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT |
|---|---|
| Product name | ComPacT NS new generation |
| Range of product | ComPacT NS630b...1600 new generation |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Number of poles | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 1600 A at 50 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category B |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H 70 kA 415 V AC |
| Trip unit name | MicroLogic 2.0 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LI |
| Control type | Manually operated |
| Mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Icw] rated short-time withstand current | 19.2 kA 1 s conforming to IEC 60947-2 |
| Mechanical durability | 10000 cycles |
| Electrical durability | 1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2 |
| Power losses | 74 W |
| Mounting support | Backplate |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 70 mm |
| Protection type | L : for overload protection (long time) I : for instantaneous short-circuit protection |
| Trip unit rating | 1600 A at 50 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
| [tr] long-time delay adjustment range | 12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir |
| Thermal memory | 20 mn |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
| Earth-leakage protection | Without |
| Neutral protection setting | No protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D) |
| Zone selective interlocking ZSI | Without |
| Auxiliary contact composition | 1 NO/NC |
| Local signalling | 4 LEDs (red) for fault indication 1 LED (yellow) for overload |
| Width (W) | 280 mm |
| Height (H) | 327 mm |
| Depth (D) | 147 mm |
| Net weight | 18 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Product certifications | IECEE CB Scheme |
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60947 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to EN 50102 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 37.000 cm |
| Package 1 Width | 38.000 cm |
| Package 1 Length | 30.000 cm |
| Package 1 Weight | 16.763 kg |
Download Cataloge
Download Cataloge
Download Cataloge
Download Cataloge
Reviews (0)
Recommended for you
Schneider A9N61502 | miniature circuit breaker – C60H – 1 pole – 2 A – C curve
-
0
Schneider A9N26946 | MX Shunt Trip MX plus 1 OF 220-415Vac dc
-
0
Schneider A9N18470 | Miniature circuit-breaker, Acti9 C120H, 3P, 125 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9L40101 | iPRD40r modular surge arrester – 1P – 350V – with remote transfert
-
0
Schneider A9K24316 | Miniature circuit-breaker, Acti9 iK60N, 3P, 16 A, C curve, 6000 A (IEC 60898-1)
-
0
Reviews
There are no reviews yet.