Schneider G12T3F50 | Circuit breaker, GoPact MCCB 125, 3 poles, 10kA at 415VAC, 50A rating, TMD trip unit, fixed thermal protection
Description
Schneider G12T3F50 | Circuit breaker, GoPact MCCB 125, 3 poles, 10kA at 415VAC, 50A rating, TMD trip unit, fixed thermal protection
Schneider G12T3F50 | Circuit Breaker, GoPact MCCB 125, 3 poles, 10kA at 415VAC, 50A rating, TMD trip unit, fixed thermal protection description
Introduction to Schneider G12T3F50 Circuit Breaker
it is a cutting-edge circuit breaker designed to provide reliable protection for electrical systems. As part of it series, it combines advanced technology with robust construction to ensure safety and efficiency in power distribution networks.
Understanding MCCBs (Molded Case Circuit Breakers)
MCCBs are essential components in electrical systems, offering protection against overloads, short circuits, and other electrical faults. They are widely used in industrial, commercial, and residential applications due to their versatility and performance.
Features of Schneider G12T3F50 MCCB
The Schneider G12T3F50 MCCB comes with a range of features that set it apart:
- Three poles: Suitable for three-phase electrical systems.
- 10kA Breaking Capacity: Capable of interrupting fault currents up to 10kA.
- 50A Rating: Designed to handle currents up to 50A.
- TMD Trip Unit: Provides precise and reliable tripping based on thermal-magnetic characteristics.
- Fixed Thermal Protection: Ensures optimal protection against thermal overloads.
Technical Specifications
- Poles: 3
- Breaking Capacity: 10kA at 415VAC
- Rating: 50A
- Trip Unit: TMD
- Thermal Protection: Fixed
Applications of Schneider G12T3F50
The G12T3F50 MCCB is suitable for a wide range of applications, including industrial machinery, commercial buildings, data centers, and more. Its reliable performance and advanced protection features make it a preferred choice for critical electrical systems.
Installation and Maintenance Tips
Proper installation and regular maintenance are crucial for ensuring the optimal performance and longevity of the Schneider G12T3F50 MCCB. Follow manufacturer guidelines and consult qualified professionals for installation and maintenance tasks.
Advantages
- Enhanced safety due to advanced trip unit and thermal protection.
- Reliable performance under varying load conditions.
- Compatibility with diverse electrical systems.
- Longevity and durability, reducing downtime and maintenance costs.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | GoPact MCCB |
|---|---|
| Product or component type | Circuit breaker |
| Product name | GoPact MCCB 125 |
| Device application | Distribution |
| Poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 50 A at 40 °C |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 10 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Performance level | T 10 kA 380/415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 440 V AC conforming to EN/IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 10 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Mechanical durability | 30000 cycles |
| Electrical durability | 8000 cycles at 415 V In |
| Power dissipation per pole | 18.7 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection terminals | screw terminals |
| Connection pitch | 25 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 50 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Fixed |
| [Ir] long-time protection pick-up adjustment range | 1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 10 x In |
| Width (W) | 75 mm |
| Height (H) | 130 mm |
| Depth (D) | 60 mm |
| Net weight | 0.7 kg |
| Colour | Grey (RAL 7035) |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H |
|---|---|
| Overvoltage category | III |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…55 °C |
| Ambient air temperature for storage | -35…85 °C |
| Operating altitude | 0...2000 m without derating 2000...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 12.4 cm |
| Package 1 Width | 8.5 cm |
| Package 1 Length | 13.9 cm |
| Package 1 Weight | 908 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 7.579 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 128 |
| Package 3 Height | 75 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 129.764 kg |