Schneider LC1E1201M5 | Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3/AC-3e,<=440V,12A,220V AC coil,50Hz,1NC auxiliary contact
Description
Schneider LC1E1201M5 | Contactor,EasyPact TVS,3P(3NO),AC-3,<=440V,12A,220V AC coil,50Hz,1NC auxiliary contact
Schneider LC1E1201M5 Description
it is a versatile and reliable contactor designed for various industrial applications. With its advanced features and robust construction, it provides efficient performance and ensures the smooth operation of electrical systems.
Introduction
it is part of the TeSys E range of contactors manufactured by Schneider Electric, a global leader in energy management and automation solutions. It is designed to control electrical circuits in industrial and commercial environments, offering high performance and reliability.
Features of Schneider LC1E1201M5
Electrical Specifications
The Schneider LC1E1201M5 contactor is rated for a voltage range of 24V AC to 240V AC, making it suitable for a wide range of applications. It has a current rating of 12A, allowing it to handle moderate to high electrical loads with ease.
Mechanical Specifications
Constructed with high-quality materials, it contactor is built to withstand harsh operating conditions. It features durable contacts that ensure long-term reliability and performance, even in demanding environments.
Environmental Specifications
With its compact and rugged design,it contactor is suitable for use in diverse environmental conditions. It has a wide operating temperature range and is resistant to dust, moisture, and vibration, making it ideal for both indoor and outdoor applications.
Applications of Schneider LC1E1201M5
it contactor finds widespread use across various industries due to its versatility and reliability. Some common applications include:
Industrial Automation
In industrial automation systems, it contactor is used to control motors, pumps, and other electrical loads, ensuring smooth and efficient operation.
HVAC Systems
In heating, ventilation, and air conditioning (HVAC) systems, it contactor helps regulate the flow of electricity to compressors, fans, and other components, maintaining optimal temperature and humidity levels.
Water Treatment Plants
In water treatment plants, it contactor plays a crucial role in controlling pumps, valves, and other equipment, facilitating the treatment and distribution of water to homes and businesses.
Advantages it
it contactor offers several advantages over traditional contactors:
- High reliability and durability
- Wide operating voltage range
- Compact and space-saving design
- Easy installation and maintenance
Installation and Maintenance Tips
When installing and maintaining it contactor, follow these guidelines:
Wiring Guidelines
- Ensure proper sizing of wires and cables according to the contactor’s specifications.
- Follow all local electrical codes and regulations.
- Double-check all connections to ensure tight and secure fittings.
Troubleshooting Techniques
- Use a multimeter to check for continuity and proper voltage levels.
- Inspect for any signs of overheating or damage.
- Refer to the user manual for troubleshooting tips and guidelines.
Comparison with Similar Products
Compared to similar products on the market, it contactor stands out for its superior performance, reliability, and durability. It offers a wider operating voltage range and more advanced features, making it the preferred choice for many industrial and commercial applications.
Customer Reviews and Testimonials
Customers who have used it contactor praise its reliability, ease of installation, and long-term performance. Many report experiencing fewer downtime incidents and reduced maintenance costs after switching to this contactor.
Conclusion
In conclusion, it contactor is a top choice for industrial and commercial applications, offering superior performance, reliability, and durability. With its advanced features and robust construction, it ensures the smooth operation of electrical systems in diverse environments.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | Easy TeSys |
|---|---|
| range of product | Easy TeSys Control |
| product or component type | Contactor |
| Device short name | LC1E |
| Contactor application | Motor control Resistive load |
| Utilisation category | AC-3 AC-3e AC-1 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
| [Ie] rated operational current | 12 A (at <55 °C) at <= 440 V AC AC-3 for power circuit 12 A (at <55 °C) at <= 440 V AC AC-3e for power circuit 25 A (at <55 °C) at <= 440 V AC AC-1 for power circuit |
| [Uc] control circuit voltage | 220 V AC 50 Hz |
| Motor power kW | 3 kW at 220...230 V AC 50/60 Hz 5.5 kW at 380...400 V AC 50/60 Hz 5.5 kW at 415 V AC 50/60 Hz 5.5 kW at 440 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 7.5 kW at 660...690 V AC 50/60 Hz |
|---|---|
| Pole contact composition | 3 NO |
| [Ith] conventional free air thermal current | 25 A (at 55 °C) for power circuit |
| Irms rated making capacity | 120 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
| Rated breaking capacity | 96 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit 61 A 40 °C - 60 s for power circuit 30 A 40 °C - 600 s for power circuit |
| Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 25 A gG at <= 690 V coordination type 1 for power circuit |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 0.36 W AC-3 1.6 W AC-1 |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
| Mechanical durability | 10000000 cycles |
| Electrical durability | 1400000 cycles AC-3 300000 cycles AC-1 |
| Control circuit type | AC at 50 Hz |
| Control circuit voltage limits | 0.85...1.1 Uc (-5…55 °C):operational 50 Hz 0.3...0.6 Uc (-5…55 °C):drop-out 50 Hz |
| Inrush power in VA | 95 VA 50 Hz cos phi 0.75 (at 20 °C) 95 VA 60 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 8.3 VA 50 Hz cos phi 0.3 (at 20 °C) 8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W for control circuit |
| Operating time | 12...22 ms on closing 4...19 ms on opening |
| Maximum operating rate | 1800 cyc/h 60 °C |
| Connections - terminals | Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end |
| Tightening torque | Power circuit: 1.2 N.m Control circuit: 1.2 N.m |
| Auxiliary contact composition | 1 NC |
| Minimum switching voltage | 17 V for control circuit |
| Minimum switching current | 5 mA for control circuit |
| Insulation resistance | > 10 MOhm for control circuit |
| Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
| mounting support | Plate DIN rail |
| Standards | IEC 60947-4-1 IEC 60947-1 IEC 60947-5-1 |
|---|---|
| Product certifications | CE EAC |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 |
| Permissible ambient air temperature around the device | -20…70 °C at Uc -60…80 °C storage -5…55 °C operation |
| Operating altitude | 3000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (7 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) |
| Height | 74 mm |
| Width | 45 mm |
| Depth | 80 mm |
| net weight | 0.3 kg |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 8.700 cm |
| Package 1 Width | 5.000 cm |
| Package 1 Length | 7.600 cm |
| Package 1 Weight | 345.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 36 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 12.882 kg |
| Warranty | 18 months |
|---|
Main documents
Main documents
| Datasheet | Download Datasheet |
| Product datasheet | LC1E1201M5 |
|
Instruction sheet
|
Download |
| Catalog | Download |
|
Environmental disclosure
|
Download |
| CAD Files | Download |
Main documents
| Datasheet | Download Datasheet |
| Product datasheet | LC1E1201M5 |
|
Instruction sheet |
Download |
| Catalog | Download |
|
Environmental disclosure |
Download |
| CAD Files | Download |
Reviews
There are no reviews yet.