Description

Schneider METSEPM5100 | PM5100 Meter, without communication, up to 15th H, 1DO 33 alarms

Product Overview: Schneider METSEPM5100 Power Meter – PM5100, No Communication, Harmonics up to 15th, 1DO, 33 Alarms

The Schneider Electric METSEPM5100 is a versatile and compact power meter designed for panel builders and facility managers. It belongs to the PM5000 series, known for providing reliable measurements in electrical distribution systems. This model does not include communication, making it ideal for local display applications with built-in alarming capabilities.

Key Features:

  • Brand: Schneider Electric

  • Series: PM5000

  • Model Number: METSEPM5100

  • Type: Power Meter

  • Display: Backlit LCD

  • Communication: Not included (no RS485 or Ethernet)

  • Digital Output: 1 DO (Digital Output)

  • Alarms: 33 configurable alarms

  • Harmonics Measurement: Up to 15th harmonic

Technical Specifications:

  • Voltage Measurement: Phase-to-phase and phase-to-neutral

  • Current Inputs: 1 A or 5 A via external CTs

  • Frequency Range: 45–65 Hz

  • Accuracy Class:
    – Voltage: ±0.5%
    – Current: ±0.5%
    – Power: ±1%

  • Mounting: DIN rail or panel flush mount

  • Power Supply: 100…277 V AC / 125…250 V DC

  • Operating Temperature: -25°C to +70°C

  • Compliance: IEC 61010, IEC 61557-12

Functional Features:

  • Real-Time Monitoring:
    – Measures voltage, current, power, power factor, frequency, and energy

  • Harmonic Analysis:
    – Displays total harmonic distortion (THD) up to the 15th harmonic

  • Alarm Management:
    – Supports 33 high/low alarms for quick fault detection

  • Digital Output (1 DO):
    – Configurable for alarms or energy pulsing

  • User-Friendly Interface:
    – Large, clear LCD display with intuitive navigation buttons

Applications:

  • Electrical panels in commercial and industrial buildings

  • Local energy monitoring in switchboards

  • Power quality assessment (basic level)

  • Preventive maintenance planning

  • Sub-billing and load monitoring

Benefits:

  • Accurate and Reliable:
    – Delivers precise energy readings for informed decision-making

  • Compact Design:
    – Easily fits in tight panel spaces

  • High Alarm Capacity:
    – Provides 33 configurable alarms for real-time diagnostics

  • Cost-Effective:
    – Perfect for applications that don’t require network connectivity

  • Plug-and-Play Installation:
    – Simple to mount and set up

Typical Users:

  • Facility and energy managers

  • Panel builders and OEMs

  • Electrical contractors

  • Commercial building operators

  • Maintenance technicians seeking visual local monitoring

Additional information

brands

Schneider Electric

Specifications

Main
Range PowerLogic
Product name PowerLogic PM5000
Device short name PM5100
Product or component type Power meter
Complementary
Power quality analysis Up to the 15th harmonic
Device application Power monitoring
Type of measurement Current Voltage Frequency Power factor Energy Active and reactive power
supply voltage 90...450 V AC 45...65 Hz 100...300 V DC
Network frequency 60 Hz 50 Hz
[In] rated current 5 A 1 A
type of network 3P + N 1P + N 3P
Maximum power consumption in VA 11 VA at 415 V
Ride-through time 80 ms 120 V AC typical 100 ms 230 V AC typical 100 ms 415 V AC typical 50 ms 125 V DC typical
Display type Monochrome graphic LCD
Display resolution 128 x 128 pixels
Sampling rate 64 samples/cycle
Measurement current 50…8500 mA
Analogue input type Voltage (impedance 5 MOhm) Current (impedance <= 0.3 mOhm)
Measurement voltage 35…760 V AC 45...65 Hz between phases 20…400 V AC 45...65 Hz between phase and neutral
Frequency measurement range 45…65 Hz
Number of inputs 0
Measurement accuracy Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.5 Current +/- 0.5 % Voltage +/- 0.5 % Apparent energy +/- 0.5 % Reactive power +/- 2 %
Accuracy class Class 0.5S active energy conforming to IEC 62053-22
Number of outputs 1 pulse (energy)
Communication port protocol -
Communication port support -
data recording Min/max of instantaneous values Time stamping
Connections - terminals Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 RS485 link: screw terminal block4
Mounting mode Flush-mounted
Mounting support Framework
Standards EN 50470-1 IEC 62053-22:2020 UL 61010-1 IEC 62053-24 IEC 61557-12:2015 EN 50470-3 IEC 60529 IEC 62053-23:2020 IEC 62052-11:2020 IEC 62052-31:2015
Product certifications CE conforming to IEC 61010-1 CULus conforming to UL 61010-1
Width 96 mm
Depth 72 mm
height 96 mm
Net weight 380 g
Environment
Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2 Electrostatic discharge level 4 conforming to IEC 61000-4-2 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Surge immunity test conforming to IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection IP54 display: conforming to IEC 60529 IP30 rear: conforming to IEC 60529
Relative humidity 5…95 % at 50 °C non-condensing
Pollution degree 2
Ambient air temperature for operation -25…70 °C meter -20…70 °C display -25…-20 °C (with reduced performance) display
Ambient air temperature for storage -40…85 °C
Operating altitude 2000 m CAT III
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.0 cm
Package 1 Width 12.6 cm
Package 1 Length 12.6 cm
Package 1 Weight 550.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 6.54 kg
Unit Type of Package 3 P06
Number of Units in Package 3 96
Package 3 Height 50.0 cm
Package 3 Width 80.0 cm
Package 3 Length 60.0 cm
Package 3 Weight 61.44 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider METSEPM5100 | PM5100 Meter, without communication, up to 15th H, 1DO 33 alarms”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare