Schneider A9N18362 | Miniature circuit-breaker, Acti9 C120N, 2P, 100 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
Schneider A9N18362 | Miniature circuit-breaker, Acti9 C120N, 2P, 100A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
Description
Schneider A9N18362 | Miniature circuit-breaker, Acti9 C120N, 2P, 100A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
Technical Specifications
The A9N18362 is a 2-pole MCB with a rated current of 100 amperes, making it suitable for high-power applications.
It operates at 400/415 volts AC, at a frequency of 50/60 Hz.
The tripping curve is type C, which allows it to handle moderate inrush currents, such as those found in motor start-ups or inductive loads.
The breaking capacity is rated at 10,000 A according to IEC 60898-1 and 10 kA according to IEC 60947-2, ensuring strong protection in case of short circuits.
It is designed for DIN rail mounting, compatible with standard electrical panels.
The unit can operate in a wide temperature range from -25°C to +70°C, and has a protection degree of IP20 when installed in an enclosed panel.
Key Features
-
High Current Protection: Supports up to 100A, suitable for demanding electrical systems.
-
C Curve Tripping Characteristics: Ideal for general-purpose loads with moderate inrush currents.
-
Compact Modular Design: Fits seamlessly in distribution boards without taking excessive space.
-
DIN Rail Mountable: Quick and easy installation into standard electrical enclosures.
-
Manual Operation Handle: Clear ON/OFF indicator for easy status checking and manual control.
-
Durable Construction: Engineered to function effectively in harsh environments.
-
Low Maintenance: Long-lasting and reliable with minimal upkeep needed.
-
Compliant with Global Standards: Fully certified under IEC 60898-1 and IEC 60947-2 for safety and performance.
Typical Applications
The Schneider A9N18362 is versatile and robust, making it suitable for:
-
Industrial Power Systems: Protecting high-power circuits in manufacturing plants and processing facilities.
-
Commercial Buildings: Ensuring safe distribution in hotels, hospitals, malls, and office towers.
-
Main Distribution Panels: Used in large-scale electrical systems as a main or sub-main breaker.
-
Residential Smart Homes: For advanced home systems with high-power devices such as HVAC units and EV chargers.
-
Data Centers and IT Infrastructure: Protecting sensitive equipment from electrical faults.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | C120 |
|---|---|
| Range | Acti9 |
| Product name | C120 |
| Product or component type | Miniature circuit-breaker |
| Device short name | C120N |
| Device application | Distribution |
| Poles description | 2P |
| Number of protected poles | 2 |
| Neutral position | Left |
| [In] rated current | 100 A at 30 °C |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 10000 A Icn at 230...400 V AC 50/60 Hz conforming to EN/IEC 60898-1 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Network frequency | 50/60 Hz |
|---|---|
| [Ue] rated operational voltage | 380...415 V AC 50/60 Hz 220...240 V AC 50/60 Hz 440 V AC 50/60 Hz <= 250 V DC 230...400 V AC 50/60 Hz |
| Magnetic tripping limit | 5...10 x In |
| [Ics] rated service breaking capacity | 7500 A 75 % conforming to EN/IEC 60898-1 - 230...400 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC |
| Limitation class | 3 conforming to EN/IEC 60947-2 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
| Contact position indicator | Yes |
| control type | Toggle |
| local signalling | ON/OFF indication |
| Mounting mode | Clip-on |
| mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | YES |
| 9 mm pitches | 6 |
| height | 81 mm |
| Width | 54 mm |
| Depth | 73 mm |
| Net weight | 0.41 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 5000 cycles conforming to IEC 60947-2 |
| Locking options description | Handle sealable with cable diameter 0.7mm in OFF or ON position |
| Connections - terminals | Tunnel type terminals1…50 mm² rigid Tunnel type terminals1.5…35 mm² flexible |
| Wire stripping length | 15 mm |
| Tightening torque | 3.5 N.m |
| earth-leakage protection | Separate block |
| Standards | EN/IEC 60898-1 EN/IEC 60947-2 |
|---|---|
| product certifications | EAC |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 2000 m |
| ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.4 cm |
| Package 1 Width | 7.5 cm |
| Package 1 Length | 8.5 cm |
| Package 1 Weight | 385 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 8.5 cm |
| Package 2 Width | 9.5 cm |
| Package 2 Length | 33 cm |
| Package 2 Weight | 2.377 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 36 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 14.749 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download