Schneider A9N61510 | miniature circuit breaker – C60H – 1 pole – 15 A – C curve
Schneider A9N61510 | miniature circuit breaker – C60H – 1 pole – 15 A – C curve
Description
Schneider A9N61510 | miniature circuit breaker – C60H – 1 pole – 15 A – C curve
Technical Specifications A9N61510
-
Product Reference: A9N61510
-
Series: Acti9 C60H
-
Type: Miniature Circuit Breaker (MCB)
-
Number of Poles: 1P (Single Pole)
-
Rated Current (In): 15 A
-
Tripping Curve: C Curve (trips at 5–10 × In)
-
Breaking Capacity: Up to 6 kA (according to IEC/EN 60898-1)
-
Rated Operational Voltage: 230/400 V AC
-
Frequency: 50/60 Hz
-
Mounting Method: DIN rail (clip-on modular design)
-
Terminal Connection: Screw terminals (top and bottom)
-
Protection Rating: IP20 (when installed in suitable enclosure)
-
Standards and Compliance:
-
IEC/EN 60898-1
-
IEC/EN 60947-2
-
Key Features:
-
Efficient 15 A Protection
Ideal for moderate-load circuits such as power outlets and small appliances. -
C Curve Tripping Characteristic
Provides a balanced response to inrush currents while maintaining safety. -
Compact and Modular Form Factor
Saves space in electrical panels and simplifies future expansion. -
Durable Design
High mechanical and electrical endurance ensures long-term performance. -
Quick Installation
Tool-free DIN rail mounting and secure screw terminals enable fast setup. -
Schneider Quality Assurance
Built with precision and tested to meet international safety standards.
Applications:
-
Home and Office Circuits
Suitable for lighting, sockets, and general electrical outlets. -
Commercial Installations
Used in lighting panels, signage systems, and distribution boards. -
Automation Panels
Protects relays, control systems, and small actuators. -
Small Machinery and Equipment
Designed for circuits with moderate startup loads. -
Backup Power Systems
Ensures protection of standby equipment and low-load critical circuits
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | Acti9 |
|---|---|
| Product name | Acti9 C60H-DC |
| Product or component type | Miniature circuit-breaker |
| Device short name | C60H-DC |
| Device application | Distribution |
| Poles description | 1P |
| Number of protected poles | 1 |
| [In] rated current | 15 A at 25 °C |
| Network type | DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 10 kA Icu at 220 V DC conforming to EN 60947-2 10 kA Icu at 220 V DC conforming to IEC 60947-2 6 kA Icu at 250 V DC conforming to EN 60947-2 6 kA Icu at 250 V DC conforming to IEC 60947-2 20 kA Icu at 110 V DC conforming to EN 60947-2 20 kA Icu at 110 V DC conforming to IEC 60947-2 |
| Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2 |
| Network frequency | 50/60 Hz |
|---|---|
| [Ue] rated operational voltage | 250 V DC |
| [Ics] rated service breaking capacity | 15 kA 75 % conforming to EN 60947-2 - 110 V DC 15 kA 75 % conforming to IEC 60947-2 - 110 V DC 4.5 kA 75 % conforming to EN 60947-2 - 250 V DC 4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN 60947-2 - 220 V DC 7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC |
| [Ui] rated insulation voltage | 500 V DC conforming to IEC 60947-2 500 V DC conforming to EN 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| control type | Toggle |
| local signalling | ON/OFF indication |
| Mounting mode | Fixed |
| mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Top or bottom: standard |
| 9 mm pitches | 2 |
| Net weight | 0.128 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 3000 cycles L/R = 2 ms |
| Provision for padlocking | Padlockable |
| Locking options description | In position O |
| Tightening torque | Power circuit: 2.5 N.m top or bottom |
| earth-leakage protection | Without |
| Standards | EN 60947-2 IEC 60947-2 |
|---|---|
| Pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-2 |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.0 cm |
| Package 1 Width | 1.8 cm |
| Package 1 Length | 8.5 cm |
| Package 1 Weight | 112.0 g |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61511 | miniature circuit breaker – C60H – 1 pole – 16 A – C curve
Schneider A9N61508 | miniature circuit breaker – C60H – 1 pole – 10 A – C curve
Schneider A9N61504 | miniature circuit breaker – C60H – 1 pole – 4 A – C curve
-
0
Schneider A9N18479 | Miniature circuit-breaker, Acti9 C120H, 4P, 80 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
Schneider A9N18361 | Miniature circuit-breaker, Acti9 C120N, 2P, 80 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.