Schneider A9R14280 | Acti 9 iID – RCCB – 2P – 80A – 300mA – type AC
Schneider A9R14280 | Acti 9 iID – RCCB – 2P – 80A – 300mA – type AC
Description
Schneider A9R14280 | Acti 9 iID – RCCB – 2P – 80A – 300mA – type AC
. Technical Specifications A9R14280
-
Brand: Schneider Electric
-
Product Series: Acti9 iID
-
Model Number: A9R14280
-
Device Type: RCCB (Residual Current Circuit Breaker)
-
Number of Poles: 2 Poles
-
Rated Current (In): 80 Amperes
-
Rated Residual Operating Current (IΔn): 300 mA
-
Sensitivity Type: Type AC (detects pure AC sinusoidal residual currents)
-
Rated Voltage (Ue): 230/240V AC (single-phase)
-
Frequency: 50/60 Hz
-
Short-Circuit Withstand: 6 kA (when used with backup protection)
-
Mounting: DIN rail, 2 modules wide (36 mm)
-
Degree of Protection: IP20 (front panel), IP40 (in suitable enclosure)
-
Operating Temperature: -25°C to +60°C
-
Electrical Endurance: 10,000 operations (typical)
-
Standard Compliance: IEC/EN 61008-1
. Key Features
-
High Current Rating (80A): Suitable for main circuit protection in high-demand installations.
-
300mA Sensitivity: Provides protection against fire hazards caused by high earth leakage currents.
-
Type AC Detection: Suitable for typical domestic and commercial applications where only AC leakage is expected.
-
Dual-Pole Switching: Disconnects both phase and neutral for improved safety and isolation.
-
Compact Design: Takes only 2 DIN modules (36 mm), ideal for use in modern switchboards.
-
Mechanical Indicator: Clearly displays ON/OFF/trip status for fast fault identification.
-
Integrated Test Button: For regular function testing to ensure device integrity.
-
No Load Protection: Should be paired with a circuit breaker (MCB) for overcurrent protection.
-
Tool-Free Installation: Designed for fast and easy DIN rail mounting.
. Applications
The A9R14280 RCCB is primarily used for equipment and fire protection, rather than personal shock protection, due to its 300mA residual current rating. Suitable applications include:
-
Main Incoming Protection: In residential and commercial distribution panels.
-
Fire Prevention: Detects high leakage currents that may lead to overheating or fire, especially in aging electrical systems.
-
Large Residential Installations: Protection for entire houses or villas with high current requirements.
-
Commercial Buildings: Offices, retail spaces, or small industrial workshops requiring robust leakage protection.
-
Sub-Distribution Boards: For partial or segmented protection of large installations.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | Acti9 |
|---|---|
| Product name | Acti9 iID |
| Product or component type | Residual current circuit breaker (RCCB) |
| Device short name | iID |
| Poles description | 2P |
| Neutral position | Left |
| [In] rated current | 80 A |
| Network type | AC |
| Earth-leakage sensitivity | 300 mA |
| earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type AC |
| device location in system | Outgoer |
|---|---|
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 220...240 V AC 50/60 Hz |
| Residual current tripping technology | Voltage independent |
| Rated breaking and making capacity | Idm 1500 A Im 1500 A |
| Rated conditional short-circuit current | 10 kA |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Contact position indicator | Yes |
| control type | Toggle |
| Mounting mode | Clip-on |
| mounting support | DIN rail |
| 9 mm pitches | 4 |
| height | 91 mm |
| Width | 36 mm |
| Depth | 73.5 mm |
| Net weight | 0.21 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | AC-1: 10000 cycles |
| Locking options description | Padlocking device |
| Connections - terminals | Single terminal top or bottom 1…35 mm² rigid Single terminal top or bottom 1…25 mm² flexible Single terminal top or bottom 1…25 mm² flexible with ferrule |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 3.5 N.m top or bottom |
| Standards | EN/IEC 61008-1 |
|---|---|
| Product certifications | SNI |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Pollution degree | 3 |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
| Ambient air temperature for operation | -5…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.300 cm |
| Package 1 Width | 8.600 cm |
| Package 1 Length | 10.300 cm |
| Package 1 Weight | 200.000 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 54 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 11.710 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61515 | miniature circuit breaker – C60H – 1 pole – 32 A – C curve
-
0
Schneider A9N26946 | MX Shunt Trip MX plus 1 OF 220-415Vac dc
-
0
Schneider A9N18468 | Miniature circuit-breaker, Acti9 C120H, 3P, 80 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18447 | Miniature circuit-breaker, Acti9 C120H, 1P, 100 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18369 | Miniature circuit-breaker, Acti9 C120N, 3P, 125 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.