Schneider G25F3A250 | Circuit breaker, GoPact MCCB 250, 3 poles, 36kA at 415VAC, 250A rating, TMD trip unit, adjustable thermal protection
Description
Schneider G25F3A250 | Circuit breaker, GoPact MCCB 250, 3 poles, 36kA at 415VAC, 250A rating, TMD trip unit, adjustable thermal protection
Technical Specifications G25F3A250
-
Model: G25F3A250
-
Type: Molded Case Circuit Breaker (MCCB)
-
Series: GoPact
-
Number of Poles: 3 poles
-
Rated Current: 250 Amperes
-
Breaking Capacity: 36 kA at 415 VAC
-
Trip Unit: TMD (Thermal Magnetic Device)
-
Thermal Protection: Adjustable thermal protection settings
-
Voltage Rating: Suitable for 415 VAC systems
-
Standards Compliance: Meets international electrical protection and safety standards
-
Mounting: Suitable for panel and switchboard installation
Features
-
High breaking capacity: Withstands short circuit currents up to 36kA, ensuring strong protection against fault conditions.
-
Adjustable thermal protection: Allows customization of overload protection according to application requirements, improving system reliability.
-
Thermal magnetic trip unit: Provides dual protection by combining thermal overload and magnetic short-circuit trip functions.
-
Compact and robust design: Suitable for use in confined electrical panels without compromising performance.
-
Easy installation and maintenance: Designed for quick mounting and straightforward servicing.
-
Reliable switching: Offers consistent performance for switching and protection in industrial and commercial electrical systems.
-
Safety compliance: Adheres to key international standards ensuring user and equipment safety.
Applications
-
Industrial electrical distribution: Ideal for protecting circuits in factories, manufacturing plants, and heavy machinery.
-
Commercial buildings: Provides circuit protection in office buildings, shopping centers, and large facilities.
-
Power distribution panels: Used in switchboards and distribution boards to safeguard electrical circuits.
-
Renewable energy systems: Suitable for use in solar and wind power installations requiring reliable overcurrent protection.
-
Maintenance and retrofit projects: Can replace or upgrade existing circuit breakers for enhanced protection.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | GoPact MCCB |
|---|---|
| product or component type | Circuit breaker |
| Product name | GoPact MCCB 250 |
| Device application | Distribution |
| poles description | 3P |
| Protected poles description | 3D |
| [In] rated current | 250 A at 40 °C |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 36 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Performance level | F 36 kA 380/415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 440 V AC conforming to EN/IEC 60947-2 |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 36 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Mechanical durability | 25000 cycles |
| Electrical durability | 8000 cycles at 415 V In |
| Power dissipation per pole | 25 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | Screw terminals |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 250 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 12 x In |
| Width (W) | 105 mm |
| Height (H) | 165 mm |
| Depth (D) | 90 mm |
| net weight | 1.9 kg |
| Colour | Grey (RAL 7035) |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H |
|---|---|
| Overvoltage category | III |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…55 °C |
| ambient air temperature for storage | -35…85 °C |
| Operating altitude | 0...2000 m without derating 2000...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 18.3 cm |
| Package 1 Width | 14.1 cm |
| Package 1 Length | 20.4 cm |
| Package 1 Weight | 3100 g |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 6.641 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 24 |
| Package 3 Height | 105 cm |
| Package 3 Width | 60 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 88.192 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61508 | miniature circuit breaker – C60H – 1 pole – 10 A – C curve
Schneider A9N61502 | miniature circuit breaker – C60H – 1 pole – 2 A – C curve
-
0
Schneider A9N26946 | MX Shunt Trip MX plus 1 OF 220-415Vac dc
-
0
Schneider A9N18569 | Vigi C120 – earth leakage add-on block – 4P – 30 mA – class AC
-
0
Schneider A9N18357 | Miniature circuit-breaker, Acti9 C120N, 1P, 80 A, C curve, 10000 A (IEC 60898-1), 10 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.