Description

Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors

1. Technical Specifications C11N6TM025B

  • Product Reference: C11N6TM025B

  • Series: ComPacT NSXm N

  • Product Type: Molded Case Circuit Breaker (MCCB)

  • Poles: 4P (3d configuration)

    • 3 protected phases + 1 dedicated neutral (not protected)

  • Rated Current (In): 25 A

  • Trip Unit Type:

    • TMD (Thermal Magnetic Device)

    • Fixed long-time (thermal) and short-circuit (magnetic) trip thresholds

  • Breaking Capacity (Icu):

    • 50 kA at 415 V AC (according to IEC 60947-2)

  • Rated Operating Voltage (Ue):

    • Up to 415 V AC (50/60 Hz)

  • Rated Insulation Voltage (Ui): 800 V AC

  • Rated Impulse Withstand Voltage (Uimp): 8 kV

  • Utilization Category: A (non-selective type)

  • Mounting Mode: Fixed

  • Terminal Type:

    • Compression lugs (for cable termination)

    • Busbar connectors (for direct panel integration with busbars)

  • Conformity:

    • IEC 60947-2

    • CE, RoHS, EAC compliant

  • Environmental Ratings:

    • Operating temperature: –25°C to +70°C

    • Degree of protection: IP40 (front), IP20 (terminals)

  • Mechanical Durability: > 10,000 operations

  • Electrical Durability: ~1,500 operations

2. Key Features

  • High breaking capacity (50 kA) for enhanced protection in demanding networks

  • Thermal-magnetic trip unit:

    • Thermal protection for overloads

    • Magnetic protection for short circuits

    • Fixed protection settings – simple and reliable

  • Compact and robust NSXm frame design for space-saving in panels

  • 4-pole configuration (3d) allows reliable 3-phase + neutral power distribution

  • Busbar compatibility ensures fast and safe installation in distribution panels

  • Compression terminals provide reliable cable connections without torque loss

  • Accessory ready: compatible with OF/SD auxiliary contacts, shunt trip (MX), under-voltage release (MN), etc.

  • Suitable for DIN rail or backplate mounting

  • Easy front-face access for installation and maintenance

3. Typical Applications

  • Low-voltage distribution boards in commercial and industrial environments

  • Final protection for 3-phase + neutral loads such as:

    • Lighting systems

    • HVAC units

    • Distribution sub-panels

    • Pumps and small motors

  • Ideal for:

    • Switchboards and control panels

    • Machine installations

    • Renewable energy combiner boxes

    • Infrastructure and utilities

  • Frequently used in:

    • Manufacturing facilities

    • Residential complexes

    • Data centers and IT environments

    • Office buildings

Additional information

brands

Schneider Electric

Specifications

Main
Range ComPacT new generation
Product name ComPacT NSXm new generation
Range of product ComPacT NSXm new generation
Device short name NSXm 63N
product or component type Circuit breaker
Device application Distribution
poles description 4P
Protected poles description 3D
Neutral position Left
[In] rated current 25A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole 2.4 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection terminals Compression lug/busbar
Connection pitch 35 Mm with spreaders 27 mm without spreaders
9 mm pitches 12 module
Trip unit rating 25 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
Neutral protection settings No protection (3D)
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 600 A
Earth-leakage protection Without
Number of slots for electrical auxiliaries 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX
Local signalling Flag (green) for presence of auxiliary contacts
Width (W) 108 mm
Height (H) 137 mm
Depth (D) 80 mm
net weight 1.42 kg
Colour Grey (RAL 7016)
Environment
Standards EN/IEC 60947
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 2000 m without derating 5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 12.500 cm
Package 1 Width 11.800 cm
Package 1 Length 21.200 cm
Package 1 Weight 1.342 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!