Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors
Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors
Description
Schneider C11N6TM025B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 25A rating TMD trip unit, compression lugs and busbar connectors
1. Technical Specifications C11N6TM025B
-
Product Reference: C11N6TM025B
-
Series: ComPacT NSXm N
-
Product Type: Molded Case Circuit Breaker (MCCB)
-
Poles: 4P (3d configuration)
-
3 protected phases + 1 dedicated neutral (not protected)
-
-
Rated Current (In): 25 A
-
Trip Unit Type:
-
TMD (Thermal Magnetic Device)
-
Fixed long-time (thermal) and short-circuit (magnetic) trip thresholds
-
-
Breaking Capacity (Icu):
-
50 kA at 415 V AC (according to IEC 60947-2)
-
-
Rated Operating Voltage (Ue):
-
Up to 415 V AC (50/60 Hz)
-
-
Rated Insulation Voltage (Ui): 800 V AC
-
Rated Impulse Withstand Voltage (Uimp): 8 kV
-
Utilization Category: A (non-selective type)
-
Mounting Mode: Fixed
-
Terminal Type:
-
Compression lugs (for cable termination)
-
Busbar connectors (for direct panel integration with busbars)
-
-
Conformity:
-
IEC 60947-2
-
CE, RoHS, EAC compliant
-
-
Environmental Ratings:
-
Operating temperature: –25°C to +70°C
-
Degree of protection: IP40 (front), IP20 (terminals)
-
-
Mechanical Durability: > 10,000 operations
-
Electrical Durability: ~1,500 operations
2. Key Features
-
High breaking capacity (50 kA) for enhanced protection in demanding networks
-
Thermal-magnetic trip unit:
-
Thermal protection for overloads
-
Magnetic protection for short circuits
-
Fixed protection settings – simple and reliable
-
-
Compact and robust NSXm frame design for space-saving in panels
-
4-pole configuration (3d) allows reliable 3-phase + neutral power distribution
-
Busbar compatibility ensures fast and safe installation in distribution panels
-
Compression terminals provide reliable cable connections without torque loss
-
Accessory ready: compatible with OF/SD auxiliary contacts, shunt trip (MX), under-voltage release (MN), etc.
-
Suitable for DIN rail or backplate mounting
-
Easy front-face access for installation and maintenance
3. Typical Applications
-
Low-voltage distribution boards in commercial and industrial environments
-
Final protection for 3-phase + neutral loads such as:
-
Lighting systems
-
HVAC units
-
Distribution sub-panels
-
Pumps and small motors
-
-
Ideal for:
-
Switchboards and control panels
-
Machine installations
-
Renewable energy combiner boxes
-
Infrastructure and utilities
-
-
Frequently used in:
-
Manufacturing facilities
-
Residential complexes
-
Data centers and IT environments
-
Office buildings
-
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSXm new generation |
| Range of product | ComPacT NSXm new generation |
| Device short name | NSXm 63N |
| product or component type | Circuit breaker |
| Device application | Distribution |
| poles description | 4P |
| Protected poles description | 3D |
| Neutral position | Left |
| [In] rated current | 25A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | N 50 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 2.4 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | Compression lug/busbar |
| Connection pitch | 35 Mm with spreaders 27 mm without spreaders |
| 9 mm pitches | 12 module |
| Trip unit rating | 25 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| Neutral protection settings | No protection (3D) |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 600 A |
| Earth-leakage protection | Without |
| Number of slots for electrical auxiliaries | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| Local signalling | Flag (green) for presence of auxiliary contacts |
| Width (W) | 108 mm |
| Height (H) | 137 mm |
| Depth (D) | 80 mm |
| net weight | 1.42 kg |
| Colour | Grey (RAL 7016) |
| Standards | EN/IEC 60947 |
|---|---|
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 2000 m without derating 5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 12.500 cm |
| Package 1 Width | 11.800 cm |
| Package 1 Length | 21.200 cm |
| Package 1 Weight | 1.342 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider C11N3TM080L | Circuit breaker, ComPacT NSXm 160N, 50kA/415VAC, 3 poles, TMD trip unit 80A, EverLink lugs
Schneider C12N3TM160B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 3 Poles 3d, 160A rating TMD trip unit, compression lugs and busbar connectors
Schneider C12E3TM125B | Circuit breaker, ComPacT NSXm 160E, 16kA/415VAC, 3 poles, TMD trip unit 125A, lugs/busbars
Schneider C12B3TM160B | Circuit breaker, ComPacT NSXm 160B, 25kA/415VAC, 3 poles, TMD trip unit 160A, lugs/busbars
Schneider C11N6TM050B | Circuit breaker ComPacT NSXm N (50kA at 415VAC), 4 Poles 3d, 50A rating TMD trip unit, compression lugs and busbar connectors
-
0
Reviews
There are no reviews yet.