Schneider C10F6TM025 | Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 25A
Description
Schneider C10F6TM025 | Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 25A
Schneider C10F6TM025 Description
Introduction
Schneider Electric is a global leader in energy management and automation, providing innovative solutions to enhance efficiency and safety. The Schneider C10F6TM025 is a high-quality circuit breaker designed to protect electrical circuits from overloads and short circuits, ensuring safety and reliability in various applications.
Overview of the Schneider C10F6TM025
The Schneider C10F6TM025 is a miniature circuit breaker (MCB) that automatically disconnects electrical circuits during fault conditions, such as overloads or short circuits, to prevent damage and ensure safety.
Basic Description
- Product Type: Miniature Circuit Breaker (MCB)
- Model Number: C10F6TM025
- Pole: 1P (single pole)
- Current Rating: 25A
Key Features
- High Breaking Capacity: Capable of handling significant load variations, making it suitable for a wide range of applications.
- Compact Design: Optimized for space-saving installation in standard electrical panels.
- Durable Construction: Manufactured with high-quality materials to ensure long-lasting performance.
- Easy Installation: Designed for user-friendly mounting and connection.
Technical Specifications
Electrical Specifications
- Rated Current: 25A
- Number of Poles: 1
- Breaking Capacity: High breaking capacity to effectively protect against overloads and short circuits.
- Operating Voltage: Suitable for both low and medium voltage applications.
Mechanical Specifications
- Dimensions: Standard size for easy integration into existing systems.
- Weight: Lightweight yet robust construction for straightforward handling and installation.
- Mounting Type: Can be mounted on DIN rails or surface-mounted, providing flexibility in installation.
Design and Build Quality
Schneider Electric ensures all its products, including the C10F6TM025, adhere to high standards of safety and durability.
Materials Used
- Housing: Fire-resistant, high-strength plastic to ensure safety and longevity.
- Internal Components: High-quality metals like copper and silver alloy for excellent conductivity and durability.
- Terminals: Corrosion-resistant terminals to maintain reliable connections over time.
Construction Details
- Robust Construction: Built to withstand mechanical stress and challenging operating conditions.
- High-Precision Manufacturing: Ensures consistent performance and reliability.
Installation Guidelines
Proper installation of the Schneider C10F6TM025 is crucial to ensure optimal performance and safety.
Pre-Installation Checklist
- Verify that the main power supply is turned off.
- Ensure the circuit breaker is compatible with the electrical panel and application.
- Gather all necessary tools and safety equipment.
Step-by-Step Installation Process
- Turn Off Power: Ensure the main power supply is completely shut off.
- Mount the Breaker: Secure the C10F6TM025 onto the DIN rail or surface mount as required.
- Connect Wiring: Attach the input and output wires to the appropriate terminals, ensuring secure connections.
- Test the Circuit: Restore power and test the breaker to ensure it functions correctly.
- Complete Installation: Organize and secure any loose wires and close the panel.
Built-In Safety Mechanisms
- Overload Protection: Automatically trips to prevent overheating and potential fire hazards.
- Short Circuit Protection: Quickly isolates faults to protect the electrical system.
- Fire-Resistant Housing: Adds an extra layer of protection against electrical fires.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSX new generation |
| Device short name | NSX100F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 4P |
| Protected poles description | 3D |
| Neutral position | Left |
| [In] rated current | 25 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | F 36 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 50000 cycles |
| Electrical durability | 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In |
| Power dissipation per pole | 4.01 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 25 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
| Neutral protection settings | No protection (3D) |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 300 A |
| Earth-leakage protection | Without |
| Number of slots for electrical auxiliaries | 5 slot(s) |
| Width (W) | 140 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Net weight | 2.4 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Overvoltage category | Class II |
| Electrical shock protection class | Class II |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14 cm |
| Package 1 Width | 15 cm |
| Package 1 Length | 19 cm |
| Package 1 Weight | 2.79 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 16.74 kg |