Description

Schneider A9F75325 | Miniature circuit breaker (MCB), Acti9 iC60N, 3P, 25A, D curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)

Schneider A9F75325 Description

The Schneider A9F75325 is a part of the Acti9 series, which is designed to ensure the protection of electrical circuits in various applications. This series is known for its high reliability and advanced safety features, making it suitable for both residential and commercial environments. Below is a detailed description of the Schneider A9F75325:

Schneider A9F75325: Technical Specifications and Features

Technical Specifications:

  • Product Range: Acti9
  • Product Type: Miniature Circuit Breaker (MCB)
  • Number of Poles: 3
  • Rated Current: 25 A
  • Tripping Curve: C-curve
  • Breaking Capacity: 10 kA at 230/400V AC
  • Rated Voltage: 230/400V AC
  • Frequency: 50/60 Hz
  • Standards: IEC/EN 60898-1

Key Features:

  1. Enhanced Safety: The A9F75325 is equipped with VisiTrip indicators which allow for quick identification of the tripped circuit, ensuring faster maintenance and reduced downtime.
  2. High Performance: With a breaking capacity of 10 kA, this MCB provides reliable protection against short circuits and overloads.
  3. Ease of Installation: The Acti9 series is designed with a modular approach, making the installation and upgrading process straightforward. The MCB can be easily mounted on DIN rails.
  4. Durability: The A9F75325 is built to last with high-quality materials that ensure long-term reliability and performance.
  5. Compatibility: It is compatible with a wide range of accessories from the Acti9 series, including auxiliary contacts and remote control units, enhancing its functionality.
  6. Environmentally Friendly: Schneider Electric is committed to sustainable practices, and the A9F75325 is designed with eco-friendly materials and processes.

The Schneider A9F75325 is a miniature circuit breaker (MCB) from the Schneider Electric Acti 9 series. Here’s a detailed description of its features and specifications:

Type: 3-pole, 3-module device.

  1. Current Rating: Rated for 25 amps.
  2. Voltage: Suitable for voltages up to 415V AC.
  3. Breaking Capacity: Provides a breaking capacity of 10 kA according to IEC/EN 60898-1 standard.
  4. Trip Curve: C-curve characteristic, meaning it trips in response to overload currents between 5 to 10 times the rated current.

Applications:

  • Ideal for protecting three-phase electrical circuits in residential, commercial, and industrial installations.
  • Commonly used in distribution boards and consumer units where three-pole protection is required.
    • Residential Buildings: Protects electrical circuits in homes from overloads and short circuits.
    • Commercial Buildings: Ensures the safety and reliability of electrical systems in offices, shops, and other commercial spaces.
    • Industrial Settings: Suitable for protecting circuits in small industrial applications where reliable circuit protection is crucial.

    Benefits of Using Schneider A9F75325

    1. Improved Operational Safety: The clear indication of trip status and the robust design minimize the risk of electrical hazards.
    2. Cost-Effective Maintenance: Easy identification of faults and straightforward replacement reduce maintenance costs.
    3. Versatility: Suitable for a wide range of applications, providing flexibility in use.
    4. Long-Term Reliability: High-quality construction ensures longevity, reducing the need for frequent replacements.

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
product or component type Miniature circuit-breaker
Device short name IC60N
poles description 3P
Number of protected poles 3
[In] rated current 25 A
Network type AC DC
Trip unit technology Thermal-magnetic
Curve code D
Breaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2
Standards IEC 60898-1 EN 60898-1 IEC 60947-2 EN 60947-2
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 12 x In +/- 20 %
[Ics] rated service breaking capacity 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 10 kA 100 % conforming to IEC 60947-2 - 125...180 V DC 10 kA 100 % conforming to EN 60947-2 - 125...180 V DC
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
local signalling Trip indicator
mounting mode Fixed
mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 6
Height 85 mm
Width 54 mm
Depth 78.5 mm
net weight 0.375 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 2 N.m top or bottom
Earth-leakage protection Separate block
Environment
IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0...2000 m
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 5.5 cm
Package 1 Width 7.3 cm
Package 1 Length 9.4 cm
Package 1 Weight 346.0 g
Unit Type of Package 2 BB1
Number of Units in Package 2 4
Package 2 Height 8.0 cm
Package 2 Width 9.5 cm
Package 2 Length 22.5 cm
Package 2 Weight 1.45 kg
Unit Type of Package 3 S03
Number of Units in Package 3 44
Package 3 Height 30.0 cm
Package 3 Width 30.0 cm
Package 3 Length 40.0 cm
Package 3 Weight 16.444 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider A9F75325 | Miniature circuit breaker (MCB), Acti9 iC60N, 3P, 25A, D curve, 6000A (IEC/EN 60898-1), 10kA (IEC/EN 60947-2)”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare