Description

Schneider A9F87440 | Miniature Circuit Breaker (MCB), Acti9, 1P, 40A, D Curve

schneider A9F87440 description

Introduction

Circuit breakers are essential components in electrical systems, providing protection against overcurrents and short circuits. This article will focus on the Schneider A9F87440, a miniature circuit breaker (MCB) known for its advanced features and reliable performance.

Schneider A9F87440

The Schneider A9F87440 is a 1-pole, 40A MCB from the Acti9 series, featuring a D curve. The D curve is designed for circuits with high inrush currents, such as those used in inductive loads like motors and transformers. This MCB is versatile, making it suitable for both residential and commercial applications where protection against high inrush currents is crucial.

How Circuit Breakers Work

Circuit breakers protect electrical systems by interrupting the power supply when they detect an overcurrent or short circuit. They continuously monitor the current flow and trip to stop the electricity when anomalies are detected, preventing potential damage to the electrical circuit and connected devices.

Types of Circuit Breakers

There are several types of circuit breakers, including Miniature Circuit Breakers (MCBs), Residual Current Circuit Breakers (RCCBs), and more. Each type serves a specific purpose, from protecting against overloads and short circuits to detecting residual currents.

Importance in Safety

Circuit breakers play a critical role in electrical safety by preventing overcurrents and short circuits, which can lead to fires, equipment damage, and electric shocks. Properly functioning circuit breakers are essential for maintaining the safety and reliability of electrical systems.

Installation Process

To install the Schneider A9F87440 circuit breaker, follow these steps:

  1. Turn off the main power: Ensure the main power supply is off to avoid any accidents.
  2. Identify the circuit: Determine the specific circuit where the MCB will be installed.
  3. Connect the MCB: Securely attach the MCB to the circuit, ensuring all connections are tight and correct.
  4. Test the installation: After installation, test the MCB to ensure it trips and resets properly.

Maintenance Tips

Regular maintenance is key to keeping your circuit breaker in optimal condition:

  1. Periodic testing: Regularly test the MCB to ensure it functions correctly.
  2. Inspect for damage: Check the MCB for any physical damage or signs of wear.
  3. Replace faulty units: If the MCB shows any signs of malfunction, replace it immediately to ensure continued safety.

Common FAQs

  1. What is the difference between an MCB and an RCCB?
    • An MCB protects against overloads and short circuits, while an RCCB detects residual currents to prevent electric shocks.
  2. Can MCBs be used in residential applications?
    • Yes, MCBs like the Schneider A9F87440 are suitable for both residential and commercial applications.
  3. What does the ‘D curve’ mean in an MCB?
    • The ‘D curve’ indicates the MCB’s tripping characteristics, suitable for circuits with high inrush currents.
  4. How often should an MCB be tested?
    • It is recommended to test MCBs at least once a year to ensure they are functioning properly.
  5. Are MCBs affected by environmental factors?
    • Yes, extreme temperatures and humidity can impact MCB performance, so consider the installation environment carefully.

Conclusion

The Schneider A9F87440 MCB is a robust and versatile solution for protecting electrical circuits, especially those with high inrush currents. Proper installation and regular maintenance ensure its effectiveness in safeguarding electrical systems.

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
Product or component type Miniature circuit-breaker
Device short name iC60H
poles description 4P
Number of protected poles 4
[In] rated current 40 A
Network type AC DC
Trip unit technology Thermal-magnetic
Curve code C
Breaking capacity 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 42 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2
Standards IEC 60898-1 EN 60898-1 EN 60947-2 IEC 60947-2
Quality labels NF
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 8 x In +/- 20 %
[Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 - 180...250 V DC 15 kA 100 % conforming to EN 60947-2 - 180...250 V DC
Limitation class 3 conforming to EN 60898-1 3 conforming to IEC 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
local signalling Trip indicator
mounting mode Fixed
Mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 8
Height 85 mm
Width 72 mm
Depth 78.5 mm
Net weight 0.5 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals Single terminal (top or bottom) 1…35 mm² rigid Single terminal (top or bottom) 1…25 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 3.5 N.m top or bottom
Earth-leakage protection Separate block
Environment
IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0...2000 m
Ambient air temperature for operation -35…70 °C
ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.3 cm
Package 1 Width 7.1 cm
Package 1 Length 8.5 cm
Package 1 Weight 479.0 g
Unit Type of Package 2 BB1
Number of Units in Package 2 3
Package 2 Height 8.2 cm
Package 2 Width 9.8 cm
Package 2 Length 22.4 cm
Package 2 Weight 1.499 kg
Unit Type of Package 3 S03
Number of Units in Package 3 33
Package 3 Height 30.0 cm
Package 3 Width 30.0 cm
Package 3 Length 40.0 cm
Package 3 Weight 16.977 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : A9F87440

Main Document

Data Sheet : A9F87440

Reviews (0)

Be the first to review “Schneider A9F87440 | Miniature Circuit Breaker (MCB), Acti9, 1P, 40A, D Curve”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare