Description

Schneider C10F3TM063 | Circuit breaker, Compact NSX100F, 36kA/415VAC, 3 poles, TMD trip unit 63A

</div>

Schneider C10F3TM063 Description

This ComPacT NSX100F is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity.

It is an optimal choice for all standard and specific applications.

The breaking capacity (Icu) is 36kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz.3.

This product embeds a 63A rating thermal-magnetic trip unit (TMD).

TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories.

It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications.

ComPacT NSX100F is part of Schneider Electric EcoStruxure Power architecture.

Introduction

Schneider Electric is a leading name in energy management and automation, renowned for delivering reliable and high-quality products. Circuit breakers are fundamental components in electrical systems, safeguarding against overloads and short circuits. One of Schneider Electric’s prominent products is the C10F3TM063 circuit breaker, designed to ensure optimal protection and efficiency. This article delves into its features, technical specifications, and practical applications, offering a comprehensive overview.

Overview of the Schneider C10F3TM063

The Schneider C10F3TM063 is a miniature circuit breaker (MCB) specifically engineered to protect electrical circuits from overloads and short circuits. It plays a crucial role in maintaining the safety and functionality of various electrical setups.

Basic Description

The Schneider C10F3TM063 is a single-pole, 63A circuit breaker with an F curve characteristic. This means it trips between 3 to 5 times the rated current, making it suitable for circuits with moderate inrush currents.

Technical Specifications

Electrical Specifications

  • Rated Voltage: 230/400V AC
  • Rated Current: 63A
  • Breaking Capacity: 10kA according to IEC/EN 60898-1
  • Tripping Curve: Type F (3-5 times the rated current)

Mechanical Specifications

  • Dimensions: 81mm x 18mm x 70mm
  • Weight: 0.160 kg
  • Mounting: DIN rail

Design and Build Quality

The Schneider C10F3TM063 is meticulously designed using high-quality materials to ensure durability and reliability.

Materials Used

  • Housing: Made from fire-resistant plastic for enhanced safety.
  • Internal Components: High-grade copper and silver alloy for optimal conductivity.
  • Terminals: Constructed from corrosion-resistant metals to ensure longevity.

Construction Details

Schneider Electric adheres to strict quality control measures, ensuring each circuit breaker meets high performance and safety standards. The C10F3TM063 is designed to withstand regular use in demanding environments, providing reliable protection over the long term.

Installation Guidelines

Proper installation is vital for the effective performance and safety of the Schneider C10F3TM063.

Pre-Installation Checklist

  • Confirm that the main power supply is turned off.
  • Ensure compatibility with the electrical panel.
  • Gather necessary tools and protective equipment.

Applications and Usage

The Schneider C10F3TM063 is versatile and suitable for various applications.

Industrial Applications

Ideal for protecting motor circuits and transformers in industrial settings.

Commercial Applications

Provides reliable protection for lighting, HVAC systems, and other commercial electrical loads.

Residential Applications

Perfect for household electrical circuits, safeguarding appliances, and preventing electrical hazards.

Compatibility and Integration

The Schneider C10F3TM063 is designed to integrate seamlessly with various electrical systems.

Compatible Systems and Devices

  • Electrical Panels: Compatible with standard residential, commercial, and industrial electrical panels.
  • Automation Systems: Can be integrated with building automation systems for enhanced control and monitoring.
  • Renewable Energy Systems: Suitable for use in small-scale solar and wind power installations.

Integration Tips

  • Ensure all connections are secure to avoid potential faults.
  • Regularly inspect and maintain the circuit breaker to ensure ongoing compatibility and performance.

Performance and Efficiency

The Schneider C10F3TM063 is engineered for high performance and energy efficiency.

Performance Metrics

  • Response Time: Quick tripping response to overloads and short circuits.
  • Reliability: Consistent protection with minimal downtime.

Energy Efficiency Considerations

The design minimizes energy loss, contributing to the overall efficiency of the electrical system.

Safety Features

Schneider Electric prioritizes safety, and the C10F3TM063 includes several built-in safety features.

Compliance with Safety Standards

The C10F3TM063 complies with international safety standards, including IEC/EN 60898-1, ensuring it meets stringent safety requirements.

Built-In Safety Mechanisms

  • Overload Protection: Automatically trips to prevent overheating and potential fires.
  • Short Circuit Protection: Quickly isolates faults to prevent damage to the electrical system.

Additional information

brands

Schneider Electric

Specifications

Main
Range ComPacT new generation
Product name ComPacT NSX new generation
Device short name NSX100F
product or component type Circuit breaker
Device application Distribution
poles description 3P
Protected poles description 3D
[In] rated current 63 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level F 36 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 12 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 50000 cycles
Electrical durability 50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Power dissipation per pole 8.61 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection pitch 35 mm
Protection type L : for overload protection (thermal) I : for short-circuit protection (magnetic)
Trip unit rating 63 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
[tr] long-time protection delay adjustment range 120…400 s at 1.5 x In 15 s at 6 x Ir
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 500 A
Earth-leakage protection Without
Number of slots for electrical auxiliaries 5 slot(s)
Width (W) 105 mm
Height (H) 161 mm
Depth (D) 86 mm
net weight 2.05 kg
Environment
Standards EN/IEC 60947
Product certifications CCC EAC Marine
Overvoltage category Class II
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 13.7 cm
Package 1 Width 11.2 cm
Package 1 Length 19.0 cm
Package 1 Weight 1.778 kg
Unit Type of Package 2 S03
Number of Units in Package 2 7
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 12.848 kg

Main Document

Main Document

Data Sheet : C10F3TM063

Main Document

Data Sheet : C10F3TM063

Reviews (0)

Be the first to review “Schneider C10F3TM063 | Circuit breaker, ComPacT NSX100F, 36kA/415VAC, 3 poles, TMD trip unit 63A”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare