Description

Schneider C11E6TM016B | Circuit breaker, ComPacT NSXm 63E, 16kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 16A,

Schneider C11E6TM016B Description:

It is a ComPacT NSXm molded case circuit breaker, 16A, 16kA at 415VAC, for all LV standard applications.
It offers new features like Everlink technology, DIN rail and plate mounting capability.
It embeds new spring type auxiliaries externally visible.
ComPacT NSXm is one of the smallest MCCB on the market, 108mm (W) x 137mm (H) x 80mm (D).
This is a 4 poles version with an embedded thermal-magnetic trip unit.
It ensures compliance with international standards (IEC 60947/CCC/EAC) and marine specifications.

Product Overview: The Schneider C11E6TM016B surge protector is likely designed to protect electrical systems and equipment from transient overvoltages caused by lightning strikes, electrical switching, and other voltage surges. It provides essential protection to ensure the safety and longevity of connected devices.

Key Features (Typical for Schneider Surge Protectors):

  1. Type 2 Surge Protection: Typically installed at distribution boards to protect against indirect lightning strikes and switching surges.
  2. Moderate Surge Current Capacity: Offers a reliable discharge capacity to divert excessive voltage away from sensitive equipment, maintaining operational integrity.
  3. Visual Indication: Often equipped with status LEDs for clear indication of operational status and potential fault conditions.
  4. Compact and Modular Design: Designed for easy installation in various electrical panels and enclosures, providing flexibility in deployment and maintenance.
  5. Compliance: Meets international standards and certifications for surge protection devices, ensuring reliability and safety in operation.

Applications:

  • Commercial: Safeguards sensitive electronic devices in offices, retail spaces, and other commercial buildings.
  • Residential: Protects household appliances and electronics from electrical surges, ensuring uninterrupted operation.

Installation: Typically installed at main distribution boards or sub-distribution boards to protect downstream equipment from transient overvoltages.

Technical Specifications (Typical):

  • Nominal Voltage: 230V AC
  • Maximum Continuous Operating Voltage: 275V AC
  • Nominal Discharge Current (In): Typically around 10 kA
  • Protection Modes: L-N, L-PE, N-PE

Manufacturer: Schneider Electric, a leading global provider of energy management and automation solutions.

Additional information

brands

Schneider Electric

Specifications

Main
Range ComPacT new generation
Product name ComPacT NSXm new generation
Range of product ComPacT NSXm new generation
Device short name NSXm 63E
product or component type Circuit breaker
Device application Distribution
poles description 4P
Protected poles description 3D
Neutral position Left
[In] rated current 16 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit breaking capacity 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Performance level E 16 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ics] rated service short-circuit breaking capacity 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Power dissipation per pole 2.4 W
mounting support Backplate
Mounting position Horizontal and vertical Flat on the back
Upside connection Front
downside connection Front
Connection terminals Compression lug/busbar
Connection pitch 35 mm with spreaders 27 mm without spreaders
9 mm pitches 12 module
Trip unit rating 16 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable
[Ir] long-time protection pick-up adjustment range 0.7...1 x In
Long-time protection delay adjustment type tr Fixed
Neutral protection settings No protection (3D)
Instantaneous protection pick-up adjustment type Ii Fixed
[Ii] instantaneous protection pick-up adjustment range 500 A
Earth-leakage protection Without
Number of slots for electrical auxiliaries 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX
Local signalling Flag (green) for presence of auxiliary contacts
Width (W) 108 mm
Height (H) 137 mm
Depth (D) 80 mm
net weight 1.42 kg
Colour Grey (RAL 7016)
Environment
Standards EN/IEC 60947
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 2000 m without derating 5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 12 cm
Package 1 Width 13 cm
Package 1 Length 22 cm
Package 1 Weight 1.6 kg
Unit Type of Package 2 S03
Number of Units in Package 2 6
Package 2 Height 30 cm
Package 2 Width 30 cm
Package 2 Length 40 cm
Package 2 Weight 10.19 kg
Unit Type of Package 3 P12
Number of Units in Package 3 144
Package 3 Height 150 cm
Package 3 Width 80 cm
Package 3 Length 120 cm
Package 3 Weight 254.49 kg

Main Document

Main Document

Data Sheet : Download

Main Document