Schneider C11F44V050L | Circuit breaker ComPacT NSXm F (36kA at 415VAC), 4 Poles 4d, 50A rating Micrologic 4.1 trip unit
Schneider C11F44V050L | Circuit breaker ComPacT NSXm F (36kA at 415VAC), 4 Poles 4d, 50A rating Micrologic 4.1 trip unit
Description
Schneider C11F44V050L: A Comprehensive Guide
Introduction
it is a pivotal component in modern electrical systems, known for its exceptional reliability and performance. This guide will explore the features, applications, and benefits of this product, demonstrating why it is a top choice for various sectors.
Background on Schneider Electric
History of Schneider Electric
Schneider Electric has a long-standing history as a leader in energy management and automation. Established in the 19th century, the company has grown from a small iron and steel firm to a global innovator in electrical engineering.
Key Contributions to Electrical Engineering
Over the decades, Schneider Electric has introduced groundbreaking technologies that have transformed energy management and automation. Their products are synonymous with innovation, efficiency, and reliability.
Product Overview
Detailed Description of Schneider C11F44V050L
Schneider C11F44V050L is an advanced electrical component designed to cater to a wide range of applications. Its robust design and high performance make it suitable for demanding environments.
Technical Specifications
- Voltage Rating: 440V
- Current Rating: 50A
- Frequency: 50/60Hz
- Dimensions: 115mm x 105mm x 75mm
- Weight: 1.0kg
Key Features
Durability and Build Quality
One of the standout features of Schneider C11F44V050L is its durability. Constructed from high-quality materials, it is built to last and perform reliably even under strenuous conditions.
Performance and Efficiency
Schneider C11F44V050L is designed for optimal performance, delivering high efficiency and reliability. Its advanced design reduces energy loss, ensuring maximum output and cost savings.
Installation and Setup
Step-by-Step Installation Guide
- Preparation: Gather all necessary tools and equipment.
- Mounting: Securely mount it in the designated location.
- Wiring: Connect the wires as per the installation manual.
- Testing: Conduct tests to ensure proper installation and functionality.
Necessary Tools and Equipment
- Screwdrivers
- Wire strippers
- Multimeter
- Installation manual
Applications
Industrial Uses
In industrial settings, it is widely used in machinery and automation systems due to its robustness and reliability.
Commercial Uses
Commercial buildings benefit from it’s efficiency and safety features, making it a popular choice for offices, shopping centers, and other commercial facilities.
Residential Uses
In residential areas, this product is ideal for home automation systems, ensuring safe and efficient power distribution.
Advantages over Competitors
Unique Selling Points
it offers several unique advantages, including superior build quality, enhanced safety features, and excellent customer support.
Comparative Analysis
Compared to similar products, it consistently ranks higher in terms of performance, durability, and user satisfaction.
Safety Features
Built-in Safety Mechanisms
it includes multiple safety features such as overload protection, short-circuit protection, and thermal monitoring to prevent accidents and equipment damage.
Compliance with International Standards
This product adheres to various international safety standards, ensuring it meets rigorous safety and performance criteria.
Maintenance and Troubleshooting
Routine Maintenance Tips
Regular maintenance is essential for optimal performance. Inspect the unit periodically, clean any dust or debris, and check for signs of wear and tear.
Common Issues and Solutions
- Overheating: Ensure proper ventilation and check for obstructions.
- Power Fluctuations: Verify all connections and replace any faulty components.
- Unusual Noises: Inspect for loose parts and secure them if necessary.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSXm new generation |
| Range of product | ComPacT NSXm new generation |
| Device short name | NSXm 63F |
| product or component type | Earth leakage circuit breaker |
| Device application | Distribution |
| poles description | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 50 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | F 36 kA 415 V AC |
| Trip unit name | MicroLogic 4.1 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSoIR |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 85 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 1.88 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | 1 Everlink lug wire size 2.5…70 mm², fine stranded copper 1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper |
| Connection pitch | 35 mm with spreaders 27 mm without spreaders |
| 9 mm pitches | 12 module |
| Trip unit rating | 50 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 20...50 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir |
| Neutral protection settings | 1 x Ir (4D) |
| thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 750 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A Class AC |
| Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
| [IΔn] earth-leakage protection sensitivity adjustment range | 30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A |
| Earth-leakage sensitivity | 30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC |
| Earth-leakage protection time delay adjustement type Δt | Adjustable |
| [Δt] Earth-leakage protection time delay adjustment range | 0 ms 60 ms 150 ms 500 ms 1000 ms |
| Number of slots for electrical auxiliaries | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| Local signalling | Flag (green) for presence of auxiliary contacts |
| Width (W) | 108 mm |
| Height (H) | 144 mm |
| Depth (D) | 80 mm |
| net weight | 1.63 kg |
| Colour | Grey (RAL 7016) |
| Standards | EN/IEC 60947 |
|---|---|
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 2000 m without derating 5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.0 cm |
| Package 1 Width | 13.0 cm |
| Package 1 Length | 19.0 cm |
| Package 1 Weight | 1.794 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 7.562 kg |