Schneider C25F6TM200 | Circuit breaker, ComPacT NSX250F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 200A
Schneider Electric green signature style for the entire ComPacT range
Description
Schneider C25F6TM200 | Circuit breaker, ComPacT NSX250F, 36kA/415VAC, 4 poles 3D (neutral not protected), TMD trip unit 200A

Description
The Schneider Electric C25F6TM200 is a fixed-mounted molded-case circuit breaker from the ComPacT NSX250F series. Designed for industrial and commercial applications, it offers reliable protection for electrical circuits against overloads and short circuits. This model features a 200 A thermal-magnetic (TMD) trip unit and is configured with 4 poles 3D, meaning three poles are protected, and the neutral is unprotected.
Key Specifications
Series: ComPacT NSX250F
Poles: 4P (3 protected poles, 1 unprotected neutral)
Rated Current (In): 200 A at 40 °C
Rated Operational Voltage (Ue): Up to 690 VAC, 50/60 Hz
Ultimate Short-Circuit Breaking Capacity (Icu): 36 kA at 415 VAC
Trip Unit: Thermal-Magnetic (TMD)
Protection Functions: Long-time (adjustable), Short-time (adjustable), Instantaneous (adjustable)
Mounting Type: Fixed
Dimensions: 140 mm (W) × 161 mm (H) × 86 mm (D)
Weight: Approximately 2.8 kg
Standards Compliance: IEC/EN 60947-2
IP Rating: IP40
IK Rating: IK07
Ambient Temperature Range: -35 °C to +70 °C
Features and Benefits
High Breaking Capacity: With an Icu of 36 kA at 415 VAC, it ensures robust protection against short circuits.
Thermal-Magnetic Trip Unit: Provides reliable overload and short-circuit protection with adjustable settings.
Compact Design: Its dimensions make it suitable for installations where space is limited.
Fixed Mounting: Designed for fixed installations, ensuring stability and reliability.
Wide Ambient Temperature Range: Operates effectively in a broad temperature range, from -35 °C to +70 °C.
Applications
Industrial Distribution Panels: Protects circuits in industrial settings.
Commercial Buildings: Suitable for electrical distribution in commercial infrastructures.
Feeder Protection: Ideal for protecting feeders in electrical distribution systems.
Motor Protection: Can be used to protect motors from overloads and short circuits.
-
Switchboards: Appropriate for integration into switchboards requiring high breaking capacity.
Additional information
| brand | Schneider Electric |
|---|
Specifications
| Range | ComPacT |
|---|---|
| Product name | ComPacT NSX |
| Device short name | NSX250F |
| Product or component type | Circuit breaker |
| Device application | Distribution |
| Poles description | 4P |
| Protected poles description | 3D |
| Neutral position | Left |
| [In] rated current | 200 A at 40 °C |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation category | Category A |
| Breaking capacity | 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
| Breaking capacity code | F 36 kA 415 V AC |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Trip unit protection functions | LI |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service breaking capacity | 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 15.4 W |
| Mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| Downside connection | Front |
| Connection pitch | 35 mm |
| Protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) |
| Trip unit rating | 200 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable |
| [Ir] long-time protection pick-up adjustment range | 0.7...1 x In |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir |
| Neutral protection setting | No protection (3D) |
| Instantaneous protection pick-up adjustment type Ii | Adjustable |
| [Ii] instantaneous protection pick-up adjustment range | 5...10 x In |
| Earth-leakage protection | Without |
| Number of slots | 5 slot(s) |
| Width (W) | 140 mm |
| Height (H) | 161 mm |
| Depth (D) | 86 mm |
| Net weight | 2.8 kg |
| Standards | EN/IEC 60947-2 |
|---|---|
| Overvoltage category | III |
| Electrical shock protection class | Class II on front face |
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -50…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.000 cm |
| Package 1 Width | 14.900 cm |
| Package 1 Length | 19.300 cm |
| Package 1 Weight | 2.630 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.340 kg |
Reviews (0)
Recommended for you
Schneider A9N61508 | miniature circuit breaker – C60H – 1 pole – 10 A – C curve
-
0
Schneider A9N26924 | Acti9 – Auxiliary contact OC plus 1 SD and OF ac dc
-
0
Schneider A9N18479 | Miniature circuit-breaker, Acti9 C120H, 4P, 80 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18470 | Miniature circuit-breaker, Acti9 C120H, 3P, 125 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9N18468 | Miniature circuit-breaker, Acti9 C120H, 3P, 80 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Reviews