Description

Schneider LV563510 EasyPact

Introduction

Circuit breakers play a vital role in protecting electrical systems from damage caused by overloads or short circuits. Schneider Electric, a leading provider of energy management solutions, offers it. This guide provides a thorough examination of this circuit breaker, including its features, benefits, and applications.

Understanding the Schneider LV563510 EasyPact

Overview of Schneider LV563510 EasyPact

it is an advanced circuit breaker designed to provide reliable protection for electrical circuits. It is part of Schneider Electric’s EasyPact series, known for its performance and efficiency.

Key Features and Specifications

  • Rated Current: Up to 630A
  • Breaking Capacity: High-breaking capacity for enhanced protection
  • Compact Design: Space-saving design suitable for various installations
  • Technology: Advanced tripping mechanism for rapid response
  • Compliance: Meets international standards for safety and quality

Design and Construction

Quality Build

it is built with high-quality materials to ensure durability and longevity. Its robust construction allows it to withstand harsh environmental conditions, making it suitable for a wide range of applications.

Compact Design Advantages

With its compact design, it offers significant advantages, including easy installation in space-constrained environments without compromising performance.

Material Composition

The circuit breaker is constructed from premium materials chosen for their resilience and reliability. These materials contribute to the overall durability and effectiveness of it.

Functionality and Performance

Operational Mechanism

The LV563510 EasyPact operates by interrupting the electrical current when an overload or short circuit is detected. Its advanced tripping mechanism ensures a swift response, minimizing the risk of electrical hazards.

Performance Metrics

Equipped with a high-breaking capacity and precise tripping mechanism, the LV563510 EasyPact delivers exceptional performance, meeting the stringent demands of industrial and commercial applications.

Reliability and Efficiency

Schneider Electric’s commitment to reliability is evident in the LV563510 EasyPact, offering consistent performance and energy efficiency. Its reliable operation minimizes downtime and reduces energy consumption.

Installation Process

Step-by-Step Installation Guide

  1. Preparation: Ensure all safety precautions are in place before commencing installation.
  2. Mounting: Securely mount the circuit breaker in the designated location.
  3. Wiring: Connect the electrical wires according to the provided guidelines.
  4. Testing: Conduct thorough testing post-installation to verify proper functionality.

Safety Measures During Installation

  • Always disconnect the power supply before initiating installation.
  • Use insulated tools to prevent electrical accidents.
  • Adhere to all installation instructions provided by Schneider Electric.

Necessary Tools

  • Screwdrivers
  • Wire cutters/strippers
  • Insulation tape
  • Multimeter

Applications of Schneider LV563510 EasyPact

Industrial Applications

In industrial settings, the LV563510 EasyPact protects critical machinery and equipment from electrical faults, ensuring uninterrupted operations and safety.

Commercial Applications

For commercial buildings, this circuit breaker offers reliable protection for electrical installations, including lighting, HVAC systems, and more.

Residential Applications

Even in residential settings, the LV563510 EasyPact can be utilized to safeguard home electrical systems, providing peace of mind to homeowners.

Benefits of Using Schneider LV563510 EasyPact

Enhanced Safety Features

The primary benefit of the LV563510 EasyPact is its enhanced safety features, which help prevent electrical hazards and protect both equipment and personnel.

Energy Efficiency

Designed for energy efficiency, the LV563510 EasyPact contributes to lower energy consumption and reduced operating costs over time.

Cost Savings

With its durable construction and reliable performance, the LV563510 EasyPact offers long-term cost savings, making it a cost-effective solution for electrical protection.

Comparison with Other Circuit Breakers

LV563510 EasyPact vs. Traditional Models

Compared to traditional circuit breakers, the LV563510 EasyPact stands out for its superior performance, compact design, and advanced features, providing optimal protection and efficiency.

Competitor Analysis

When compared to competitors, it excels in terms of build quality, reliability, and comprehensive support, making it a preferred choice for professionals.

Maintenance and Troubleshooting

Maintenance Tips

  • Regularly inspect for signs of wear or damage.
  • Ensure all connections are secure and tight.
  • Perform periodic testing to ensure proper functionality.

Common Issues and Solutions

  • Tripping Frequency: Check for overloads or short circuits in the electrical system.
  • Failure to Reset: Verify the breaker is not damaged and all connections are correct.

Replacement Guidelines

Replace it if significant wear or damage is observed, or if it fails to function properly after troubleshooting.

Additional information

brands

Schneider Electric

Specifications

Main
Range EasyPact
Product name EasyPact CVS
Device short name CVS630N
Product or component typee Circuit breaker
Device application Distribution
Poles description 3P
Protected poles description 3D
Earth leakage protection (Vigi add on) Without
[In] rated current 630 A at 40 °C
Network type AC
utilisation category Category A
[Icu] Breaking capacity 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit name ETS 2.3
Trip unit technology Electronic
Trip unit rating 630 A at 40 °C
Protection type Instantaneous short-circuit protection Overload protection (long time) Short time short-circuit protection
Complementary
[Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
Network frequency 50/60 Hz
Breaking capacity code N
[Ics] rated service breaking capacity 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 15000 cycles
Electrical durability 4000 cycles 415 V In conforming to IEC 60947-2
Trip unit protection functions LSoI
control type Toggle
Long time pick-up adjustment type Ir Adjustable 9 settings
long time pick-up adjustment range 250...630 A
Long time delay adjustment type Fixed
[tr] long-time delay adjustment range 5.5 s at 7.2 x Ir 8 s at 6 x Ir 200 s at 1.5 x Ir
thermal memory Yes
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment range 1.5...10 x Ir
Short-time delay adjustment type Fixed
instantaneous pick-up adjustment type Ii Fixed
instantaneous pick-up adjustment range 11 x In
Contact position indicator Yes
Mounting mode Fixed
mounting support Backplate
Upside connection Front
downside connection Front
Connections - terminals Screw connection
Connection pitch 45 mm
Compatibility code CVS630
Width 140 mm
Depth 110 mm
height 255 mm
Net weight 5.2 kg
Environment
Standards EN 60947-2 IEC 60947-2
product certifications GOST IEC
Electrical shock protection class Class II
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40
ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 15.207 cm
Package 1 Width 15.632 cm
Package 1 Length 29.21 cm
Package 1 Weight 5.568 kg
Unit Type of Package 2 CAR
Number of Units in Package 2 3
Package 2 Height 22.7 cm
Package 2 Width 37.8 cm
Package 2 Length 49.3 cm
Package 2 Weight 18.5 kg
Unit Type of Package 3 PAL
Number of Units in Package 3 48
Package 3 Height 90.0 cm
Package 3 Width 80.0 cm
Package 3 Length 120.0 cm
Package 3 Weight 282840.0 g
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : LV563510 

Main Document

Data Sheet : LV563510 

Reviews (0)

Be the first to review “Schneider LV563510 EasyPact | circuit breaker EasyPact CVS630N, 50 kA at 415 VAC, 630 A rating ETS 2.3 electronic trip unit, 3P 3d”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare