Description

Schneider A9F73404 | Miniature circuit breaker (MCB), Acti9 iC60N, 4P, 4A, B curve, 6000A (IEC/EN 60898-1), 50kA (IEC/EN 60947-2)

Schneider A9F73404 Description.

The Schneider A9F73404 is a part of the Acti9 series by Schneider Electric. This series is known for its high-quality and reliable modular protection devices, designed for electrical distribution systems in residential, commercial, and industrial applications. Here’s a detailed description of the A9F73404 model.

Schneider A9F73404 Miniature Circuit Breaker (MCB)

Key Features:

  1. Protection:
    • Provides protection against overcurrents, including both overloads and short circuits.
    • Enhances safety by preventing damage to electrical circuits and reducing the risk of fire.
  2. Current Rating:
    • Rated at 4A, making it suitable for applications that require protection of circuits with this specific current rating.
  3. Breaking Capacity:
    • High breaking capacity, ensuring reliable operation even in the event of significant overcurrent conditions.
    • Specifically designed to handle breaking capacity requirements as per manufacturer specifications.
  4. Design:
    • Compact and modular design allows for efficient use of space in electrical distribution boards.
    • DIN rail mountable, facilitating easy installation and integration with other modular devices.
  5. Indicators:
    • Includes visual indicators for operational status and trip status, making it easier to identify when the circuit breaker has tripped.
  6. Compliance:
    • Complies with international standards for circuit protection, ensuring reliable and safe operation.

Applications:

  • Residential: Ideal for protecting household electrical circuits, including power outlets, lighting circuits, and small appliances.
  • Commercial: Suitable for safeguarding electrical circuits in office buildings, retail spaces, and other commercial environments.
  • Industrial: Applicable in light industrial settings to protect control circuits, machinery, and equipment from overcurrents.

Benefits:

  • Enhanced Safety: Provides reliable protection against overcurrents, reducing the risk of fire and damage to electrical installations.
  • Space-Saving: The modular design ensures efficient use of space in electrical panels.
  • Ease of Maintenance: Visual indicators provide quick identification of operational status and faults, facilitating easier maintenance and troubleshooting.
  • Reliability: Constructed with high-quality materials to ensure long-lasting performance and dependable protection.

Considerations:

  • Compatibility: Ensure the MCB is compatible with the specific electrical system and load requirements of your installation.
  • Professional Installation: It is recommended to have a qualified electrician install and maintain the MCB for optimal performance and safety.

Specifications:

  • Model: Schneider A9F73404
  • Series: Acti9
  • Current Rating: 4A
  • Poles: Single-pole (1P)
  • Breaking Capacity: As per manufacturer specifications
  • Mounting: DIN rail

The Schneider A9F73404 MCB is an excellent choice for ensuring the safety and efficiency of your electrical systems, providing robust protection and reliability.

Additional information

brands

Schneider Electric

Specifications

Main
Device application Distribution
Range Acti9
Product name Acti9 iC60
product or component type Miniature circuit-breaker
Device short name IC60N
poles description 4P
Number of protected poles 4
[In] rated current 4 A
Network type DC AC
Trip unit technology Thermal-magnetic
Curve code B
Breaking capacity 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 50 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2
Utilisation category Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2
Standards IEC 60898-1 EN 60898-1 EN 60947-2 IEC 60947-2
Complementary
Network frequency 50/60 Hz
Magnetic tripping limit 4 x In +/- 20 %
[Ics] rated service breaking capacity 50 kA 100 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 10 kA 100 % conforming to IEC 60947-2 - 180...250 V DC 10 kA 100 % conforming to EN 60947-2 - 180...250 V DC
Limitation class 3 conforming to EN 60898-1 3 conforming to IEC 60898-1
[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator Yes
Control type Toggle
local signalling Trip indicator
mounting mode Fixed
mounting support DIN rail
Comb busbar and distribution block compatibility Top or bottom: YES
9 mm pitches 8
Height 85 mm
Width 72 mm
Depth 78.5 mm
net weight 0.5 kg
Colour White
Mechanical durability 20000 cycles
Electrical durability 10000 cycles
Connections - terminals Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length 14 mm for top or bottom connection
Tightening torque 2 N.m top or bottom
Earth-leakage protection Separate block
Environment
IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529
Pollution degree 3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category IV
Tropicalisation 2 conforming to IEC 60068-1
Relative humidity 95 % at 55 °C
Operating altitude 0...2000 m
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -40…85 °C
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.000 cm
Package 1 Width 7.500 cm
Package 1 Length 9.500 cm
Package 1 Weight 440.700 g
Unit Type of Package 2 BB1
Number of Units in Package 2 3
Package 2 Height 8.000 cm
Package 2 Width 10.000 cm
Package 2 Length 22.500 cm
Package 2 Weight 1.388 kg
Unit Type of Package 3 S03
Number of Units in Package 3 33
Package 3 Height 30.000 cm
Package 3 Width 30.000 cm
Package 3 Length 40.000 cm
Package 3 Weight 15.704 kg
Contractual warranty
Warranty 18 months

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider A9F73404 | Miniature circuit breaker (MCB), Acti9 iC60N, 4P, 4A, B curve, 6000A (IEC/EN 60898-1), 50kA (IEC/EN 60947-2)”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare