Schneider A9F77463 | Miniature circuit-breaker, Acti9 iC60N, 4P, 63 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
Description
Schneider A9F77463 | Miniature circuit-breaker, Acti9 iC60N, 4P, 63 A, C curve, 6000 A (IEC 60898-1), 10 kA (IEC 60947-2)
Schneider A9F77463 Description
The Schneider A9F77463 is a miniature circuit breaker (MCB) designed for residential and small commercial electrical installations. Here’s a detailed description:
Product Name: Schneider A9F77463 Type: Miniature Circuit Breaker (MCB) Current Rating: 63 Amps Number of Poles: 4 Poles (Quadri) Breaking Capacity: 10 kA Voltage Rating: 230/400V AC Frequency: 50/60 Hz Trip Curve: C Curve (standard magnetic trip characteristics) Mounting: DIN rail mountable
Features:
- Compact Design: Occupies minimal space in electrical panels.
- High Breaking Capacity: Can safely interrupt faults up to 10,000 amps.
- C Curve Trip Characteristics: Suitable for general electrical installations where moderate overloads and short-circuits are expected.
- Quadri Pole Configuration: Provides protection for all four poles, ensuring comprehensive circuit protection.
Applications: The Schneider A9F77463 is commonly used in residential buildings, small commercial installations, and light industrial applications where reliable circuit protection against overloads and short circuits is essential. It is suitable for protecting circuits supplying power to various electrical devices and equipment.
Standards: Compliant with international standards for circuit breakers, ensuring safety and reliability in electrical installations.
This MCB is part of Schneider Electric’s range of circuit protection devices, known for their durability, performance, and ease of installation in diverse electrical setups.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Device application | Distribution |
|---|---|
| Range | Acti9 |
| Product name | Acti9 iC60 |
| product or component type | Miniature circuit-breaker |
| Device short name | IC60N |
| poles description | 4P |
| Number of protected poles | 4 |
| [In] rated current | 63 A |
| Network type | AC DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 36 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 |
| Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
| Standards | EN 60947-2 IEC 60898-1 IEC 60947-2 EN 60898-1 |
| Quality labels | NF |
| Network frequency | 50/60 Hz |
|---|---|
| Magnetic tripping limit | 8 x In +/- 20 % |
| [Ics] rated service breaking capacity | 15 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 15 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 27 kA 75 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 27 kA 75 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 10 kA 100 % conforming to IEC 60947-2 - 180...250 V DC 10 kA 100 % conforming to EN 60947-2 - 180...250 V DC |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| Control type | Toggle |
| local signalling | Trip indicator |
| mounting mode | Fixed |
| mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Top or bottom: YES |
| 9 mm pitches | 8 |
| Height | 85 mm |
| Width | 72 mm |
| Depth | 78.5 mm |
| net weight | 0.5 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections - terminals | Single terminal (top or bottom) 1…35 mm² rigid Single terminal (top or bottom) 1…25 mm² flexible |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 3.5 N.m top or bottom |
| Earth-leakage protection | Separate block |
| IP degree of protection | IP20 conforming to IEC 60529 IP20 conforming to EN 60529 |
|---|---|
| Pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 0...2000 m |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.3 cm |
| Package 1 Width | 7.1 cm |
| Package 1 Length | 8.5 cm |
| Package 1 Weight | 512 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 8.2 cm |
| Package 2 Width | 9.8 cm |
| Package 2 Length | 22.4 cm |
| Package 2 Weight | 1.601 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 33 |
| Package 3 Height | 30 cm |
| Package 3 Width | 30 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 18.099 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
-
0
Schneider A9F87432 | Miniature circuit-breaker, Acti9 iC60H, 4P, 32 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9F87416 | Miniature circuit-breaker, Acti9 iC60H, 4P, 16 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9F87410 | Miniature circuit-breaker, Acti9 iC60H, 4P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9F74303 | Miniature circuit breaker (MCB), Acti9 iC60N, 3P, 3A, C curve, 6000A (IEC/EN 60898-1), 50kA (IEC/EN 60947-2)
-