Schneider A9F74302 | Miniature circuit breaker (MCB), Acti9 iC60N, 3P, 2A, C curve, 6000A (IEC/EN 60898-1), 50kA (IEC/EN 60947-2)
Description
Schneider A9F74302 | Miniature circuit breaker (MCB), Acti9 iC60N, 3P, 2A, C curve, 6000A (IEC/EN 60898-1), 50kA (IEC/EN 60947-2)
Product Overview: Schneider A9F74302 | Miniature Circuit Breaker (MCB) – Acti9 iC60N – 3P – 2A – C Curve – 6000A
The Schneider Electric A9F74302 is a 3-pole Miniature Circuit Breaker (MCB) from the trusted Acti9 iC60N range, designed to offer precise protection for circuits requiring low current rating and high safety standards. With a rated current of 2A, C curve tripping, and breaking capacity of 6000 A (IEC/EN 60898-1) and up to 50 kA (IEC/EN 60947-2), it ensures excellent performance in various electrical environments.
Key Features:
-
Brand: Schneider Electric
-
Range: Acti9 iC60N
-
Model Number: A9F74302
-
Type: Miniature Circuit Breaker (MCB)
-
Number of Poles: 3P (Triple Pole)
-
Rated Current: 2 Amperes
-
Tripping Curve: C Curve
-
Breaking Capacity:
– 6 kA (IEC/EN 60898-1)
– Up to 50 kA (IEC/EN 60947-2) -
Rated Operational Voltage: 400 V AC
-
Frequency: 50/60 Hz
Technical Specifications:
-
Mounting: DIN rail (35 mm)
-
Terminal Capacity: 1.5–25 mm² (flexible/rigid cables)
-
Operating Temperature: −25°C to +70°C
-
IP Rating: IP20 (with terminal covers)
-
Endurance:
– Electrical: up to 10,000 cycles
– Mechanical: up to 20,000 cycles -
Conformity Standards:
– IEC/EN 60898-1
– IEC/EN 60947-2
Functional Characteristics:
-
C Curve Tripping:
– Trips between 5 to 10 times the rated current
– Ideal for protecting general-purpose loads such as lighting, receptacles, and small motors -
Fault Protection:
– Overload protection
– Short-circuit protection -
Indicators:
– ON/OFF/Tripped position status -
Accessory Compatibility:
– Fully compatible with Acti9 iOF auxiliary contacts, alarms, and remote-control accessories
Applications:
-
Industrial control panels
-
Distribution boards in commercial buildings
-
Sub-circuits in manufacturing plants
-
Lighting and power circuits requiring low amperage
-
Equipment and process protection in sensitive installations
Why Choose A9F74302?
-
Trusted Schneider Electric quality
-
Enhanced safety with high breaking capacity
-
Easy installation and modular expandability
-
Durable for both electrical and mechanical longevity
-
Ideal for low-current, three-phase circuits
Recommended For:
-
Electrical consultants and engineers
-
Industrial electricians
-
Panel manufacturers
-
Maintenance teams
-
Facilities management
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Device application | Distribution |
|---|---|
| Range | Acti9 |
| Product name | Acti9 iC60 |
| Product or component type | Miniature circuit-breaker |
| Device short name | IC60N |
| Poles description | 3P |
| Number of protected poles | 3 |
| [In] rated current | 2 A |
| Network type | AC DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 50 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 |
| Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
| Standards | EN 60947-2 IEC 60947-2 IEC 60898-1 EN 60898-1 |
| Quality labels | NF |
| Network frequency | 50/60 Hz |
|---|---|
| Magnetic tripping limit | 8 x In +/- 20 % |
| [Ics] rated service breaking capacity | 50 kA 100 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 50 kA 100 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 6000 A 100 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 6000 A 100 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 10 kA 100 % conforming to IEC 60947-2 - 125...180 V DC 10 kA 100 % conforming to EN 60947-2 - 125...180 V DC |
| Limitation class | 3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| control type | Toggle |
| local signalling | Trip indicator |
| Mounting mode | Fixed |
| mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Top or bottom: YES |
| 9 mm pitches | 6 |
| height | 85 mm |
| Width | 54 mm |
| Depth | 78.5 mm |
| Net weight | 0.375 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections - terminals | Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 2 N.m top or bottom |
| earth-leakage protection | Separate block |
| IP degree of protection | IP20 conforming to IEC 60529 IP20 conforming to EN 60529 |
|---|---|
| Pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 0...2000 m |
| ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.5 cm |
| Package 1 Width | 7.3 cm |
| Package 1 Length | 9.3 cm |
| Package 1 Weight | 334.0 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 8.0 cm |
| Package 2 Width | 10.0 cm |
| Package 2 Length | 22.5 cm |
| Package 2 Weight | 1.384 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 44 |
| Package 3 Height | 30.0 cm |
| Package 3 Width | 30.0 cm |
| Package 3 Length | 40.0 cm |
| Package 3 Weight | 15.717 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : A9F74302
Main Document
Data Sheet : A9F74302
Reviews (0)
Recommended for you
-
0
Schneider A9F94163 |Miniature circuit-breaker, Acti9 iC60L, 1P, 63 A, C curve, 15 kA (IEC 60947-2)
-
0
Schneider A9F94140 | Miniature circuit-breaker, Acti9 iC60L, 1P, 40 A, C curve, 15000 A (IEC 60898-1), 20 kA (IEC 60947-2)
-
0
Schneider A9F87432 | Miniature circuit-breaker, Acti9 iC60H, 4P, 32 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Schneider A9F87110 | Miniature circuit-breaker, Acti9 iC60H, 1P, 10 A, C curve, 10000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.