Description

Schneider C125N320FM | Circuit breaker, ComPacT NS1250N, 50kA at 415VAC, 3P, fixed, manually operated, MicroLogic 2.0 control unit, 1250A

The Schneider C125N320FM is a type of circuit breaker that is part of the ComPacT NS1250N series, designed for protection and control in electrical installations. It is a fixed, manually operated, three-pole circuit breaker with a MicroLogic 2.0 control unit. Here is a detailed breakdown of its specifications, features, and uses:

1. Technical Specifications of Schneider C125N320FM:

  • Product Series: ComPacT NS1250N
  • Current Rating: 1250A
  • Rated Voltage: 415VAC
  • Rated Breaking Capacity: 50kA at 415V AC
  • Poles: 3-pole configuration
  • Control Unit: MicroLogic 2.0 (provides protection, measurement, and control functions)
  • Operation Type: Manually operated
  • Mounting Type: Fixed installation
  • Frame Size: 1250A
  • Frequency: Suitable for 50/60 Hz applications
  • Interrupting Capacity: Can handle fault currents up to 50,000 amperes (50kA), ensuring safe operation in case of electrical faults.

2. Features of Schneider C125N320FM

  • High Breaking Capacity: The circuit breaker can interrupt fault currents up to 50kA at 415V AC, offering high protection against electrical overloads and short circuits.
  • MicroLogic 2.0 Control Unit: This advanced control unit provides:
    • Overload protection: Ensures the breaker trips if the current exceeds safe levels.
    • Short circuit protection: Instantly trips the breaker in case of short circuits.
    • Under-voltage protection: Helps prevent damage to the circuit when voltage drops below the safe level.
    • Measurement functions: Monitors parameters like current, voltage, and other essential electrical data for better system management.
  • Manual Operation: The breaker is manually operated, making it easy to reset or disconnect during maintenance.
  • Fixed Installation: Designed for fixed, permanent installation in electrical distribution boards or panel systems.
  • Compact and Reliable: Despite its high current capacity, the circuit breaker is compact in design, allowing for space-efficient installation.

3. Applications of Schneider C125N320FM

  • Electrical Protection: The C125N320FM is primarily used for protecting electrical circuits from damage caused by overloads, short circuits, or other electrical faults. It’s ideal for both residential and industrial applications.
  • Industrial Distribution Systems: It is commonly used in large industrial systems, including manufacturing facilities and power distribution stations, to protect high-current equipment.
  • Switchgear Panels: The circuit breaker is suitable for integration into low-voltage switchgear panels and motor control centers (MCCs).
  • Control and Measurement: Due to its MicroLogic 2.0 control unit, it can be employed in control and measurement systems where precise monitoring of electrical parameters is needed.
  • HVAC and Data Centers: Can be used to protect electrical equipment in HVAC systems or data centers, where continuous, reliable power is critical.

Additional information

brands

Schneider Electric

Specifications

Main
Range ComPacT
product name ComPacT NS new generation
Range of product ComPacT NS630b...1600 new generation
Product or component type Circuit breaker
Device application Distribution
Number of poles 3P
Protected poles description 3D
(In) rated current up to 65 °C 1250 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit breaking capacity 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
Trip unit name MicroLogic 2.0
Trip unit technology Electronic
Trip unit protection functions LI
control type Manually operated
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 8 kV conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current 19.2 kA 1 s conforming to IEC 60947-2
Mechanical durability 10000 cycles
Electrical durability 2000 cycles at 690 V In 3000 cycles at 690 V In/2 4000 cycles at 440 V In 5000 cycles at 440 V In/2
Power losses 44 W
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 70 mm
Protection type L : for overload protection (long time) I : for instantaneous short-circuit protection
Trip unit rating 1250 A at 50 °C
Long-time pick-up adjustment type Ir (thermal protection) Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range 0.4...1 x In
Long-time protection delay adjustment type tr Adjustable 9 settings
[tr] long-time protection delay adjustment range 12.5…600 s at 1.5 x Ir 0.5…24 s at 6 x Ir 0.7…16.6 s at 7.2 x Ir
Thermal memory 20 mn
Instantaneous protection pick-up adjustment type Ii Adjustable
[Ii] instantaneous protection pick-up adjustment range 1.5...10 x Ir
Earth-leakage protection Without
Zone selective interlocking ZSI Without
Auxiliary contact composition 1 NO/NC
Local signalling 4 LEDs (red) for fault indication 1 LED (yellow) for overload
Width (W) 210 mm
Height (H) 327 mm
Depth (D) 147 mm
Product weight 14 kg
Environment
Standards EN/IEC 60947-2
Product certifications IECEE CB Scheme
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
ambient air temperature for operation -25…70 °C
Ambient air temperature for storage -50…85 °C
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 30.000 cm
Package 1 Width 40.000 cm
Package 1 Length 60.000 cm
Package 1 Weight 12.832 kg

Reviews (0)

Be the first to review “Schneider C125N320FM | Circuit breaker, ComPacT NS1250N, 50kA at 415VAC, 3P, fixed, manually operated, MicroLogic 2.0 control unit, 1250A”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare