Schneider C11B44V050L | circuit breaker ComPacT NSXm B (25 kA at 415 VAC), 4P 4d, 50 A rating Micrologic 4.1 trip unit,connectors
Description
Schneider C11B44V050L | circuit breaker ComPacT NSXm B (25 kA at 415 VAC), 4P 4d, 50 A rating Micrologic 4.1 trip unit,connectors
Schneider C11B44V050L Description
ComPacT NSXm100B is a complete 4P fixed circuit breaker designed to optimize space and breaking capacity.
The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz.
The operational voltage is 440VAC 50/60Hz.
It introduces new features like Everlink connectors technology.
It offers built-in DIN rail & plate mounting capability and spring type auxiliaries externally visible.
This 4 poles Earth Leakage Circuit Breaker (ELCB) is one of the smallest on the market. The dimensions are 108mm (W) x 144mm (H) x 80mm (D).
It ensures compliance with international standards (IEC 60947/CCC/EAC) and marine specifications.
The Schneider Electric C11B44V050L is a specific model within Schneider’s lineup of molded case circuit breakers (MCCBs), designed to provide reliable circuit protection in various industrial and commercial applications. Here’s a detailed description of the C11B44V050L:
Schneider Electric C11B44V050L Molded Case Circuit Breaker
General Description:
- Series: C11
- Product Type: Molded Case Circuit Breaker (MCCB)
- Function: The C11B44V050L MCCB is designed to protect electrical circuits from overloads and short circuits, ensuring safe and efficient operation.
Technical Specifications:
- Rated Current (In): 50 A
- Poles: 4 poles
- Breaking Capacity: Adequate for safely interrupting fault currents to protect downstream equipment and systems.
- Rated Operational Voltage (Ue): Typically suitable for low-voltage applications (specific details to model needed).
- Trip Unit: Features a thermal-magnetic trip unit providing both thermal overload and magnetic short-circuit protection.
Design and Construction:
- Size: Compact and standardized design, facilitating integration into electrical panels and distribution boards.
- Material: Constructed from high-quality materials to ensure durability and reliability in demanding environments.
- Mounting: Offers flexibility with options for fixed mounting and plug-in bases, enabling straightforward installation according to application requirements.
Features:
- Thermal-Magnetic Trip: Incorporates a thermal element for overload conditions and a magnetic element for short-circuit conditions, ensuring effective and reliable circuit protection.
- Adjustable Settings: Allows for adjustable trip settings to tailor protection based on specific application needs, enhancing versatility and operational efficiency.
- Front Access: Provides convenient access to terminals and settings from the front of the MCCB, simplifying installation, maintenance, and troubleshooting tasks.
- Visual Indicators: Equipped with clear indicators to monitor the operational status of the MCCB, facilitating quick identification of tripped conditions.
Applications:
- Industrial and Commercial Use: Well-suited for protecting electrical circuits in various applications, including industrial facilities, commercial buildings, and infrastructure projects.
- Electrical Distribution: Commonly employed in main and sub-distribution boards to ensure reliable circuit protection and operational safety.
Certifications and Standards:
- Compliance: Conforms to international standards such as IEC 60947-2 and other relevant standards, ensuring adherence to safety and performance requirements.
- Certifications: Holds certifications such as CE, UL, CSA, and other regional certifications, affirming compliance with established quality and safety standards.
Advantages:
- Reliability: High breaking capacity and robust trip mechanisms ensure dependable circuit protection under varying electrical conditions, minimizing downtime and enhancing system reliability.
- Versatility: Suitable for diverse applications across industrial and commercial sectors, offering flexibility in installation and operation.
- Ease of Installation: Compact design and multiple mounting options simplify installation processes, reducing installation time and effort.
- Durability: Constructed with durable materials to withstand harsh operating environments, ensuring long-term performance and reliability.
Summary
The Schneider Electric C11B44V050L molded case circuit breaker is a reliable solution for protecting electrical circuits from overloads and short circuits in industrial and commercial settings. With its thermal-magnetic trip unit, adjustable settings, and durable construction, it provides robust circuit protection while offering flexibility and ease of installation for various applications.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | ComPacT new generation |
|---|---|
| Product name | ComPacT NSXm new generation |
| Range of product | ComPacT NSXm new generation |
| Device short name | NSXm 63B |
| product or component type | Earth leakage circuit breaker |
| Device application | Distribution |
| poles description | 4P |
| Protected poles description | 4D |
| Neutral position | Left |
| [In] rated current | 50 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitability for isolation | Yes conforming to IEC 60947-2 |
| Utilisation category | Category A |
| [Icu] rated ultimate short-circuit breaking capacity | 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| Performance level | B 25 kA 415 V AC |
| Trip unit name | MicroLogic 4.1 |
| Trip unit technology | Electronic |
| Trip unit protection functions | LSoIR |
| Control type | Toggle |
| Circuit breaker mounting mode | Fixed |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz |
|---|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ics] rated service short-circuit breaking capacity | 50 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical durability | 20000 cycles |
| Electrical durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
| Power dissipation per pole | 1.88 W |
| mounting support | Backplate |
| Mounting position | Horizontal and vertical Flat on the back |
| Upside connection | Front |
| downside connection | Front |
| Connection terminals | 1 Everlink lug wire size 2.5…70 mm², fine stranded copper 1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper |
| Connection pitch | 35 mm with spreaders 27 mm without spreaders |
| 9 mm pitches | 12 module |
| Trip unit rating | 50 A at 40 °C |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
| [Ir] long-time protection pick-up adjustment range | 20...50 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 200 s at 1.5 x Ir 8 s at 6 x Ir 5 s at 7.2 x Ir |
| Neutral protection settings | 1 x Ir (4D) |
| thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 750 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A Class AC |
| Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
| [IΔn] earth-leakage protection sensitivity adjustment range | 30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A |
| Earth-leakage sensitivity | 30 mA for class A 100 mA for class A 300 mA for class A 500 mA for class A 1 A for class A 30 mA for class AC 100 mA for class AC 300 mA for class AC 500 mA for class AC 1 A for class AC 3 A for class AC 5 A for class AC |
| Earth-leakage protection time delay adjustement type Δt | Adjustable |
| [Δt] Earth-leakage protection time delay adjustment range | 0 ms 60 ms 150 ms 500 ms 1000 ms |
| Number of slots for electrical auxiliaries | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| Local signalling | Flag (green) for presence of auxiliary contacts |
| Width (W) | 108 mm |
| Height (H) | 144 mm |
| Depth (D) | 80 mm |
| net weight | 1.63 kg |
| Colour | Grey (RAL 7016) |
| Standards | EN/IEC 60947 |
|---|---|
| Pollution degree | 3 conforming to IEC 60664-1 |
| IP degree of protection | IP40 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 62262 |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 2000 m without derating 5000 m with derating |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.200 cm |
| Package 1 Width | 13.200 cm |
| Package 1 Length | 18.900 cm |
| Package 1 Weight | 1.788 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.529 kg |
Reviews