Overview and Specifications
it is part of the Acti9 series, known for its robustness and advanced features. It is a 2-pole circuit breaker with a breaking capacity of 6 kA, designed for use in residential, commercial, and industrial environments.
Key Features
- High Breaking Capacity: With a capacity of 6 kA, it can handle significant electrical loads.
- Compact Design: Easy to integrate into various electrical panels.
- Reliable Performance: Ensures long-term safety and functionality.
- Energy Efficient: Helps in reducing energy consumption and costs.
Applications of Schneider A9K24206
Residential Use
In homes, it provides essential protection for electrical systems, ensuring that household appliances and electronics are safe from electrical surges and faults.
Commercial Use
In commercial buildings, it ensures that critical systems like lighting, HVAC, and security systems operate reliably without interruptions due to electrical issues.
Industrial Use
In industrial settings, where electrical loads are significantly higher, the Schneider A9K24206 ensures machinery and equipment are protected, maintaining operational efficiency and safety.
Installation of Schneider A9K24206
Pre-Installation Requirements
- Ensure Compatibility: Verify that the Schneider A9K24206 is suitable for your electrical system.
- Gather Tools and Equipment: Necessary tools include screwdrivers, wire strippers, and multimeters.
Step-by-Step Installation Guide
- Turn Off Power: Ensure the main power supply is switched off to avoid electrical shocks.
- Mount the Breaker: Securely mount the Schneider A9K24206 in the designated slot in the electrical panel.
- Connect Wires: Connect the input and output wires to the respective terminals on the breaker.
- Test the Installation: After installation, turn on the power and test the breaker to ensure it operates correctly.
Safety Precautions
- Always follow manufacturer instructions.
- Wear protective gear such as gloves and safety goggles.
- If unsure, consult a professional electrician.
Advantages of Using Schneider A9K24206
Durability and Reliability
The Schneider A9K24206 is built to last, with high-quality materials ensuring it performs reliably over time.
Energy Efficiency
Designed to minimize energy losses, it helps in reducing electricity bills.
Cost-Effectiveness
While it may have a higher upfront cost, the long-term savings in energy and maintenance make it a cost-effective choice.
Maintenance and Troubleshooting
Regular Maintenance Tips
- Periodic Inspections: Regularly check for any signs of wear or damage.
- Clean Components: Keep the breaker and surrounding area clean to avoid dust buildup.
- Test Functionality: Periodically test the breaker to ensure it trips correctly.
Common Issues and Solutions
- Breaker Tripping Frequently: Check for overloaded circuits and reduce the load if necessary.
- No Power to Circuit: Ensure all connections are secure and there are no loose wires.
- Physical Damage: Replace the breaker if there are any visible signs of damage.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Device application | Distribution |
|---|---|
| Range | Acti9 |
| Product name | Acti9 iK60 |
| product or component type | Miniature circuit-breaker |
| Device short name | iK60N |
| poles description | 2P |
| Number of protected poles | 2 |
| [In] rated current | 6 A at 30 °C |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Suitability for isolation | Yes conforming to EN/IEC 60898-1 |
| Standards | EN/IEC 60898-1 |
| Network frequency | 50/60 Hz |
|---|---|
| Magnetic tripping limit | 5...10 x In |
| [Ics] rated service breaking capacity | 6000 A 100 % conforming to EN/IEC 60898-1 - 230 V AC 50/60 Hz |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage | 440 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60898-1 |
| Contact position indicator | No |
| Control type | Toggle |
| local signalling | ON/OFF indication |
| mounting mode | Clip-on |
| mounting support | DIN rail |
| 9 mm pitches | 4 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 78.5 mm |
| net weight | 200 g |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Locking options description | Padlocking device |
| Connections - terminals | Tunnel type terminal (top or bottom) 1…25 mm² rigid Tunnel type terminal (top or bottom) 1…16 mm² flexible |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 2 N.m top or bottom |
| Earth-leakage protection | Without |
| IP degree of protection | IP20 conforming to IEC 60529 |
|---|---|
| Pollution degree | 2 conforming to EN/IEC 60898-1 |
| Overvoltage category | II |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.500 cm |
| Package 1 Width | 7.500 cm |
| Package 1 Length | 9.000 cm |
| Package 1 Weight | 195.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 8.500 cm |
| Package 2 Width | 10.000 cm |
| Package 2 Length | 22.000 cm |
| Package 2 Weight | 1.225 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 66 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 13.904 kg |
| Warranty | 18 months |
|---|