Schneider A9D61820 | iC60N – earth leakage circuit breaker – 1P + N – C curve – 20 A – 30 mA – 240 V
Description
Schneider A9D61820 | iC60N – earth leakage circuit breaker – 1P + N – C curve – 20 A – 30 mA – 240 V
Schneider A9D61820 Description
This Acti9 iC60 is a modular residual current breaker with overcurrent protection (RCBO).
It is a 1P+N circuit breaker with 1 protected pole, 20A In rated current and C tripping curve.
The earth leakage protection class is A type with a sensitivity of 30mA.
The earth-leakage protection time delay is instantaneous.
The Icn rated short circuit breaking capacity is up to 6000A according 0 standard.
Its unique Visitrip indicator reduces intervention time by showing the faulty circuit.
Its Visisafe green strip guarantees the physical opening of the contacts to allow downstream maintenance.
Its fast closing mechanism independent of manual operation improves its service life.
This product is compliant with AS/NZS 61009.1 and IEC 61009-2-2 standards.
It has an electrical endurance going up to 5000 cycles and a mechanical endurance going up to 20000 cycles.
The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 400VAC.
The Uimp rated impulse withstand voltage is 4kV.
The frequency is 50Hz. It is DIN rail mountable.
The width in 9mm pitches is 2. The product color is white (RAL9003).
The dimensions are (W) 18mm x (H) 110mm x (D) 77.5mm. The weight is 205g.
It has an IP20 degree of protection (as per IEC/EN 60529 standard) and becomes IP40 once in modular enclosure.
The operating temperature is from -15°C to 60°C.
The storage temperature is from -40°C to 85°C.
The Schneider A9D61820 is part of the Acti9 series, which includes a range of modular protection devices designed for electrical distribution systems in residential, commercial, and industrial applications. This specific model is a Residual Current Circuit Breaker with Overcurrent Protection (RCBO).
Schneider A9D61820 Residual Current Circuit Breaker with Overcurrent Protection (RCBO)
Key Features:
- Protection:
- Combines the functions of a miniature circuit breaker (MCB) and a residual current device (RCD) in one unit.
- Provides protection against overcurrents (overload and short-circuit) and earth leakage currents.
- Enhances safety by protecting people against electric shocks and preventing electrical fires.
- Current Rating:
- Rated at 20A, making it suitable for a range of applications requiring this current rating.
- Sensitivity:
- Earth leakage sensitivity of 30mA, which is the standard for protecting against indirect contact and fire hazards.
- Design:
- Compact and modular design allows for efficient use of space in electrical distribution boards.
- DIN rail mountable, making installation and integration with other modular devices straightforward.
- Breaking Capacity:
- Designed to handle specific breaking capacity, ensuring reliable operation in various electrical installations.
- Indicators:
- Includes visual indicators for operational status and trip status, facilitating quick identification of issues.
Applications:
- Residential: Ideal for protecting household electrical circuits, including power outlets, lighting circuits, and appliances.
- Commercial: Suitable for protecting electrical circuits in offices and commercial buildings.
- Industrial: Applicable in light industrial settings for protecting machinery and control circuits from overcurrents and earth leakage.
Benefits:
- Enhanced Safety: Provides comprehensive protection by combining overcurrent and earth leakage protection, reducing the risk of electric shocks and fires.
- Space-Saving: The modular design ensures efficient use of space in electrical panels.
- Ease of Maintenance: Visual indicators provide quick identification of operational status and faults, making maintenance and troubleshooting easier.
- Reliability: Built with high-quality materials to ensure long-lasting performance and reliable protection.
Considerations:
- Compatibility: Ensure the RCBO is compatible with the specific electrical system and load requirements of your installation.
- Regular Testing: Periodically test the RCBO to ensure it is functioning correctly and providing necessary protection.
- Professional Installation: It is recommended to have a qualified electrician install and maintain the RCBO for optimal performance and safety.
Specifications:
- Model: Schneider A9D61820
- Series: Acti9
- Current Rating: 20A
- Sensitivity: 30mA
- Poles: Single-pole + Neutral (1P+N)
- Breaking Capacity: As per manufacturer specifications
Schneider Electric’s Acti9 series is known for its high-quality and reliable electrical protection devices, and the A9D61820 RCBO is an excellent choice for ensuring the safety and efficiency of your electrical systems.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Circuit breaker application | Distribution |
|---|---|
| Range | Acti9 |
| Product name | Acti9 iC60 RCBO |
| product or component type | Residual current breaker with overcurrent protection (RCBO) |
| Device short name | iC60N RCBO |
| poles description | 1P + Ns |
| [In] rated current | 20 A at 50 °C |
| Earthing system | TN |
| Curve code | C |
| Earth-leakage sensitivity | 30 mA |
| Breaking capacity | 6000 A Icn at 230/240 V AC 50/60 Hz |
| Neutral position | Left |
|---|---|
| Number of protected poles | 1 |
| Device location in system | Outgoer |
| Network frequency | 50 Hz |
| Network type | AC |
| Trip unit technology | Thermal-magnetic |
| [Ue] rated operational voltage | 230/240 V AC 50/60 Hz |
| Residual current tripping technology | Voltage dependent |
| Earth-leakage protection time delay | Instantaneous |
| Earth-leakage protection class | Type A |
| [Icw] rated short-time withstand current | Icw: 250 A during 8/20 µs impulse withstand |
| [Ics] rated service breaking capacity | 6000 A at 230/240 V AC 50/60 Hz |
| Limitation class | 3 |
| [Ui] rated insulation voltage | 400 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Surge current | 250 A |
| Suitability for isolation | Yes |
| Contact position indicator | Yes |
| Control type | Toggle |
| local signalling | ON/OFF indication |
| mounting mode | Clip-on |
| mounting support | DIN rail |
| Comb busbar and distribution block compatibility | NO |
| 9 mm pitches | 2 |
| Height | 110 mm |
| Width | 18 mm |
| Depth | 77.5 mm |
| net weight | 205 g |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 5000 cycles |
| Provision for padlocking | Padlockable with padlock Ø 4 mm |
| Locking options description | ON/OFF locking facilities |
| Connections - terminals | Screw clamp terminal (top) 1…25 mm² rigid without cable end Screw clamp terminal (top) 1…16 mm² flexible Screw clamp terminal (bottom) 1…16 mm² rigid without cable end Screw clamp terminal (bottom) 1…10 mm² flexible |
| Wire stripping length | Power circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection |
| Tightening torque | Power circuit: 3.5 N.m top Power circuit: 2 N.m bottom |
| Earth-leakage protection | Integrated |
| Standards | AS/NZS 61009.1 IEC 61009-2-2 IEC 61009-1 |
|---|---|
| IP degree of protection | IP20 |
| Tropicalisation | 2 |
| Relative humidity | 95 % at 55 °C |
| Ambient air temperature for operation | -15…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.5 cm |
| Package 1 Width | 9.5 cm |
| Package 1 Length | 1.8 cm |
| Package 1 Weight | 211 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 34 |
| Package 2 Height | 15 cm |
| Package 2 Width | 29.2 cm |
| Package 2 Length | 39.8 cm |
| Package 2 Weight | 7.896 kg |
| Unit Type of Package 3 | P12 |
| Number of Units in Package 3 | 1088 |
| Package 3 Height | 70 cm |
| Package 3 Width | 120 cm |
| Package 3 Length | 80 cm |
| Package 3 Weight | 229.568 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9D61816 | iC60N – earth leakage circuit breaker – 1P + N – C curve – 16 A – 30 mA – 240 V
Schneider A9D11825 | iC60H – earth leakage circuit breaker – 1P + N – C curve – 25 A – 30 mA – 240 V
-
0
Reviews
There are no reviews yet.