Schneider CAD50BD | Control relay, TeSys Deca, 5NO, 0 to 690V, 24VDC standard coil, screw clamp
CAD50BD | Control relay, TeSys Deca, 5NO, 0 to 690V, 24VDC standard coil, screw clamp
Description
Schneider CAD50BD| Control relay, TeSys Deca, 5NO, 0 to 690V, 24VDC standard coil, screw clamp
it is a versatile and reliable industrial control relay developed by Schneider Electric, a global leader in energy management and automation. With its compact design, robust construction, and advanced features, the CAD50BD offers exceptional performance across various industrial applications.
What is Schneider CAD50BD?
it is a control relay designed to provide efficient control and protection in industrial automation systems. It is specifically engineered to meet the demanding requirements of modern industrial environments, offering a blend of durability, functionality, and ease of use.
Key Features
Compact Design
it boasts a compact design, making it suitable for installations where space is limited. Its small footprint allows for flexible mounting options, enabling integration into diverse industrial setups without occupying excessive space.
Robust Construction
Constructed with high-quality materials,it is built to withstand harsh industrial conditions. Its rugged construction ensures reliability and longevity, providing uninterrupted operation even in challenging environments characterized by dust, moisture, and temperature variations.
Versatile Compatibility
Equipped with versatile connectivity options,it is compatible with a wide range of control systems and devices. Whether interfacing with PLCs (Programmable Logic Controllers), motor starters, or other control components, this relay offers seamless integration for enhanced system performance.
Applications
it finds application across various industrial sectors, including manufacturing, process control, and infrastructure. Its versatility makes it suitable for controlling motors, pumps, conveyors, and other essential machinery, facilitating efficient automation and monitoring processes.
Installation and Setup
Installing it is straightforward, thanks to its user-friendly design and comprehensive installation manual. The relay can be easily mounted on DIN rails or directly onto panels, allowing for quick and hassle-free setup in industrial environments.
Operating Principle
At the core of its operation, it utilizes advanced relay technology to control electrical circuits based on predefined logic and input signals. By effectively managing the flow of current, it ensures precise control and protection of connected equipment, enhancing overall system reliability.
Advantages of Using
The adoption of it offers several advantages to industrial users, including:
- Enhanced reliability and durability
- Simplified installation and setup
- Compatibility with diverse control systems
- Improved efficiency and productivity
- Comprehensive protection features for connected equipment
Potential Limitations
While it offers numerous benefits, it’s essential to consider potential limitations such as:
- Compatibility issues with specific control systems
- Limited availability of technical support in certain regions
- Cost implications compared to alternative solutions
Comparison with Similar Products
In comparison to similar industrial control relays available in the market, the Schneider CAD50BD stands out due to its:
- Compact design
- Robust construction
- Versatile compatibility
- Comprehensive feature set
- Reputation for reliability and performance
Maintenance and Troubleshooting
Maintaining it involves periodic inspections and testing to ensure proper functionality. In case of any issues, troubleshooting guides and technical support from Schneider Electric can assist users in diagnosing and resolving problems effectively.
Cost Considerations
When evaluating the cost of implementing it in industrial systems, factors such as initial investment, maintenance expenses, and long-term reliability should be taken into account. While the upfront cost may vary depending on specific requirements, the overall value offered by the CAD50BD justifies its investment.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | TeSys TeSys Deca |
|---|---|
| Product name | TeSys CAD |
| Product or component type | Control relay |
| Device short name | CAD |
| Contactor application | Control circuit |
| Utilisation category | AC-14 DC-13 AC-15 |
|---|---|
| Pole contact composition | 5 NO |
| [Ue] rated operational voltage | <= 690 V AC 25...400 Hz |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 24 V DC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 250 A DC conforming to IEC 60947-5-1 |
| [Icw] rated short-time withstand current | 100 A - 1 s 120 A - 500 ms 140 A - 100 ms |
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 600 V UL certified 600 V CSA certified 690 V conforming to IEC 60947-5-1 |
| Mounting support | Rail Plate |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
| Tightening torque | 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC 0.7...1.25 Uc (-40…60 °C):operational DC 1...1.25 Uc (60…70 °C):operational DC |
| Operating time | 53...72 ms coil energisation and NO closing 16...24 ms coil de-energisation and NO opening |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 180 cyc/mn |
| Time constant | 28 ms |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Minimum switching voltage | 17 V |
| Minimum switching current | 5 mA |
| Non-overlap time | 1.5 ms on energisation between NC and NO contact 1.5 ms on de-energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm |
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 93 mm |
| Net weight | 0.58 kg |
| Standards | EN/IEC 60947-5-1 GB/T 14048.5 UL 60947-5-1 CSA C22.2 No 60947-5-1 JIS C8201-5-1 |
|---|---|
| Product certifications | CB CCC UL CSA EAC CE UKCA |
| IP degree of protection | IP2X front face conforming to VDE 0106 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -40…60 °C 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 11.200 cm |
| Package 1 Weight | 526.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.220 kg |
| Warranty | 18 months |
|---|