Technical Specifications:

  1. Number of I/O Points: The TM221ME32TK features 32 I/O points. These include both digital inputs and digital outputs, providing flexibility for controlling sensors, actuators, and other industrial devices.

  2. Input/Output Type:

    • Inputs: The controller supports digital inputs for connecting devices that send binary signals (on/off), such as switches, sensors, and other simple devices.

    • Outputs: The digital outputs are transistor PNP outputs, which are commonly used in control circuits that require switching or driving external devices like motors, lights, and relays. The transistor PNP outputs provide better efficiency and faster switching compared to traditional relay outputs.

  3. Ethernet Connectivity: The TM221ME32TK comes with built-in Ethernet connectivity, allowing it to communicate with other devices in a network or be integrated into larger control systems. The Ethernet port also enables remote programming, monitoring, and diagnostics, offering significant flexibility in system design and maintenance.

  4. Processing Power: The M221 PLC has a powerful processing capability, enabling it to handle complex control tasks in real-time. It is equipped with a 32-bit processor for efficient data processing and quick response times in industrial automation systems.

  5. Programming: The controller can be programmed using SoMachine Basic software, which is user-friendly and designed for ease of use. It supports IEC 61131-3 programming languages, including Ladder Logic, Function Block Diagram, and Structured Text.

  6. Compact and Modular Design: The TM221ME32TK is designed for applications with space constraints. Its compact size makes it easy to integrate into control panels, machine control setups, or distributed automation systems.

  7. Power Supply: The module is powered by a 24V DC supply, which is commonly used in industrial control systems and ensures compatibility with most industrial equipment.

Features:

  1. Ethernet Communication: The built-in Ethernet port allows the PLC to be part of a larger network, enabling communication with other PLCs, HMIs (Human-Machine Interfaces), SCADA systems, or enterprise-level systems.

  2. Transistor PNP Outputs: The PNP transistor outputs provide fast switching, reduced power loss, and enhanced reliability compared to relay-based outputs, making them suitable for applications that require precise control over devices.

  3. User-Friendly Programming: The SoMachine Basic programming environment simplifies the programming process, making it accessible even for users with limited experience in PLC programming.

  4. Compact and Space-Saving: The compact form factor of the TM221ME32TK makes it ideal for applications where space is limited, such as control cabinets or small machine control systems.

  5. Flexible I/O Options: With 32 I/O points, this controller can be used in a wide range of industrial applications. It offers sufficient I/O for small to medium-scale control systems while still maintaining a small footprint.

  6. Real-Time Control: The M221 PLC is capable of real-time control, which is crucial for applications where precise timing and response are required, such as conveyor systems, packaging machines, or automated assembly lines.

  7. Connectivity for Remote Access: Ethernet support allows for remote programming, monitoring, and diagnostics, helping reduce downtime and improve system reliability.

Applications:

The Schneider TM221ME32TK is ideal for a variety of industrial and commercial automation applications, such as:

  • Machine Control: For controlling small to medium-sized machines in packaging, assembly, or processing lines.

  • Process Control: Used in systems requiring precise control and monitoring of industrial processes, such as HVAC systems, water treatment, or conveyor belts.

  • Building Automation: Can be used to manage lighting, HVAC, and security systems in commercial or residential buildings.

  • IoT and Remote Monitoring: Due to its Ethernet connectivity, it is well-suited for Internet of Things (IoT) applications, allowing for remote monitoring and control via the cloud.

Additional information

brands

Schneider Electric

Specifications

Main
Range of product Modicon M221
Product or component type Logic controller
[Us] rated supply voltage 24 V DC
Discrete input number 16, discrete input 4 fast input conforming to IEC 61131-2 Type 1
Analogue input number 2 at 0...10 V
Discrete output type Transistor
Discrete output number 16 transistor 2 fast output
Discrete output voltage 24 V DC
Discrete output current 0.1 A
Complementary
Discrete I/O number 32
Maximum number of I/O expansion module 7 (local I/O-Architecture) 14 (remote I/O-Architecture)
Supply voltage limits 20.4…28.8 V
Inrush current 35 A
Maximum power consumption in W 23.2 W at 24 V (with max number of I/O expansion module) 4.2 W at 24 V (without I/O expansion module)
Power supply output current 0.52 A 5 V for expansion bus 0.48 A 24 V for expansion bus
Discrete input logic Sink or source (positive/negative)
Discrete input voltage 24 V
Discrete input voltage type DC
Analogue input resolution 10 bits
LSB value 10 mV
Conversion time 1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs +/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed >= 15 V for input
Voltage state 0 guaranteed <= 5 V for input
Discrete input current 7 mA for discrete input 5 mA for fast input
Input impedance 100 kOhm for analog input 3.4 kOhm for input 4.9 kOhm for fast input
Response time 35 µs turn-off, I2...I5 terminal(s) for input 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input 5 µs turn-on, turn-off, Q0...Q1 terminal(s) for output 50 µs turn-on, turn-off, Q2...Q3 terminal(s) for output 300 µs turn-on, turn-off, other terminals terminal(s) for output
Configurable filtering time 0 ms for input 3 ms for input 12 ms for input
Discrete output logic Positive logic (source)
Maximum current per output common 1.6 A
Output frequency 100 kHz for fast output (PWM/PLS mode) at Q0...Q1 5 kHz for output at Q2...Q3 0.1 kHz for output at Q4...Q15
Absolute accuracy error +/- 1 % of full scale for analog input
Maximum leakage current 0.1 mA for transistor output
Maximum voltage drop <1 V
Mechanical durability 20000000 cycles for transistor output
Maximum tungsten load <2.4 W for output and fast output
Protection type Short-circuit and overload protection with automatic reset Short-circuit protection on output Overload and short-circuit protection at 1 A
Reset time 1 s automatic reset
Memory capacity 256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM
Data backed up 256 kB built-in flash memory for backup of application and data
Data storage equipment 2 GB SD card (optional)
Battery type BR2032 or CR2032X lithium non-rechargeable
Backup time 1 year at 25 °C (by interruption of power supply)
Execution time for 1 KInstruction 0.3 ms for event and periodic task 0.7 ms for other instruction
Execution time per instruction 0.2 µs Boolean
Exct time for event task 60 µs response time
Application structure 1 cyclic auxiliary task 1 configurable freewheeling/cyclic master task 8 interrupt tasks
Maximum size of object areas 255 %C counters 512 %M memory bits 512 %KW constant words 8000 %MW memory words 255 %TM timers
Realtime clock With
Clock drift <= 30 s/month at 25 °C
Regulation loop Adjustable PID regulator up to 14 simultaneous loops
Positioning functions Position PTO 2 axe(s)pulse/direction mode (100 kHz) Position PTO 1 axe(s)CW/CCW mode (100 kHz)
Function available Frequency generator PWM PLS
Counting input number 4 fast input (HSC mode) at 100 kHz 32 bits
counter function Single phase A/B Pulse/direction
Integrated connection type USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector
Supply (serial 1)serial link supply: 5 V, <200 mA
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB
Communication port protocol USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet
Port Ethernet 10BASE-T/100BASE-TX 1 port with 100 m copper cable
communication service Modbus TCP slave device Modbus TCP server Modbus TCP client Ethernet/IP adapter DHCP client
Local signalling 1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status)
Electrical connection terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal HE-10 connector, 20 terminal(s) for inputs HE-10 connector, 20 terminal(s) for outputs
Maximum cable distance between devices Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input Shielded cable: <3 m for fast output
Insulation Between input and internal logic at 500 V AC Between fast input and internal logic at 500 V AC Non-insulated between inputs Between output and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs
Marking CE
Mounting support Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 70 mm
Net weight 0.27 kg
Environment
Standards IEC 61131-2 UL 508 CAN/CSA C22.2 No. 213 IACS E10 ANSI/ISA 12-12-01
Product certifications ABS DNV-GL LR cULus EAC RCM CE UKCA cULus HazLoc
Environmental characteristic Ordinary and hazardous location
Resistance to electrostatic discharge 8 kV in air conforming to IEC 61000-4-2 4 kV on contact conforming to IEC 61000-4-2
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
Resistance to magnetic fields 30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance to fast transients 2 kV (power lines) conforming to IEC 61000-4-4 2 kV (relay output) conforming to IEC 61000-4-4 1 kV (I/O) conforming to IEC 61000-4-4 1 kV (Ethernet line) conforming to IEC 61000-4-4 1 kV (serial link) conforming to IEC 61000-4-4
Surge withstand 2 kV power lines (AC) common mode conforming to IEC 61000-4-5 2 kV relay output common mode conforming to IEC 61000-4-5 1 kV I/O common mode conforming to IEC 61000-4-5 1 kV shielded cable common mode conforming to IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to IEC 61000-4-5 1 kV relay output differential mode conforming to IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to IEC 61000-4-5
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to IEC 61000-4-6 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to IEC 55011 Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to IEC 55011
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10…55 °C (horizontal installation) -10…35 °C (vertical installation)
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
IP degree of protection IP20 with protective cover in place
Pollution degree <= 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting
Shock resistance 147 m/s² for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 10.8 cm
Package 1 Width 10.0 cm
Package 1 Length 12.6 cm
Package 1 Weight 420.0 g
Unit Type of Package 2 S04
Number of Units in Package 2 24
Package 2 Height 30 cm
Package 2 Width 40 cm
Package 2 Length 60 cm
Package 2 Weight 10.678 kg
Unit Type of Package 3 P12
Number of Units in Package 3 288
Package 3 Height 105.0 cm
Package 3 Width 120.0 cm
Package 3 Length 80.0 cm
Package 3 Weight 140 kg

Main Document

Main Document

Data Sheet : Download

Main Document

Data Sheet : Download

Reviews (0)

Be the first to review “Schneider TM221ME32TK | controller M221 32 IO transistor PNP Ethernet”

Your email address will not be published. Required fields are marked *

Reviews

There are no reviews yet.

Product was successfully added to your cart!

Select at least 2 products
to compare