Schneider A9F94410 | Miniature circuit-breaker, Acti9 iC60L, 4P, 10 A, C curve, 15000 A (IEC 60898-1), 25 kA (IEC 60947-2)
Schneider A9F94410 | Miniature circuit-breaker, Acti9 iC60L, 4P, 10 A, C curve, 15000 A (IEC 60898-1), 25 kA (IEC 60947-2)
Description
Schneider A9F94410 | Miniature circuit-breaker, Acti9 iC60L, 4P, 10 A, C curve, 15000 A (IEC 60898-1), 25 kA (IEC 60947-2)
Specifications Schneider A9F94410
-
Model: A9F94410
-
Type: Miniature Circuit-Breaker (MCB)
-
Series: Acti9 iC60L
-
Poles: 4P (Four Poles)
-
Rated Current: 10 Amps
-
Curve Type: C Curve (for moderate inrush current)
-
Breaking Capacity:
-
15 kA (at 415 VAC, IEC 60898-1)
-
25 kA (at 415 VAC, IEC 60947-2)
-
-
Standards Compliance:
-
IEC 60898-1 (Standard for residential and light commercial electrical installations)
-
IEC 60947-2 (Standard for low-voltage circuit breakers)
-
-
Voltage: Suitable for 230/415 VAC systems
Features Schneider A9F94410
-
High Breaking Capacity:
-
The 15 kA breaking capacity (at 415 VAC) according to IEC 60898-1 and the 25 kA capacity according to IEC 60947-2 ensures that the Acti9 iC60L circuit breaker can handle high fault currents, providing effective protection against both overloads and short circuits in industrial and residential installations.
-
-
C Curve:
-
The C curve type means the circuit breaker trips between 5 to 10 times the rated current. This is ideal for protecting circuits that have moderate inrush currents, such as lighting circuits, heating systems, and motors with typical startup characteristics.
-
-
Four-Pole Design (4P):
-
The 4P (four-pole) configuration is perfect for protecting three-phase systems with a neutral, typically found in complex or industrial electrical installations. It ensures balanced protection across all phases, including the neutral wire.
-
-
Thermal-Magnetic Trip Mechanism:
-
The thermal-magnetic trip unit provides both overload protection (thermal) and short-circuit protection (magnetic), making this breaker versatile and highly effective for both gradual overloads and immediate fault conditions.
-
-
Compact and Space-Saving Design:
-
The Acti9 iC60L is designed to be compact, which allows it to be easily installed in standard distribution boards and electrical panels, saving valuable space while still offering high performance and protection.
-
-
Long Life and Reliability:
-
Schneider’s Acti9 range is designed for long-term durability, with the iC60L providing reliable operation in both normal and fault conditions, ensuring continued protection over an extended service life.
-
-
Standards Compliance:
-
The breaker complies with both IEC 60898-1 for residential and light commercial applications and IEC 60947-2 for industrial installations, ensuring high standards of performance and safety.
-
Applications:
-
Industrial Electrical Systems: Ideal for use in three-phase systems with a neutral in industrial settings, where high reliability and protection are needed for critical machinery and equipment.
-
Commercial Installations: Suitable for offices, retail spaces, and commercial buildings with complex electrical distribution systems requiring four-pole protection.
-
Residential Installations: Can be used in residential buildings, especially in systems where four-pole protection is required, such as certain types of air conditioning units, heating systems, or motor-driven appliances.
-
Motor Protection: Offers protection for motors and other equipment that may have moderate inrush currents during startup, ensuring protection without unnecessary tripping.
-
Power Distribution Panels: Commonly used in low-voltage electrical panels and distribution boards to protect circuits from short circuits and overloads.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Device application | Distribution |
|---|---|
| Range | Acti9 |
| Product name | Acti9 iC60 |
| Product or component type | Miniature circuit-breaker |
| Device short name | iC60L |
| poles description | 4P |
| Number of protected poles | 4 |
| [In] rated current | 10 A |
| network type | AC DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at <= 250 V DC conforming to EN/IEC 60947-2 |
| Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 |
| Standards | EN 60898-1 EN 60947-2 IEC 60898-1 IEC 60947-2 |
| Network frequency | 50/60 Hz |
|---|---|
| Magnetic tripping limit | 8 x In +/- 20 % |
| [Ics] rated service breaking capacity | 12.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 12.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 10 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 25 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 25 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 35 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 35 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 7500 A 50 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 7500 A 50 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 20 kA 100 % conforming to EN 60947-2 - 180...250 V DC 20 kA 100 % conforming to IEC 60947-2 - 180...250 V DC |
| Limitation class | 3 conforming to EN 60898-1 3 conforming to IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| Control type | Toggle |
| local signalling | Trip indicator |
| Mounting mode | Fixed |
| Mounting support | DIN rail |
| Comb busbar and distribution block compatibility | Top or bottom: YES |
| 9 mm pitches | 8 |
| Height | 85 mm |
| Width | 72 mm |
| Depth | 78.5 mm |
| Net weight | 0.5 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Connections - terminals | Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible |
| Wire stripping length | 14 mm for top or bottom connection |
| Tightening torque | 2 N.m top or bottom |
| Earth-leakage protection | Separate block |
| IP degree of protection | IP20 conforming to IEC 60529 IP20 conforming to EN 60529 |
|---|---|
| Pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative humidity | 95 % at 55 °C |
| Operating altitude | 0...2000 m |
| Ambient air temperature for operation | -35…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.500 cm |
| Package 1 Width | 7.200 cm |
| Package 1 Length | 9.400 cm |
| Package 1 Weight | 439.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 3 |
| Package 2 Height | 8.000 cm |
| Package 2 Width | 9.800 cm |
| Package 2 Length | 22.500 cm |
| Package 2 Weight | 1.379 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 33 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 15.670 kg |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61521 | miniature circuit breaker – C60H – 2 poles – 1 A – C curve
-
0
Schneider A9N18569 | Vigi C120 – earth leakage add-on block – 4P – 30 mA – class AC
-