Schneider RM17TE00 | Multifunction control relay RM17-TE – range 183..528 V AC
Description
Schneider RM17TE00 | Multifunction control relay RM17-TE – range 183..528 V AC
Schneider RM17TE00 | Multifunction Control Relay RM17-TE – Range 183..528 V AC Description
Introduction Schneider RM17TE00 is a multifunction control relay that plays a crucial role in electrical systems. It offers a wide range of functionalities and is designed to operate within a voltage range of 183 to 528 volts AC. Understanding its features, applications, installation process, and maintenance tips is essential for anyone working with electrical equipment.
Features The Schneider RM17TE00 is known for its versatile features. It operates seamlessly within the specified voltage range, making it suitable for various industrial and commercial applications. Its functionality includes but is not limited to voltage monitoring, phase control, and fault detection. These features ensure smooth operations and enhance safety in electrical systems.
Applications This control relay finds extensive use in industrial settings such as manufacturing plants, power distribution centers, and automation systems. Its ability to monitor voltage fluctuations and control electrical parameters makes it indispensable in maintaining stable operations. Additionally, commercial applications like building management systems and HVAC (Heating, Ventilation, and Air Conditioning) units benefit from its reliability and precision.
Installation Installing the Schneider RM17TE00 requires careful attention to detail. Begin by identifying the appropriate mounting location and ensuring the power source is disconnected. Follow the provided user manual for a step-by-step guide, including wiring instructions and safety precautions. Proper installation ensures optimal performance and prevents electrical hazards.
Maintenance To prolong the lifespan of the RM17TE00 relay, regular maintenance is crucial. Inspect for any signs of wear, check connections for tightness, and clean components as necessary. Conduct periodic testing to verify its functionality and address any issues promptly. Routine maintenance not only prevents downtime but also ensures safety and efficiency.
Comparison Comparing the Schneider RM17TE00 with similar control relays reveals its unique advantages. Its wide voltage range sets it apart, accommodating diverse electrical setups. The reliability and precision of its functions make it a preferred choice among professionals seeking robust control solutions for their systems.
User Reviews Real user experiences provide valuable insights into the performance of the Schneider RM17TE00. Users commend its durability, accurate monitoring capabilities, and ease of installation. Positive feedback often highlights its contribution to maintaining stable electrical operations and preventing potential breakdowns.
Conclusion In conclusion, the Schneider RM17TE00 multifunction control relay is a reliable and efficient component for managing electrical systems. Its versatile features, wide voltage range, and user-friendly design make it a valuable asset in both industrial and commercial environments. Proper installation, maintenance, and adherence to safety guidelines ensure optimal performance and longevity.
FAQs
- What is the voltage range of the Schneider RM17TE00?
- Can the relay be used in commercial HVAC systems?
- How often should maintenance checks be performed on the RM17TE00 relay?
- Is professional installation recommended for this control relay?
- Are there any safety precautions to consider when working with the Schneider RM17TE00?
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Harmony Control Relays |
|---|---|
| Relay type | Multifunction control relay |
| Product or component type | 3-phase control relay |
| Product specific application | For 3-phase supply |
| Relay name | RM17TE |
| Relay monitored parameters | Undervoltage and overvoltage in window mode Asymmetry Phase sequence Phase failure detection |
| time delay | Adjustable 0.1...10 s, +/- 10 % of the full scale value Tt- time delay upon fault |
| Output contacts | 1 C/O |
| Nominal output current | 5 A |
| Contacts type and composition | 1 C/O |
| [Uc] control circuit voltage | 208...480 V |
| [Un] rated nominal voltage | , self-powered |
|---|---|
| Supply voltage limits | 183…528 V AC |
| Reset time | 1500 ms time delay |
| Maximum switching voltage | 250 V AC 250 V DC |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum switching current | 5 A AC 5 A DC |
| Control circuit voltage limits | - 12 % + 10 % Un |
| Power consumption in VA | 0…22 VA at 400 V AC 50 Hz |
| Control circuit frequency | 50...60 Hz +/- 10 % |
| Measurement voltage limits | 183…528 V AC |
| Hysteresis | 2 % |
| delay at power up | 650 ms |
| Maximum measuring cycle | 150 ms measurement cycle as true rms value |
| Threshold adjustment voltage | 2...20 % of Un selected -2...-17 % in the range 220 V AC +2...+10 % in the range 480 V AC -2...-12 % in the range 208 V AC |
| Voltage range | 208...480 V phase to phase |
| Adjustment of asymmetry threshold | 5...15 % of Un selected |
| Repeat accuracy | 0.5 % for input and measurement circuit 3 % for time delay |
| Measurement error | < 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation |
| Phase failure sensitivity | 0.7 Un |
| Response time | < 200 ms (in the event of a fault) |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Supply frequency | 50/60 Hz +/- 10 % |
| Operating position | Any position without derating |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Local signalling | LED (green) for power ON LED (yellow) for relay ON |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Operating rate | <= 360 operations/hour full load |
| Utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
| Safety reliability data | MTTFd = 502.2 years B10d = 470000 |
| Width | 17.5 mm |
| Net weight | 0.13 kg |
| Control type | Without test button |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Immunity for industrial environments conforming to IEC 61000-6-2 |
|---|---|
| Standards | IEC 60255-1 |
| Product certifications | GOST C-Tick CSA UL GL |
| Marking | CE |
| Directives | 89/336/EEC - electromagnetic compatibility 73/23/EEC - low voltage directive |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Overvoltage category | III conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1 |
| Non-dissipating shock wave | 4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5 |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 2.7 cm |
| Package 1 Width | 7.7 cm |
| Package 1 Length | 9.6 cm |
| Package 1 Weight | 92.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 48 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 4.936 kg |
| Warranty | 18 months |
|---|