Schneider ATV12HU22M2 Altivar |variable speed drive ATV12 – 2.2kW – 3hp – 200..240V – 1ph – with heat sink
Schneider ATV12HU22M2 Altivar
Description
Schneider ATV12HU22M2 Altivar
Schneider ATV12HU22M2 Altivar, a name synonymous with reliability and efficiency in the industrial sector, holds immense significance in powering various applications with precision and control. In this article, we delve into the intricacies of Schneider ATV12HU22M2 Altivar, exploring its features, installation process, maintenance tips, troubleshooting techniques, and its pivotal role in shaping the future of industrial automation.
Understanding the Basics of Schneider ATV12HU22M2 Altivar
it stands as a prominent variable speed drive designed to regulate the speed and torque of electric motors in industrial applications. Its compact design and advanced functionalities make it a preferred choice for diverse industries ranging from manufacturing to energy.
What is Schneider ATV12HU22M2 Altivar?
it boasts a plethora of features tailored to meet the demands of modern industrial automation. With a voltage rating of 200-240V and a power rating of 0.75 kW, this variable speed drive offers precise control over motor speed, ensuring optimal performance and energy efficiency.
The Importance of Schneider ATV12HU22M2 Altivar in Industrial Applications
In the competitive landscape of industrial automation, efficiency and reliability are paramount. it addresses these requirements by providing seamless control over motor speed, thereby enhancing productivity and minimizing downtime.
Installation and Setup Guide for Schneider ATV12HU22M2 Altivar
Installing it is a straightforward process, provided you follow the manufacturer’s guidelines diligently. Begin by ensuring all power sources are disconnected, then proceed with mounting the drive securely in a well-ventilated area. Connect the necessary cables as per the wiring diagram provided in the user manual, and power up the drive after verifying all connections.
Tips for Optimal Performance and Maintenance
To prolong the lifespan of your it, regular maintenance is essential. Keep the drive clean and free from dust accumulation, and inspect it periodically for any signs of wear or damage. Additionally, ensure proper ventilation to prevent overheating, and adhere to recommended operating conditions for optimal performance.
Troubleshooting Common Issues with Schneider ATV12HU22M2 Altivar
Despite its robust design, it may encounter issues during operation. Common problems include overvoltage, undervoltage, and motor overheating. Refer to the user manual for troubleshooting steps, and if the issue persists, consult with a qualified technician for assistance.
The Future of Schneider ATV12HU22M2 Altivar: Innovations and Advancements
As technology evolves, so does it. With ongoing research and development, we can expect to see advancements in efficiency, connectivity, and integration with emerging technologies such as IoT and cloud computing. These innovations will further solidify its position as a cornerstone of industrial automation.
Conclusion
it represents a pinnacle of innovation in industrial automation, offering unparalleled control and efficiency. By understanding its features, installation process, maintenance requirements, and troubleshooting techniques, businesses can harness its full potential to drive productivity and stay ahead in today’s competitive market.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Altivar 12 |
|---|---|
| Product or component type | Variable speed drive |
| Product specific application | Simple machine |
| Mounting mode | Cabinet mount |
| communication port protocol | Modbus |
| Supply frequency | 50/60 Hz +/- 5 % |
| [Us] rated supply voltage | 200...240 V - 15...10 % |
| Nominal output current | 10 A |
| Motor power hp | 3 hp |
| Motor power kW | 2.2 kW |
| Motor power hp | 3 hp |
| EMC filter | Integrated |
| IP degree of protection | IP20 |
| Discrete input number | 4 |
|---|---|
| Discrete output number | 2 |
| analogue input number | 1 |
| analogue output number | 1 |
| Relay output number | 1 |
| Physical interface | 2-wire RS 485 |
| Connector type | 1 RJ45 |
| Continuous output current | 10 A at 4 kHz |
| Method of access | Server Modbus serial |
| Speed drive output frequency | 0.5…400 Hz |
| Speed range | 1…20 |
| Sampling duration | 20 ms, tolerance +/- 1 ms for logic input 10 ms for analogue input |
| Linearity error | +/- 0.3 % of maximum value for analogue input |
| Frequency resolution | Analog input: converter A/D, 10 bits Display unit: 0.1 Hz |
| Time constant | 20 ms +/- 1 ms for reference change |
| Transmission rate | 9.6 kbit/s 19.2 kbit/s 38.4 kbit/s |
| Transmission frame | RTU |
| Number of addresses | 1…247 |
| Data format | 8 bits, configurable odd, even or no parity |
| Communication service | Read holding registers (03) 29 words Write single register (06) 29 words Write multiple registers (16) 27 words Read/write multiple registers (23) 4/4 words Read device identification (43) |
| Type of polarization | No impedance |
| 4 quadrant operation possible | False |
| Asynchronous motor control profile | Sensorless flux vector control Quadratic voltage/frequency ratio Voltage/frequency ratio (V/f) |
| Maximum output frequency | 4 kHz |
| Transient overtorque | 150…170 % of nominal motor torque depending on drive rating and type of motor |
| Acceleration and deceleration ramps | Linear from 0 to 999.9 s U S |
| Motor slip compensation | Adjustable Preset in factory |
| Switching frequency | 2...16 kHz adjustable 4...16 kHz with derating factor |
| Nominal switching frequency | 4 kHz |
| Braking to standstill | By DC injection |
| Brake chopper integrated | False |
| Line current | 24.0 A at 100 V (heavy duty) 20.2 A at 120 V (heavy duty) |
| Maximum input current | 20.2 A |
| Maximum output voltage | 240 V |
| Apparent power | 4.8 kVA at 240 V (heavy duty) |
| Maximum transient current | 15.0 A during 60 s (heavy duty) 16.5 A during 2 s (heavy duty) |
| Network frequency | 50...60 Hz |
| Relative symmetric network frequency tolerance | 5 % |
| Prospective line Isc | 1 kA |
| Base load current at high overload | 10.0 A |
| Power dissipation in W | Forced cooling: 93.0 W |
| With safety function Safely Limited Speed (SLS) | False |
| With safety function Safe brake management (SBC/SBT) | False |
| With safety function Safe Operating Stop (SOS) | False |
| With safety function Safe Position (SP) | False |
| With safety function Safe programmable logic | False |
| With safety function Safe Speed Monitor (SSM) | False |
| With safety function Safe Stop 1 (SS1) | False |
| With sft fct Safe Stop 2 (SS2) | False |
| With safety function Safe torque off (STO) | False |
| With safety function Safely Limited Position (SLP) | False |
| With safety function Safe Direction (SDI) | False |
| Protection type | Line supply overvoltage Line supply undervoltage Overcurrent between output phases and earth Overheating protection Short-circuit between motor phases Against input phase loss in three-phase Thermal motor protection via the drive by continuous calculation of I²t |
| tightening torque | 1.2 N.m |
| insulation | Electrical between power and control |
| Quantity per set | Set of 1 |
| Width | 105 mm |
| height | 142 mm |
| Depth | 156.2 mm |
| Net weight | 1.4 kg |
| Operating altitude | > 1000...2000 m with current derating 1 % per 100 m <= 1000 m without derating |
|---|---|
| Operating position | Vertical +/- 10 degree |
| product certifications | NOM CSA C-Tick UL GOST RCM KC |
| Marking | CE |
| Standards | UL 508C UL 618000-5-1 EN/IEC 61800-5-1 EN/IEC 61800-3 |
| Assembly style | With heat sink |
| Electromagnetic compatibility | Electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2 Immunity to conducted disturbances level 3 conforming to EN/IEC 61000-4-6 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3 Surge immunity test level 3 conforming to EN/IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11 |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3 |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Volume of cooling air | 16 m3/h |
| Overvoltage category | Class III |
| Regulation loop | Adjustable PID regulator |
| Electromagnetic emission | Radiated emissions environment 1 category C2 conforming to EN/IEC 61800-3 2...16 kHz shielded motor cable Conducted emissions with integrated EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <5 m Conducted emissions with additional EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m Conducted emissions with additional EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m Conducted emissions with additional EMC filter environment 2 category C3 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <50 m Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...16 kHz shielded motor cable <5 m Conducted emissions with integrated EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 2, 4, 8, 12 and 16 kHz shielded motor cable <10 m |
| Vibration resistance | 1 gn (f = 13…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f = 3…13 Hz) - drive unmounted on symmetrical DIN rail - conforming to EN/IEC 60068-2-6 |
| Shock resistance | 15 gn conforming to EN/IEC 60068-2-27 for 11 ms |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3 |
| Noise level | 45 dB |
| Pollution degree | 2 |
| Ambient air transport temperature | -25…70 °C |
| Ambient air temperature for operation | -10…50 °C without derating 50…60 °C with current derating 2.2 % per °C |
| Ambient air temperature for storage | -25…70 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 20.000 cm |
| Package 1 Width | 18.000 cm |
| Package 1 Length | 20.000 cm |
| Package 1 Weight | 1.753 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 65.950 kg |
| Warranty | 18 months |
|---|