Schneider GV2P08 | Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, screw clamp terminals
Schneider GV2P08 | Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, screw clamp terminals
Description
Schneider GV2P08 | Motor circuit breaker, TeSys GV2, 3P, 2.5-4 A, thermal magnetic, screw clamp terminals
Schneider GV2P08 Description
Introduction
Schneider Electric is a globally recognized leader in energy management and automation solutions, offering a wide range of products designed to improve efficiency, safety, and reliability in electrical systems. Among these products, motor protection circuit breakers play a crucial role in safeguarding motors against potential electrical faults. The Schneider GV2P08 is a notable example, providing robust protection for a variety of motor applications.
Overview of the Schneider GV2P08
The Schneider GV2P08 is a motor protection circuit breaker designed to provide reliable protection for motors in industrial and commercial settings. It combines thermal and magnetic protection to safeguard motors from overloads, short circuits, and phase loss.
Basic Description
The GV2P08 is part of Schneider Electric’s TeSys GV2 range, known for its compact design and high performance. This particular model is rated for 2.5-4 A and is designed to protect motors with a nominal power of up to 1.5 kW (at 400V AC).
Key Features
- Thermal-Magnetic Protection: Provides comprehensive protection against overloads and short circuits.
- Compact Design: Saves space in control panels.
- Adjustable Settings: Allows for fine-tuning to match motor requirements.
- High Breaking Capacity: Ensures safe disconnection of high fault currents.
- Easy Installation: Designed for quick and straightforward mounting.
Technical Specifications
Electrical Specifications
- Rated Operational Voltage: 690V AC
- Rated Current: 2.5-4 A
- Breaking Capacity: 100 kA at 400V AC
- Thermal Adjustment Range: 2.5-4 A
Mechanical Specifications
- Dimensions: 81mm x 45mm x 73.5mm
- Weight: 0.32 kg
- Mounting: DIN rail or screw fixing
Design and Build Quality
The Schneider GV2P08 is designed with durability and reliability in mind, ensuring long-term performance in demanding environments.
Materials Used
- Housing: Made of robust, fire-resistant plastic for enhanced safety.
- Internal Components: Utilizes high-quality metals like copper and silver alloys for excellent conductivity and durability.
- Terminals: Corrosion-resistant terminals to ensure reliable connections over time.
Construction Details
The GV2P08 is built to withstand harsh industrial conditions, with rigorous quality control processes ensuring each unit meets Schneider Electric’s high standards for performance and safety.
Installation Guidelines
Proper installation is key to ensuring the Schneider GV2P08 operates effectively and safely.
Pre-Installation Checklist
- Ensure the power supply is turned off before starting.
- Verify compatibility with the motor and control panel.
- Gather necessary tools and safety equipment.
Step-by-Step Installation Process
- Power Down: Turn off the main power supply to avoid electrical hazards.
- Mount the Breaker: Secure the GV2P08 to a DIN rail or directly to the panel using screws.
- Connect Wiring: Attach the input and output wires to the appropriate terminals, ensuring secure connections.
- Set Thermal Adjustment: Adjust the thermal setting to match the motor’s rated current.
- Test the Circuit: Restore power and test the breaker to ensure it operates correctly.
- Finalize Installation: Organize and secure any loose wires and close the panel.
Applications and Usage
The Schneider GV2P08 is versatile and suitable for various applications.
Industrial Applications
Ideal for protecting motors in industrial machinery, conveyor systems, and production lines.
Commercial Applications
Provides reliable protection for HVAC systems, pumps, and other motor-driven equipment in commercial buildings.
Residential Applications
While primarily designed for industrial and commercial use, the GV2P08 can also be used in residential settings for specific motor protection needs.
Compatibility and Integration
The Schneider GV2P08 is designed to integrate seamlessly with a variety of electrical systems and devices.
Compatible Systems and Devices
- Motor Starters: Compatible with a range of motor starters for easy integration.
- Control Panels: Fits standard industrial and commercial control panels.
- Automation Systems: Can be integrated with building automation systems for enhanced control and monitoring.
Integration Tips
- Ensure secure connections to prevent potential faults.
- Regularly inspect and maintain the breaker to ensure ongoing compatibility and performance.
Performance and Efficiency
The Schneider GV2P08 is engineered to deliver high performance and energy efficiency.
Performance Metrics
- Response Time: Quick tripping response to overloads and short circuits, ensuring motor protection.
- Reliability: Consistent protection with minimal downtime.
Energy Efficiency Considerations
The design minimizes energy loss, contributing to the overall efficiency of the electrical system.
Safety Features
Safety is a paramount concern for Schneider Electric, and the GV2P08 includes several built-in safety features.
Compliance with Safety Standards
The GV2P08 complies with international safety standards, including IEC/EN 60947-4-1, ensuring it meets stringent safety requirements.
Built-In Safety Mechanisms
- Thermal Overload Protection: Prevents overheating by tripping when the motor draws too much current.
- Magnetic Short Circuit Protection: Quickly isolates faults to prevent damage to the motor and electrical system.
- Phase Loss Protection: Protects the motor in case of phase loss, reducing the risk of motor damage.
Maintenance and Troubleshooting
Regular maintenance ensures the continued effective operation of the Schneider GV2P08.
Regular Maintenance Practices
- Visual Inspection: Regularly check for signs of wear or damage.
- Testing: Periodically test the breaker to ensure it functions correctly.
- Cleaning: Keep the breaker and surrounding area clean and free of dust.
Common Troubleshooting Tips
- Frequent Tripping: This may indicate an overload condition; verify that the connected load is within the breaker’s rated capacity.
- Loose Connections: Check and tighten any loose wire connections to prevent arcing and potential faults.
Customer Support and Warranty
Schneider Electric offers robust customer support and warranty services for the GV2P08.
Warranty Coverage
The GV2P08 comes with a manufacturer’s warranty covering defects in materials and workmanship for a specified period.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | TeSys Deca |
|---|---|
| Product name | TeSys GV2 TeSys Deca |
| product or component type | Motor circuit breaker |
| Device short name | GV2P |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| poles description | 3P |
|---|---|
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
| Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 2 x M4 screws) |
| Motor power kW | 1.1 kW at 400/415 V AC 50/60 Hz 1.5 kW at 500 V AC 50/60 Hz 2.2 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 4 A |
| Thermal protection adjustment range | 2.5…4 A conforming to IEC 60947-4-1 |
| Magnetic tripping current | 51 A |
| [Ith] conventional free air thermal current | 4 A conforming to IEC 60947-4-1 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 § 7-1-6 |
| Power dissipation per pole | 2.5 W |
| Mechanical durability | 100000 cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In |
| Rated duty | Continuous conforming to IEC 60947-4-1 |
| Tightening torque | 1.7 N.m - on screw clamp terminal |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 97 mm |
| Colour | Dark grey |
| Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 |
|---|---|
| Product certifications | CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV RINA DNV-GL UKCA |
| IK degree of protection | IK04 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Climatic withstand | Conforming to IACS E10 |
| ambient air temperature for storage | -40…80 °C |
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient air temperature for operation | -20…60 °C |
| Mechanical robustness | Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz |
| Operating altitude | 2000 m |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.800 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 10.200 cm |
| Package 1 Weight | 324.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.756 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 114.912 kg |
| Warranty | 18 months |
|---|
Reviews