Schneider A9N61517 | miniature circuit breaker – C60H – 1 pole – 40 A – C curve
Schneider A9N61517 | miniature circuit breaker – C60H – 1 pole – 40 A – C curve
Description
Schneider A9N61517 | miniature circuit breaker – C60H – 1 pole – 40 A – C curve
. Technical Specifications A9N61517
-
Manufacturer: Schneider Electric
-
Model Number: A9N61517
-
Series: Acti9 C60H
-
Device Type: Miniature Circuit Breaker (MCB)
-
Number of Poles: 1 Pole
-
Rated Current: 40 Amperes
-
Tripping Curve: Type C (C Curve)
-
Rated Operational Voltage: Up to 240/415V AC
-
Supported Phase: Single-phase
-
Degree of Protection: IP20 (when installed in a distribution board)
-
Breaking Capacity: 6 kA (according to IEC/EN 60898-1)
-
Mounting: DIN rail compatible
-
Operating Temperature Range: -25°C to +60°C
-
Width: 18 mm (single module size)
. Key Features
-
Overcurrent and Short-Circuit Protection: Offers fast and accurate protection for electrical circuits and appliances.
-
High Breaking Capacity: Can safely interrupt fault currents up to 6 kA without damage.
-
Compact Design: Slim and space-saving, suitable for modern distribution boards.
-
C Curve Response: Ideal for loads with moderate inrush currents like lighting and small motors.
-
Quick and Easy Installation: Designed for tool-free DIN rail mounting.
-
Durable and Reliable: Made from high-quality materials ensuring long service life.
-
Standards Compliance: Fully compliant with IEC 60898-1 for domestic and similar installations.
-
Thermal and Magnetic Trip Elements: Ensures both overload and fault protection.
. Applications
-
Residential Buildings: Circuit protection for lighting, outlets, air conditioners, etc.
-
Commercial Facilities: Offices, hotels, and retail stores where safe and reliable protection is needed.
-
Light Industrial Use: Protects control panels and small motors in workshops and production units.
-
Sub-Distribution Boards: Efficient for segmenting power supply in larger systems.
-
Solar and Smart Home Systems: Offers dependable protection for modern renewable energy installations.
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range | Acti9 |
|---|---|
| Product name | Acti9 C60H-DC |
| Product or component type | Miniature circuit-breaker |
| Device short name | C60H-DC |
| Device application | Distribution |
| Poles description | 1P |
| Number of protected poles | 1 |
| [In] rated current | 40 A at 25 °C |
| Network type | DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Breaking capacity | 10 kA Icu at 220 V DC conforming to EN 60947-2 10 kA Icu at 220 V DC conforming to IEC 60947-2 6 kA Icu at 250 V DC conforming to EN 60947-2 6 kA Icu at 250 V DC conforming to IEC 60947-2 20 kA Icu at 110 V DC conforming to EN 60947-2 20 kA Icu at 110 V DC conforming to IEC 60947-2 |
| Utilisation category | Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2 |
| Suitability for isolation | Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2 |
| Network frequency | 50/60 Hz |
|---|---|
| [Ue] rated operational voltage | 250 V DC |
| [Ics] rated service breaking capacity | 15 kA 75 % conforming to EN 60947-2 - 110 V DC 15 kA 75 % conforming to IEC 60947-2 - 110 V DC 4.5 kA 75 % conforming to EN 60947-2 - 250 V DC 4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN 60947-2 - 220 V DC 7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC |
| [Ui] rated insulation voltage | 500 V DC conforming to IEC 60947-2 500 V DC conforming to EN 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 |
| Contact position indicator | Yes |
| control type | Toggle |
| local signalling | ON/OFF indication |
| Mounting mode | Fixed |
| mounting support | 35 mm symmetrical DIN rail |
| Comb busbar and distribution block compatibility | Top or bottom: standard |
| 9 mm pitches | 2 |
| Net weight | 0.128 kg |
| Colour | White |
| Mechanical durability | 20000 cycles |
| Electrical durability | 3000 cycles L/R = 2 ms |
| Provision for padlocking | Padlockable |
| Locking options description | In position O |
| Tightening torque | Power circuit: 2.5 N.m top or bottom |
| earth-leakage protection | Without |
| Standards | EN 60947-2 IEC 60947-2 |
|---|---|
| Pollution degree | 3 conforming to EN 60947-2 3 conforming to IEC 60947-2 |
| Overvoltage category | IV |
| Tropicalisation | 2 conforming to IEC 60068-2 |
| Operating altitude | 2000 m |
| Ambient air temperature for operation | -25…70 °C |
| Ambient air temperature for storage | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.0 cm |
| Package 1 Width | 1.8 cm |
| Package 1 Length | 8.5 cm |
| Package 1 Weight | 122.0 g |
| Warranty | 18 months |
|---|
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider A9N61510 | miniature circuit breaker – C60H – 1 pole – 15 A – C curve
Schneider A9N61502 | miniature circuit breaker – C60H – 1 pole – 2 A – C curve
Schneider A9N61501 | miniature circuit breaker – C60H – 1 pole – 1 A – C curve
-
0
Schneider A9N18470 | Miniature circuit-breaker, Acti9 C120H, 3P, 125 A, C curve, 15000 A (IEC 60898-1), 15 kA (IEC 60947-2)
-
0
Reviews
There are no reviews yet.