Schneider ATV610D45N4 | variable speed drive, Easy Altivar 610, 45kW, 60hp, 380 to 460V, IP20
Schneider ATV610D45N4 | variable speed drive, Easy Altivar 610, 45kW, 60hp, 380 to 460V, IP20
Description
Schneider ATV610D45N4 | variable speed drive, Easy Altivar 610, 45kW, 60hp, 380 to 460V, IP20
Technical Specifications
The Schneider ATV610D45N4 features advanced technical specifications, ensuring reliability and high efficiency. It operates with an input frequency of 50/60 Hz and has an IP20 protection rating, which safeguards it from dust and environmental factors.
The drive includes an LCD display with integrated control buttons, making it easy to monitor and adjust settings. It can be wall-mounted or installed within control panels, providing flexibility in different industrial setups.
Key Features
1. Energy Efficiency Optimization
The drive is engineered to reduce energy consumption by optimizing motor performance, making it a cost-effective solution for industrial applications.
2. Compatibility with Modern Control Systems
It supports multiple industrial communication protocols such as Modbus and CANopen, allowing seamless integration into advanced automation and control systems.
3. Advanced Protection and Safety Features
The ATV610D45N4 includes overload protection, short-circuit protection, and thermal management, ensuring extended device lifespan and minimizing downtime due to faults.
4. User-Friendly Operation and Programming
Equipped with an intuitive user interface, this drive allows easy configuration and speed adjustment. Pre-programmed settings can be customized to meet specific operational requirements.
5. Precise Speed Control
The drive supports multiple speed control methods, including V/F control and vector control, providing enhanced motor performance and accurate speed regulation.
Applications
The Schneider ATV610D45N4 is widely used across various industries, including:
-
Heavy Industry: Controls motors in production lines and manufacturing plants.
-
Pumping Systems: Regulates water flow in treatment plants and distribution networks.
-
Ventilation Systems: Manages fan operations in commercial and industrial facilities.
-
Material Handling: Operates conveyor belts and elevators efficiently.
-
Power Plants: Enhances generator performance and motor speed regulation in energy systems
Additional information
| brands | Schneider Electric |
|---|
Specifications
| Range of product | Easy Altivar 610 |
|---|---|
| Product or component type | Variable speed drive |
| Product specific application | Fan, pump, compressor, conveyor |
| Device short name | ATV610 |
| variant | Standard version |
| product destination | Asynchronous motors Synchronous motors |
| Mounting mode | Cabinet mount |
| EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
| IP degree of protection | IP20 |
| Type of cooling | Forced convection |
| Supply frequency | 50...60 Hz +/-5 % |
| Network number of phases | 3 phases |
| [Us] rated supply voltage | 380...460 V - 15...10 % |
| Motor power kW | 45 kW for normal duty 37 kW for heavy duty |
| Motor power hp | 60 hp for normal duty 50 hp for heavy duty |
| Line current | 92.9 A at 380 V (normal duty) 82.7 A at 460 V (normal duty) 80.5 A at 380 V (heavy duty) 69.6 A at 460 V (heavy duty) |
| Prospective line Isc | 22 kA |
| Apparent power | 65.9 kVA at 460 V (normal duty) 55.4 kVA at 460 V (heavy duty) |
| Continuous output current | 88 A at 4 kHz for normal duty 75 A at 4 kHz for heavy duty |
| Maximum transient current | 97 A during 60 s (normal duty) 112 A during 60 s (heavy duty) |
| Asynchronous motor control profile | Optimized torque mode Constant torque standard Variable torque standard |
| Output frequency | 0.1…500 Hz |
| Nominal switching frequency | 4 kHz |
| Switching frequency | 2...12 kHz adjustable |
| number of preset speeds | 16 preset speeds |
| Communication port protocol | Modbus serial |
| Option card | Slot A: communication card, Profibus DP V1 Slot A: digital or analog I/O extension card Slot A: relay output card |
| Output voltage | <= power supply voltage |
|---|---|
| Motor slip compensation | Automatic whatever the load Adjustable Not available in permanent magnet motor law Can be suppressed |
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s S, U or customized |
| Braking to standstill | By DC injection |
| Protection type | Thermal protection: motor Motor phase break: motor Thermal protection: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive |
| Frequency resolution | Display unit: 0.1 Hz Analog input: 0.012/50 Hz |
| Electrical connection | Control, screw terminal: 0.5...1.5 mm² Line side, screw terminal: 35...50 mm² Motor, screw terminal: 50 mm² |
| Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
| Physical interface | 2-wire RS 485 for Modbus serial |
| Transmission frame | RTU for Modbus serial |
| Transmission rate | 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
| Type of polarization | No impedance for Modbus serial |
| Number of addresses | 1…247 for Modbus serial |
| Method of access | Slave |
| Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
| Local signalling | 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage |
| Width | 226 mm |
| Height | 613 mm 706 mm with EMC plate |
| Depth | 271 mm |
| Net weight | 25.5 kg |
| Analogue input number | 3 |
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI2, AI3 software-configurable temperature probe or water level sensor |
| Discrete input number | 6 |
| Discrete input type | DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
| Input compatibility | DI1...DI6: logic input level 1 PLC conforming to IEC 61131-2 DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68 |
| Discrete input logic | Positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1) Negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1) Positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1) |
| Analogue output number | 2 |
| Analogue output type | Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Sampling duration | 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input 5 ms +/- 1 ms (DI5, DI6)configurable - pulse input 10 ms +/- 1 ms (AQ1, AQ2) - analog output |
| Accuracy | +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output |
| Linearity error | AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output |
| Relay output number | 3 |
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
| Refresh time | Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) |
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
| Isolation | Between power and control terminals |
| Insulation resistance | > 1 MOhm 500 V DC for 1 minute to earth |
| Noise level | 75 dB conforming to 86/188/EEC |
|---|---|
| Power dissipation in W | 1000 W(forced convection) at 380 V, switching frequency 4 kHz 121 W(natural convection) at 380 V, switching frequency 4 kHz |
| Volume of cooling air | 240 m3/h |
| Operating position | Vertical +/- 10 degree |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60068-2-27 |
| Relative humidity | 5…95 % without condensation conforming to IEC 60068-2-3 |
| Ambient air temperature for operation | -15…45 °C (without derating) 45…60 °C (with derating factor) |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | <= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m |
| Environmental characteristic | Chemical pollution resistance class 3C3 conforming to IEC 60721-3-3 Dust pollution resistance class 3S3 conforming to IEC 60721-3-3 |
| Standards | IEC 61800-3 Environment 2 category C3 IEC 61800-3 IEC 61800-5-1 IEC 60721-3 |
| Marking | CE |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 34.000 cm |
| Package 1 Width | 52.000 cm |
| Package 1 Length | 73.000 cm |
| Package 1 Weight | 30.200 kg |
Main Document
Main Document
Data Sheet : Download
Main Document
Data Sheet : Download
Reviews (0)
Recommended for you
Schneider NSYSFC106 | Spacial SF bottom and top frame – 1000×600 mm
Schneider NSYSFD208 | Spacial SF plain door – 2000×800 mm
Schneider NSYBP208 | Spacial SF rear panel external fixing – 2000×800 mm
Schneider NSYSM1612402D | PanelSeT SM compact enclosure without mounting plate – 1600x1200x400 mm
Schneider NSYSM16840 | Spacial SM compact enclosure without mounting plate – 1600x800x400 mm
-
0
Reviews
There are no reviews yet.